Part 9

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from Part 9 — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as Part 9 — Pro

9.1. — General

Content not available for this version.

9.1.1. — Application

Content not available for this version.

9.1.1.1. — Scope

(1) The scope of this Part shall be as described in Subsection 1.1.2. of Division A.

Text · e-Laws consolidated snapshot

9.1.1.2. — Signs

(1) Signs shall conform to the requirements in Section 3.15.

Text · e-Laws consolidated snapshot

9.1.1.3. — Self-Service Storage Buildings

(1) Self-service storage buildings shall conform to the requirements in Section 3.10.

Text · e-Laws consolidated snapshot

9.1.1.4. — Tents and Air-Supported Structures

(1) Tents shall conform to the requirements in Subsection 3.14.1.

(2) Air-supported structures shall conform to the requirements in Subsection 3.14.2.

Text · e-Laws consolidated snapshot

9.1.1.5. — Proximity to Existing Above Ground Electrical Conductors

(1) Where a building is constructed in close proximity to existing above ground electrical conductors the requirements of Subsection 3.1.19. shall apply.

Text · e-Laws consolidated snapshot

9.1.1.6. — Food Premises

(1) The requirements of Subsection 3.7.6. apply to all food premises.

Text · e-Laws consolidated snapshot

9.1.1.7. — Radon

(1) In addition to all other requirements, a building in the following designated areas shall be designed and constructed so that the annual average concentration of radon 222 does not exceed 250 millibecquerels per litre of air and the annual average concentration of the short lived daughters of radon 222 does not exceed 0.02 working levels inside the building for,

(a) the Town of Elliot Lake in the Territorial District of Algoma,

(b) the Township of Faraday in the County of Hastings, and

(c) the geographic Township of Hyman in the Territorial District of Sudbury.

Text · e-Laws consolidated snapshot

9.1.1.8. — Building in Flood Plains

(1) Buildings constructed on flood plains shall,

(a) be designed and constructed in accordance with good engineering practice to withstand anticipated vertical and horizontal hydrostatic pressures acting on the structure, and

(b) incorporate floodproofing measures that will preserve the integrity of exits and means of egress during times of flooding.

Text · e-Laws consolidated snapshot

9.1.1.9. — Site Assembled and Factory-Built Buildings

(1) Except as provided in Sentence (2), a manufactured building intended for residential occupancy is deemed to comply with this Code if it is designed and constructed in compliance with,

(a) CAN/CSA-Z240.2.1, “Structural Requirements for Mobile Homes”, and CAN/CSA-Z240.3.1, “Plumbing Requirements for Mobile Homes”, if the building is constructed in Sections not wider than 4.88 m, or

(b) CAN/CSA-A277, “Procedure for Certification of Factory-Built Houses”.

(2) The requirements of this Code shall apply to,

(a) building components designed and constructed outside the place of manufacture, and

(b) site installation of such buildings.

Text · e-Laws consolidated snapshot

9.1.1.10. — 9.1.1.10.

Not in force at this date.

9.1.1.11. — 9.1.1.11.

Not in force at this date.

9.2. — Reserved

Content not available for this version.

9.3. — Materials, Systems and Equipment

Content not available for this version.

9.3.1. — Concrete

Content not available for this version.

9.3.1.1. — General

(1) Except as provided in Sentence (2), nominally unreinforced concrete shall be designed, mixed, placed, cured and tested in accordance with CAN/CSA-A438, “Concrete Construction for Housing and Small Buildings”.

(2) Nominally unreinforced site-batched concrete shall be designed, mixed, placed and cured in accordance with Articles 9.3.1.2. to 9.3.1.9.

(3) Except as provided in Sentence (4), reinforced concrete shall be designed to conform to the requirements of Part 4.

(4) For flat insulating concrete form walls not exceeding 2 storeys, and having a maximum floor to floor height of 3 m, in buildings of light frame construction containing only a single dwelling unit, the concrete and reinforcing shall comply with Part 4 or,

(a) concrete shall conform to CAN/CSA-A23.1, “Concrete Materials and Methods of Concrete Construction”, with a maximum aggregate size of 19 mm, and

(b) reinforcing shall,

(i) conform to CAN/CSA-G30.18-M, “Billet Steel Bars for Concrete Reinforcement”,

(ii) have a minimum specified yield strength of 400 MPa, and

(iii) be lapped a minimum of 450 mm for 10M bars and 650 mm for 15 mm bars.

Text · e-Laws consolidated snapshot

9.3.1.2. — Cement

(1) Cement shall meet the requirements of CAN/CSA-A3001, “Cementitious Materials for Use in Concrete”.

Text · e-Laws consolidated snapshot

9.3.1.3. — Concrete in Contact with Sulfate Soil

(1) Concrete in contact with sulfate soil, which is deleterious to normal cement, shall conform to the requirements in Clause 15.5 of CAN/CSA-A23.1, “Concrete Materials and Methods of Concrete Construction”.

Text · e-Laws consolidated snapshot

9.3.1.4. — Aggregates

(1) Aggregates shall,

(a) consist of sand, gravel, crushed rock, crushed air-cooled blast furnace slag, expanded shale or expanded clay conforming to CAN/CSA-A23.1, “Concrete Materials and Methods of Concrete Construction”, and

(b) be clean, well-graded and free of injurious amounts of organic and other deleterious material.

Text · e-Laws consolidated snapshot

9.3.1.5. — Water

(1) Water shall be clean and free of injurious amounts of oil, organic matter, sediment or any other deleterious material.

Text · e-Laws consolidated snapshot

9.3.1.6. — Compressive Strength

(1) Except as provided elsewhere in this Part, the compressive strength of unreinforced concrete after 28 days shall be not less than,

(a) 32 MPa for garage floors, carport floors and all exterior flatwork,

(b) 20 MPa for interior floors other than those for garages and carports, and

(c) 15 MPa for all other applications.

(2) Concrete used for garage and carport floors and exterior steps shall have air entrainment of 5 to 8%.

Text · e-Laws consolidated snapshot

9.3.1.7. — Concrete Mixes

(1) For site-batched concrete, the concrete mixes described in Table 9.3.1.7. shall be considered acceptable if the ratio of water to cementing materials does not exceed,

(a) 0.45 for garage floors, carport floors and all exterior flatwork,

(b) 0.65 for interior floors other than those for garages and carports, and

(c) 0.70 for all other applications.

(2) The size of aggregate in unreinforced concrete mixes referred to in Sentence (1) shall not exceed,

(a) 1/5 the distance between the sides of vertical forms, or

(b) 1/3 the thickness of flatwork.

(1) A 40 kg bag of cement contains 28 L.

Text · e-Laws consolidated snapshot

Table 9.3.1.7. Concrete Mixes Forming Part of Sentence 9.3.1.7.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Maximum Size of Course Aggregate, mm

Materials, volume

Cement

Fine Aggregate (damp average course sand)

Course Aggregate (gravel or crushed stone)

Parts

L(1)

Parts

L

Parts

L

14

1

28

1.75

49

2

56

20

1

28

1.75

49

2.5

70

28

1

28

2

56

3

84

40

1

28

2

56

3.5

98

Notes to Table 9.3.1.7.:

9.3.1.8. — Admixtures

(1) Admixtures shall conform to ASTM C260, “Air-Entraining Admixtures for Concrete”, or ASTM C494 / C494M, “Chemical Admixtures for Concrete”, as applicable.

Text · e-Laws consolidated snapshot

9.3.1.9. — Cold Weather Requirements

(1) When the air temperature is below 5°C , concrete shall be,

(a) kept at a temperature of not less than 10°C or more than 25°C while being placed, and

(b) maintained at a temperature of not less than 10°C for 72 h after placing.

(2) No frozen material or ice shall be used in concrete described in Sentence (1).

Text · e-Laws consolidated snapshot

9.3.2. — Lumber and Wood Products

Content not available for this version.

9.3.2.1. — Grade Marking

(1) Lumber for joists, rafters, trusses and beams and for the uses listed in Table 9.3.2.1. shall be identified by a grade stamp to indicate its grade as determined by the NLGA, “Standard Grading Rules for Canadian Lumber (Interpretation Included)”.

Text · e-Laws consolidated snapshot

Table 9.3.2.1. Minimum Lumber Grades for Specific End Uses Forming Part of Sentence 9.3.2.1.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Use

Boards

Framing

Paragraph in the NLGA Grading Rules Under Which Boards are Graded

All Species

Eastern White

Pine & Red Pine

All Species

Para 113

Para 114

Para 118

Stud wall framing (loadbearing members)

Stud, Standard, No. 2

Stud wall framing (non-loadbearing members)

Stud, Utility, No. 3

Plank frame construction (loadbearing members)

No. 3 Common

No. 3 Common

No. 2

Plank frame construction (non-loadbearing members)

No. 5 Common

No. 5 Common

Economy, No 3

Post and beams less than 114 mm in thickness

Standard, No.2

Post and beams not less than 114 mm in thickness

Standard

Roof sheathing

No. 3 Common

Standard

No. 4 Common

Subflooring

No. 3 common

Standard

No. 3 Common

Wall sheathing when required as a nailing base

No. 4 Common

Utility

No. 4 Common

Wall sheathing not required as a nailing base

No. 5 Common

Economy

No. 5 Common

9.3.2.2. — Lumber Grades

(1) Except for joists, rafters, trusses and beams, visually graded lumber shall conform to the grades in Table 9.3.2.1.v1

Text · e-Laws consolidated snapshot

9.3.2.3. — Machine Stress Rated Lumber

(1) Machine stress rated lumber shall conform to the requirements of Subsection 4.3.1.

Text · e-Laws consolidated snapshot

9.3.2.4. — OSB, Waferboard and Plywood Marking

(1) OSB, waferboard and plywood used for roof sheathing, wall sheathing and subflooring shall be legibly identified on the face of the material indicating,

(a) the manufacturer of the material,

(b) the standard to which it is produced, and

(c) that the material is of an exterior type.

Text · e-Laws consolidated snapshot

9.3.2.5. — Moisture Content

(1) Moisture content of lumber shall be not more than 19% at the time of installation.

Text · e-Laws consolidated snapshot

9.3.2.6. — Lumber Dimensions

(1) Lumber dimensions referred to in this Part are actual dimensions determined in conformance with CSA O141, “Softwood Lumber”.

Text · e-Laws consolidated snapshot

9.3.2.7. — Panel Thickness Tolerances

(1) The thickness specified in this Part for plywood, hardboard, particleboard, OSB and waferboard shall be subject to the tolerances permitted in the standards referenced for these products unless specifically indicated in this Part.

Text · e-Laws consolidated snapshot

9.3.2.8. — Undersized Lumber

(1) Joist, rafter, lintel and beam members up to 5% less than the actual Canadian standard sizes are permitted to be used provided the allowable spans for the grade and species of lumber under consideration are reduced 5% from those shown in the span tables for full size members.

Text · e-Laws consolidated snapshot

9.3.2.9. — Termite and Decay Protection

(1) In localities where termites are known to occur,

(a) clearance between structural wood elements and the finished ground level directly below them shall be not less than 450 mm and, except as provided in Sentence (2), all sides of the supporting elements shall be visible to permit inspection, or

(b) structural wood elements, supported by elements in contact with the ground or exposed over bare soil, shall be pressure-treated with a chemical that is toxic to termites.

(2) In localities where termites are known to occur and foundations are insulated or otherwise finished in a manner that could conceal a termite infestation,

(a) a metal or plastic barrier shall be installed through the insulation and any other separation or finish materials above finished ground level to control the passage of termites behind or through the insulation, separation or finish materials, and

(b) all sides of the finish supporting assembly shall be visible to permit inspection.

(3) Structural wood elements shall be pressure-treated with a preservative to resist decay,

(a) where the vertical clearance between structural wood elements and the finished ground level is less than 150 mm, or

(b) where,

(i) the wood elements are not protected from exposure to precipitation, and

(ii) the configuration is conducive to moisture accumulation.

(4) Structural wood elements used in retaining walls and cribbing shall be pressure-treated with a preservative to resist decay, where,

(a) the retaining wall or cribbing supports ground that is critical to the stability of building foundations, or

(b) the retaining wall or cribbing is greater than 1.2 m in height.

(5) Where wood is required by this Article to be treated to resist termites or decay, such treatment shall be in accordance with the requirements of,

(a) CSA O80.1, “Preservative Treatment of All Timber Products by Pressure Processes”,

(b) CSA O80.2, “Preservative Treatment of Lumber, Timber, Bridge Ties and Mine Ties by Pressure Processes”,

(c) CSA O80.9, “Preservative Treatment of Plywood by Pressure Processes”,

(d) CSA O80.15, “Preservative Treatment of Wood for Building Foundation Systems, Basements and Crawl Spaces by Pressure Processes”, or

(e) CSA O80.34, “Pressure Preservative Treatment of Lumber and Timbers with Borates for Use Out of Ground Contact and Continuously Protected from Liquid Water”.

(6) In addition to the requirements of Clause (5)(e), where wood is protected in accordance with CSA O80.34, “Pressure Preservative Treatment of Lumber and Timbers with Borates for Use Out of Ground Contact and Continuously Protected from Liquid Water”, the wood shall be,

(a) protected from direct exposure to moisture during and after the completion of construction, and

(b) separated from permeable supporting materials by a moisture barrier that is resistant to all expected mechanisms of deterioration in the service environment when the vertical clearance to the ground is less than 150 mm.

(7) Wood that is required by this Article to be treated to resist termites or decay shall be identified by a mark to indicate its conformance to the relevant required standard.

Text · e-Laws consolidated snapshot

9.3.3. — Metal

Content not available for this version.

9.3.3.1. — Sheet Metal Thickness

(1) Minimum thicknesses for sheet metal material required in this Part refer to the actual minimum base metal thicknesses measured at any point of the material, and in the case of galvanized steel described in Sentence 9.3.3.2.(1), include the thickness of the galvanizing coating unless otherwise indicated.

Text · e-Laws consolidated snapshot

9.3.3.2. — Galvanized Sheet Steel

(1) Where sheet steel is required to be galvanized, it shall be metallic-coated with zinc or an alloy of 55% aluminium-zinc meeting the requirements of,

(a) ASTM A653 / A653M, “Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvanealed) by the Hot-Dip Process”, or

(b) ASTM A792 / A792M, “Sheet Steel, 55% Aluminum-Zinc Alloy-Coated by the Hot Dip Process”.

(2) Where galvanized sheet steel is intended for use in locations exposed to the weather or as a flashing material, it shall have a zinc coating not less than the G90 (Z275) coating designation or an aluminum-zinc alloy coating not less than the AZM150 coating designation, as referred to in Sentence (1).

Text · e-Laws consolidated snapshot

9.4. — Structural Requirements

Content not available for this version.

9.4.1. — Structural Design Requirements and Application Limitations

Content not available for this version.

9.4.1.1. — General

(1) Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall,

(a) conform to requirements provided elsewhere in this Part,

(b) be designed according to good engineering practice such as provided in the CWC, “Engineering Guide for Wood Frame Construction”, or

(c) be designed according to Part 4 using the loads and deflection and vibration limits specified in,

(i) this Part,

(ii) Part 4.

(2) Where floor framing is designed in accordance with Clause (1)(b) or (c) and where supporting wall framing and fastenings, or footings are designed according to Clause (1)(a), the specified live load on the floor shall not exceed 2.4 kPa.

(3) Location-specific information for structural design, including snow and wind loads and seismic spectral response accelerations, shall be determined according to Supplementary Standard SB-1.

Text · e-Laws consolidated snapshot

9.4.2. — Specified Loads

Content not available for this version.

9.4.2.1. — Application

(1) This Subsection applies to light-frame construction whose wall, floor and roof planes are generally comprised of frames of small repetitive structural members, and where,

(a) the roof and wall planes are clad, sheathed or braced on at least one side,

(b) the small repetitive structural members are spaced not more than 600 mm o.c.,

(c) the clear span of any structural member does not exceed 12.20 m,

(d) the maximum deflection of the structural roof members conforms to Article 9.4.3.1.,

(e) the maximum total roof area, notwithstanding any separation of adjoining buildings by firewalls, is 4 550 m2, and

(f) for flat roofs, there are no significant obstructions on the roof, such as parapet walls, spaced closer than the distance calculated by,

Do = 10(Ho – 0.8 Ss/γ)

where,

Do = minimum distance between obstructions, m,

Ho = height of the obstruction above the roof, m,

Ss = ground snow load, kPa, and

γ = unit weight of snow, kN/m3.

Text · e-Laws consolidated snapshot

9.4.2.2. — Specified Design Snow Loads

(1) Except as provided in Sentences (2) and (3), specified snow loads shall be not less than those calculated using the following formula:

S = Cb ∙ Ss + Sr

where,

S = specified snow load,

Cb = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and 0.55 for all other roofs,

Ss = 1-in-50 year ground snow load in kPa, determined according to Supplementary Standard SB-1, and

Sr = associated 1-in-50 year rain load in kPa, determined according to Supplementary Standard SB-1.

(2) In no case shall the specified snow load be less than 1 kPa.

(3) Bow string, arch or semi-circular roof trusses having an unsupported span greater than 6 m shall be designed in conformance with the snow load requirements in Subsection 4.1.6.

Text · e-Laws consolidated snapshot

9.4.2.3. — Platforms Subject to Snow and Occupancy Loads

(1) Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit.

Text · e-Laws consolidated snapshot

9.4.2.4. — Attics and Roof Spaces

(1) Ceiling joists or truss bottom chords in residential attic or roof spaces shall be designed for a total specified load of not less than 0.35 kPa, where the total specified load is the sum of the specified dead load plus the specified live load of the ceiling and where,

(a) the attic or roof spaces have limited accessibility that precludes the storage of equipment or material, and

(b) the maximum attic height is not more than 1 000 mm measured vertically from the top of the truss bottom chord to the underside of the roof deck.

Text · e-Laws consolidated snapshot

9.4.3. — Deflections

Content not available for this version.

9.4.3.1. — Deflections

(1) The maximum deflection of structural members shall conform to Table 9.4.3.1.

(2) Dead loads need not be considered in computing deflections referred to in Sentence (1).

Text · e-Laws consolidated snapshot

Table 9.4.3.1. Maximum Deflections Forming Part of Sentence 9.4.3.1.(1)

Column 1

Column 2

Column 3

Structural Members

Type of Ceiling Supported

Max. Allowable Deflection as an Expressed Ratio of the Clear Span

Roof rafters, roof joists and roof beams

No ceiling

1/180

Other than plaster or gypsum board

1/240

Plaster or gypsum board

1/360

Ceiling joists

Other than plaster or gypsum board

1/240

Plaster or gypsum board

1/360

Floor beams, floor joists and floor decking

All cases

1/360

Beams, joists and decking for balconies, decks and other accessible exterior platforms

Serving a single dwelling unit

1/240

Other

1/360

9.4.4. — Foundation Conditions

Content not available for this version.

9.4.4.1. — Allowable Bearing Pressures

(1) Footing sizes for shallow foundations shall be,

(a) determined in accordance with Section 9.15., or

(b) designed in accordance with Section 4.2. using,

(i) the maximum allowable bearing pressures in Table 9.4.4.1., or

(ii) allowable bearing pressures determined from subsurface investigation.

(2) The design procedures described in Section 4.2. are permitted to be used in lieu of the design procedures in this Subsection.

(3) The design procedures described in Section 4.2. shall be used where,

(a) deep foundations are used,

(b) the footing size falls outside the scope of this Section, or

(c) the foundation is constructed on peat, filled ground or on sensitive clays as described in Article 9.15.1.1.v1v2

Text · e-Laws consolidated snapshot

Table 9.4.4.1. Allowable Bearing Pressure for Soil or Rock Forming Part of Sentence 9.4.4.1.(1)

Column 1

Column 2

Type and Condition of Soil or Rock

Maximum Allowable Bearing Pressure, kPa

Dense or compact sand or gravel

150

Loose sand or gravel

50

Dense or compact silt

100

Stiff clay

150

Firm clay

75

Soft clay

40

Till

200

Clay shale

300

Sound rock

500

9.4.4.2. — Foundation Capacity in Weaker Soil and Rock

(1) Where a soil or rock within a distance equal to twice the footing width below the bearing surface has a lower allowable bearing pressure than that at the bearing surface as shown in Article 9.4.4.1., the design capacity of the foundation shall not be greater than would cause the weakest soil or rock to be stressed beyond its allowable bearing pressure.

(2) In calculating subsurface pressures referred to in Sentence (1), the loads from the footings shall be assumed to be distributed uniformly over a horizontal plane within a frustum extending downward from the footing at an angle of 60° to the horizontal.

Text · e-Laws consolidated snapshot

9.4.4.3. — High Water Table

(1) Where a foundation bears on gravel, sand or silt, and the water table is within a distance below the bearing surface equal to the width of the foundation, the allowable bearing pressure shall be 50% of that determined in Article 9.4.4.1.

Text · e-Laws consolidated snapshot

9.4.4.4. — Soil Movement

(1) Where a foundation is located in an area where soil movement caused by changes in soil moisture content, freezing, or chemical-microbiological oxidation is known to occur to the extent that it will damage a building, measures shall be taken to preclude such movement or to reduce the effects on the building so that the building’s stability and the performance of assemblies will not be adversely affected.

(2) Any surcharge shall be in addition to the equivalent fluid pressure specified in Sentence (1).

Text · e-Laws consolidated snapshot

9.4.4.5. — Reserved

Content not available for this version.

9.4.4.6. — Wall Supporting Drained Earth

(1) Except where constructed in accordance with Section 9.15., walls supporting drained earth shall be designed,

(a) for a pressure equivalent to that exerted by a fluid with a density of not less than 480 kg/m3 and a depth equal to that of the retained earth, or

(b) in accordance with Section 4.2. so as to be able to resist the loads and effects described in Article 4.1.2.1.

(2) Walls supporting other than drained earth shall be designed,

(a) for the pressure described in Clause 1(a) plus the fluid pressure of the surcharge, or

(b) in accordance with Section 4.2. so as to be able to resist the loads, forces and effects described in Article 4.1.2.1.

Editor's note

As filed in O. Reg. 350/06, Clause (2)(a) cites 'Clause 1(a)', without parentheses around the sentence number; the consolidated e-Laws text renders it in the standard form 'Clause (1)(a)'. No amending regulation makes this change; the as-filed wording is retained here.

9.5. — Design of Areas and Spaces

Content not available for this version.

9.5.1. — General

Content not available for this version.

9.5.1.1. — Application

(1) Unless otherwise specifically indicated, this Section applies only to dwelling units that are intended for use on a continuing or year-round basis as the principal residence of the occupant.

Text · e-Laws consolidated snapshot

9.5.1.2. — Method of Measurement

(1) Unless otherwise indicated in this Part, the areas, dimensions and heights of rooms or spaces shall be measured between finished wall surfaces and between finished floor and ceiling surfaces.

Text · e-Laws consolidated snapshot

9.5.1.3. — Floor Areas

(1) Minimum floor areas specified in this Section do not include closets or built-in bedroom cabinets unless otherwise indicated.

Text · e-Laws consolidated snapshot

9.5.1.4. — Combination Rooms

(1) Two or more areas may be considered as a combination room if the opening between the areas occupies the larger of 3 m2 or 40% or more of the wall measured on the side of the dependent area.

(2) Where the dependent area is a bedroom, direct passage shall be provided between the two areas.

(3) The opening required in Sentence (1) shall not contain doors or windows.

Text · e-Laws consolidated snapshot

9.5.1.5. — Lesser Areas and Dimensions

(1) Areas of rooms and spaces are permitted to be less than required in this Section provided it can be shown that the rooms and spaces are adequate for their intended use, such as by the provision of built-in furniture to compensate for reduced sizes.

Text · e-Laws consolidated snapshot

9.5.2. — Barrier-Free Design

Content not available for this version.

9.5.2.1. — General

(1) Except as provided in Sentence (2) and Article 3.8.1.1., every building shall be designed in conformance with Section 3.8.

(2) The requirements of Section 3.8. need not be provided for houses including semi-detached houses, duplexes, triplexes, town houses, row houses and boarding, or rooming houses with fewer than 8 boarders or roomers.

Text · e-Laws consolidated snapshot

9.5.2.2. — Protection on Floor Areas with a Barrier-Free Path of Travel

(1) Where a barrier-free path of travel required in Article 9.5.2.1. is provided to any storey above the first storey, the requirements in Article 3.3.1.7.v1 shall apply.

Text · e-Laws consolidated snapshot

9.5.2.3. — Stud Wall Reinforcement

(1) If wood wall studs or sheet steel wall studs enclose the main bathroom in a dwelling unit, reinforcement shall be installed to permit the future installation of a grab bar on a wall adjacent to,

(a) a water closet in the location required by Clause 3.8.3.8.(1)(d)v1, and

(b) a shower or bathtub in the location required by Clause 3.8.3.13.(1)(f).

Text · e-Laws consolidated snapshot

9.5.3. — Ceiling Heights

Content not available for this version.

9.5.3.1. — Ceiling Heights of Rooms or Spaces

(1) The ceiling heights of rooms or spaces in residential occupancies and live/work units shall conform to Table 9.5.3.1.

(2) Areas in rooms or spaces over which ceiling height is not less than the minimum specified in Table 9.5.3.1. shall be contiguous with the entry or entries to those rooms or spaces.

Editor's note

In the notes to Table-9.5.3.1., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.5.3.1. Room Ceiling Heights Forming Part of Sentences 9.5.3.1.(1) and (2)

Column 1

Column 2

Room or Space

Minimum Heights(1)

Living room or space, dining room or space, kitchen or kitchen space

2 300 mm over at least 75 per cent of the required floor area with a clear height of 2 100 mm at any point over the required area

Bedroom or bedroom space

2 300 mm over at least 50 per cent of the required area or 2 100 mm over all of the required floor area. Any part of the floor having a clear height of less than 1 400 mm shall not be considered in computing the required floor area.

Basement space

2 100 mm over at least 75 per cent of the basement area except that under beams and ducts the clearance is permitted to be reduced to 1 950 mm

Bathroom, water closet room or laundry area above grade

2 100 mm in any area where a person would normally be in a standing position

Passage, hall or main entrance vestibule and finished rooms not specifically mentioned above

2 100 mm

Notes to Table 9.5.3.1.:

(1)Area of the space shall be measured at floor level.

9.5.3.2. — Mezzanines

(1) The ceiling height above and below a mezzanine floor assembly in all occupancies shall be not less than 2 100 mm.

Text · e-Laws consolidated snapshot

9.5.3.3. — Storage Garages

(1) The clear height in a storage garage shall be not less than 2 000 mm.

Text · e-Laws consolidated snapshot

9.5.4. — Living Rooms or Spaces Within Dwelling Units

Content not available for this version.

9.5.4.1. — Areas of Living Rooms and Spaces

(1) Living areas within dwelling units, either as separate rooms or in combination with other spaces, shall have an area not less than 13.5 m².

(2) Where the area of a living space is combined with a kitchen and dining area, the living area alone in a dwelling unit that contains sleeping accommodation for not more than 2 persons shall be not less than 11 m².

Text · e-Laws consolidated snapshot

9.5.5. — Dining Rooms or Spaces Within Dwelling Units

Content not available for this version.

9.5.5.1. — Area of Dining Rooms or Spaces

(1) A dining space in combination with other space shall have an area of not less than 3.25 m².

(2) Dining rooms not combined with other space shall have a minimum area of 7 m².

Text · e-Laws consolidated snapshot

9.5.6. — Kitchens Within Dwelling Units

Content not available for this version.

9.5.6.1. — Kitchen Areas

(1) Kitchen areas within dwelling units either separate from or in combination with other spaces, shall have an area of not less than 4.2 m² including the area occupied by the base cabinets, except that in dwelling units containing sleeping accommodation for not more than 2 persons, the minimum area shall be 3.7 m².

Text · e-Laws consolidated snapshot

9.5.7. — Bedrooms or Spaces in Dwelling Units and Dormitories

Content not available for this version.

9.5.7.1. — Areas of Bedrooms

(1) Except as provided in Articles 9.5.7.2. and 9.5.7.3., bedrooms in dwelling units shall have an area not less than 7 m² where built-in cabinets are not provided and not less than 6 m² where built-in cabinets are provided.

Text · e-Laws consolidated snapshot

9.5.7.2. — Areas of Master Bedrooms

(1) Except as provided in Article 9.5.7.3., at least one bedroom in every dwelling unit shall have an area of not less than 9.8 m² where built-in cabinets are not provided and not less than 8.8 m² where built-in cabinets are provided.

Text · e-Laws consolidated snapshot

9.5.7.3. — Areas of Combination Bedrooms

(1) Bedroom spaces in combination with other spaces in dwelling units shall have an area not less than 4.2 m².

Text · e-Laws consolidated snapshot

9.5.7.4. — Areas of Other Sleeping Rooms

(1) Sleeping rooms other than in dwelling units shall have an area not less than 7 m² per person for single occupancy and 4.6 m² per person for multiple occupancy.

Text · e-Laws consolidated snapshot

9.5.7.5. — Recreational Camps

(1) Recreational camps shall have an area in the sleeping quarters of at least 3.72 m² per camper or, if double or triple tier bunk units are used, 2.79 m² per camper.

Text · e-Laws consolidated snapshot

9.5.7.6. — Camps for Housing Workers

(1) A camp for housing of workers shall have a minimum area of 3.72 m² per employee in every room used for sleeping purposes.

Text · e-Laws consolidated snapshot

9.5.8. — Combined Spaces

Content not available for this version.

9.5.8.1. — Combined Living, Dining, Bedroom and Kitchen Spaces

(1) Despite Subsections 9.5.4. to 9.5.7., where living, dining, bedroom and kitchen spaces are combined in a dwelling unit that contains sleeping accommodation for not more than 2 persons, the area of the combined spaces shall be not less than 13.5 m2.

Text · e-Laws consolidated snapshot

9.5.9. — Bathrooms and Water Closet Rooms

Content not available for this version.

9.5.9.1. — Space to Accommodate Fixtures

(1) In every dwelling unit an enclosed space of sufficient size shall be provided to accommodate a water closet, lavatory and bathtub or shower stall.

Text · e-Laws consolidated snapshot

9.5.10. — Hallways

Content not available for this version.

9.5.10.1. — Width of Hallway Within Dwelling Unit

(1) The unobstructed width of a hallway within a dwelling unit shall be not less than 860 mm, except that the hallway width is permitted to be 710 mm where,

(a) there are only bedrooms and bathrooms at the end of the hallway furthest from the living area, and

(b) a second exit is provided,

(i) in the hallway near the end furthest from the living area, or

(ii) in each bedroom served by the hallway.

Text · e-Laws consolidated snapshot

9.6. — Doors

Content not available for this version.

9.6.1. — General

Content not available for this version.

9.6.1.1. — Application

(1) This Section applies to doors, to glazed areas in doors and to sidelights for doors.

Text · e-Laws consolidated snapshot

9.6.2. — Required Doors

Content not available for this version.

9.6.2.1. — Doors for Dwelling Units

(1) A door shall be provided at each entrance to a dwelling unit and to each room containing a water closet within a dwelling unit.

Text · e-Laws consolidated snapshot

9.6.3. — Doorway Sizes

Content not available for this version.

9.6.3.1. — Doorway Opening Sizes

(1) Except as provided in Articles 9.6.3.3., 9.9.6.2. and 9.9.6.3., doorway openings within dwelling units shall be designed to accommodate at least the door sizes in Table 9.6.3.1. for swing-type doors or folding doors.

Editor's note

In the notes to Table-9.6.3.1., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.6.3.1. Minimum Size of Door Forming Part of Sentence 9.6.3.1.(1)

Column 1

Column 2

Column 3

At Entrance to:

Minimum Width, mm

Minimum Height, mm

Dwelling unit (required entrance)

810

1 980

Vestibule or entrance hall

Stairs to a floor level that contains a finished space

810

1 980

All doors in at least one line of passage from the exterior to the basement

Utility rooms

Walk-in closet

610

1 980

Bathroom, water closet room, shower room(1)

610

1 980

Rooms located off hallways that are permitted to be 710 mm wide

610

1 980

Rooms not mentioned above, exterior balconies

760

1 980

Notes to Table 9.6.3.1.:

(1)See Article 9.6.3.3.

9.6.3.2. — Doors to Public Water Closet Rooms

(1) Doors to public water closet rooms shall be not less than 810 mm wide and 2 030 mm high.

Text · e-Laws consolidated snapshot

9.6.3.3. — Doors to Bathrooms

(1) Where a barrier-free path of travel conforming to Section 3.8. is provided into a suite of residential occupancy and where a bathroom within the suite is at the level of the suite entrance door, the doorway to such bathroom and to each bedroom at the same level as such bathroom shall have, when the door is in the open position, a clear width of not less than,

(a) 760 mm where the door is served by a corridor or space not less than 1 060 mm wide, and

(b) 810 mm where the door is served by a corridor or space less than 1 060 mm wide.

Text · e-Laws consolidated snapshot

9.6.4. — Door Sill Height

Content not available for this version.

9.6.4.1. — Height of Door Sills Above Floors or Ground

(1) Doors in buildings of residential occupancy, where the finished floor on one side of the door is more than 600 mm above the floor or other surface or ground level on the other side of the door, shall be protected by,

(a) a guard, in accordance with Subsection 9.8.8., or

(b) a mechanism capable of controlling the free swinging or sliding of the door so as to limit any clear unobstructed opening to not more than 100 mm.

Text · e-Laws consolidated snapshot

9.6.5. — Exterior Doors

Content not available for this version.

9.6.5.1. — Exterior Wood Flush Doors

(1) Exterior wood flush doors shall conform to CAN/CSA-O132.2 Series, “Wood Flush Doors”.

(2) Each door described in Sentence (1) shall indicate legibly,

(a) the name of the manufacturer,

(b) the standard to which it is produced, and

(c) that it is of an exterior type.

Text · e-Laws consolidated snapshot

9.6.5.2. — Sliding Doors

(1) Sliding doors shall conform to CAN/CGSB-82.1-M, “Sliding Doors”.

Text · e-Laws consolidated snapshot

9.6.5.3. — Insulated Steel Doors

(1) Insulated steel doors shall conform to CAN/CGSB-82.5-M, “Insulated Steel Doors”.

Text · e-Laws consolidated snapshot

9.6.5.4. — Air Infiltration for Exterior Swing Type Doors

(1) Except where a door is weather-stripped on all edges, and protected with a storm door, or by an enclosed unheated space, an exterior swing type door assemblies shall have a rate of air infiltration not exceeding 1.16 L/s for each metre of crack length when tested at a pressure differential of 75 Pa in conformance with ASTM E283, “Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen”.

Text · e-Laws consolidated snapshot

9.6.5.5. — Air Infiltration for Patio Type Sliding Doors

(1) A patio type sliding glass door shall have a rate of air infiltration not exceeding 3.8 L/s for each square metre of door area when tested in conformance with ASTM E283, “Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen”.

Text · e-Laws consolidated snapshot

9.6.5.6. — Weather Stripping

(1) In buildings of residential occupancy weather stripping shall be provided around all exterior doors except garage doors.

Text · e-Laws consolidated snapshot

9.6.6. — Glass

Content not available for this version.

9.6.6.1. — Maximum Area of Glass

(1) The maximum area of individual panes of glass for doors shall conform to Table 9.6.6.1.

Editor's note

As filed in O. Reg. 350/06, the headings for Column 5 and Column 7 of Table 9.6.6.1. appear as '5 Column' and '7 Column' (number before the word), the 'Notes to Table 9.6.6.1.:' headnote is bold, and the footnote reference '(1)' is shown inline. The consolidated e-Laws text normalizes the headings to 'Column 5' and 'Column 7', sets the headnote in regular weight, and presents the footnote reference as a superscript. No amending regulation makes any of these changes; the as-filed wording and presentation are retained here.

Text · e-Laws consolidated snapshot

Table 9.6.6.1. Maximum Glass Area for Doors Forming Part of Sentence 9.6.6.1.(1)

Column 1

Column 2

Column 3

Column 4

5 Column

Column 6

7 Column

Column 8

Maximum Glass Area, m2

Type of Glass

Glass Thickness, mm

Annealed

Annealed Multiple-Glazed Factory-Sealed Units

Laminated

Wired

Heat Strengthened

Fully Tempered

Fully Tempered Multiple-Glazed Factory-Sealed Units

3

0.50

0.70

(1)

(1)

1.00

1.00

2.00

4

1.00

1.50

(1)

(1)

1.50

4.00

4.00

5

1.50

1.50

(1)

(1)

1.50

No Limit

No Limit

6

1.50

1.50

1.20

1.00

1.50

No Limit

No Limit

Notes to Table 9.6.6.1.:

(1)Not generally available.

9.6.6.2. — Glass in Doors and Sidelights

(1) Glass in doors and sidelights for doors shall conform to Sentence 9.7.3.1.(1).

(2) Glass in sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be,

(a) safety glass of the tempered or laminated type conforming to CAN/CGSB-12.1-M, “Tempered or Laminated Safety Glass”, or

(b) wired glass conforming to CAN/CGSB-12.11-M, “Wired Safety Glass”.

(3) Except as provided in Article 9.7.5.2., glass in entrance doors to dwelling units and in public areas other than the entrance door described in Sentence (2), shall be safety glass or wired glass of the type described in Sentence (2) where the glass area exceeds 0.5 m2 and extends to less than 900 mm from the bottom of the door.

Text · e-Laws consolidated snapshot

9.6.6.3. — Mirrored Glass Doors

(1) Mirrored glass doors are permitted to be used only at the entrance to clothes closets and shall conform to the requirements of CAN/CGSB-82.6-M, “Doors, Mirrored Glass, Sliding or Folding Wardrobe”.

(2) Mirrored glass doors reinforced with a film backing shall meet the impact resistance requirements specified in CAN/CGSB-12.5-M, “Mirrors, Silvered”.

Text · e-Laws consolidated snapshot

9.6.6.4. — Visibility of Glass or Transparent Doors

(1) Except as provided in Article 9.7.5.2., every glass or transparent door accessible to the public shall be equipped with hardware, bars or other permanent fixtures designed so that the existence and position of such door will be readily apparent.

Text · e-Laws consolidated snapshot

9.6.6.5. — Glass for Shower or Bathtub Enclosures

(1) Glass other than safety glass shall not be used for a shower or bathtub enclosure.

Text · e-Laws consolidated snapshot

9.6.7. — Thermal Breaks

Content not available for this version.

9.6.7.1. — Application

(1) This Subsection applies to doors and sidelights separating heated space from unheated space or the exterior.

Text · e-Laws consolidated snapshot

9.6.7.2. — Required Thermal Breaks

(1) Except as provided in Sentence (2), metal frames for doors, for glazing in doors, and for sidelights for doors shall incorporate a thermal break.

(2) Thermal breaks need not be installed in accordance with Sentence (1) where the doors are,

(a) garage doors,

(b) storm doors, or

(c) doors that are required to have a fire-resistance rating.

Text · e-Laws consolidated snapshot

9.6.8. — Resistance to Forced Entry

Content not available for this version.

9.6.8.1. — Application

(1) Except as permitted in Sentence (2), this Subsection applies to,

(a) swinging entrance doors to dwelling units,

(b) swinging doors between dwelling units and attached garages or other ancillary spaces, and

(c) swinging doors that provide access directly or indirectly from a storage garage to a dwelling unit.

(2) Sentence (1) does not apply to exterior doors to garages and to other ancillary spaces.

Text · e-Laws consolidated snapshot

9.6.8.2. — Wood Doors

(1) Except as permitted in Article 9.6.8.10., wood doors as described in Sentence 9.6.8.1.(1) shall,

(a) be solid core or stile and rail type,

(b) be not less than 45 mm thick, and

(c) if of the stile and rail panel type, have a panel thickness of not less than 19 mm, with a total panel area not more than half of the door area.

Text · e-Laws consolidated snapshot

9.6.8.3. — Deadbolt Lock

(1) Except as permitted in Article 9.6.8.10., doors described in Sentence 9.6.8.1.(1) shall be provided with a deadbolt lock with a cylinder having no fewer than 5 pins and a bolt throw not less than 25 mm, protected with a solid or hardened free-turning ring or bevelled cylinder housing.

Text · e-Laws consolidated snapshot

9.6.8.4. — Double Doors

(1) Except as permitted in Article 9.6.8.10., an inactive leaf in double doors used in locations specified in Sentence 9.6.8.1.(1) shall be provided with heavy duty bolts top and bottom having an engagement of not less than 15 mm.

Text · e-Laws consolidated snapshot

9.6.8.5. — Fastening of Hinges

(1) Except as permitted in Article 9.6.8.10., hinges for doors in Sentence 9.6.8.1.(1) shall be fastened to wood doors with wood screws not less than 25 mm long and to wood frames with wood screws such that at least two screws per hinge penetrate not less than 30 mm into solid wood.

(2) Except as permitted in Article 9.6.8.10., hinges for doors in Sentence 9.6.8.1.(1) shall be fastened to metal doors and metal frames with machine screws not smaller than No. 8 and not less than 10 mm long.

Text · e-Laws consolidated snapshot

9.6.8.6. — Fastening of Strikeplates

(1) Except as permitted in Article 9.6.8.10., strikeplates for deadbolts described in Sentence 9.6.8.3.(1) shall be fastened to wood frames with wood screws that penetrate not less than 30 mm into solid wood.

(2) Except as permitted in Article 9.6.8.10., strikeplates for deadbolts in Sentence 9.6.8.3.(1) shall be fastened to metal frames with machine screws not smaller than No. 8 and not less than 10 mm long.

Text · e-Laws consolidated snapshot

9.6.8.7. — Outward Swinging Doors

(1) Except for storm doors or screen doors, doors described in Sentence 9.6.8.1.(1) that swing outward shall be provided with hinges or pins so that the doors cannot be removed when they are in the closed position.

Text · e-Laws consolidated snapshot

9.6.8.8. — Door Viewer

(1) Main entrance doors to dwelling units shall be provided with,

(a) a door viewer or transparent glazing in the door, or

(b) a sidelight.

Text · e-Laws consolidated snapshot

9.6.8.9. — Solid Blocking

(1) Solid blocking shall be provided on both sides at the lock height between the jambs for doors described in Sentence 9.6.8.1.(1) and the structural framing so that the jambs will resist spreading by force.

Text · e-Laws consolidated snapshot

9.6.8.10. — Alternate Test Procedure

(1) Doors, frames and hardware that conform to a security level of at least Grade 10 as described in the Annex to ASTM F476, “Security of Swinging Door Assemblies”, are not required to conform to Articles 9.6.8.2. to 9.6.8.6.

Text · e-Laws consolidated snapshot

9.7. — Windows and Skylights

Content not available for this version.

9.7.1. — General

Content not available for this version.

9.7.1.1. — Application

(1) Windows and skylights shall conform to the requirements of this Section.

Text · e-Laws consolidated snapshot

9.7.1.2. — Minimum Window Areas

(1) Except as required in Article 9.7.1.3. and Sentence (3), the minimum window glass area for rooms in buildings of residential occupancy or that are used for sleeping shall conform to Table 9.7.1.2.

(2) The unobstructed glass area of a door or skylight is considered equivalent to that of a window.

(3) Work areas in live/work units shall conform to Clause 3.7.2.1.(2)(a).

(4) Where rooms with different requirements for window glass area are combined as described in Sentence 9.5.1.4.(1), the more restrictive requirement shall govern.

Editor's note

Table-9.7.1.2. — This map follows the as-filed text of O. Reg. 350/06 for Note (1) to Table 9.7.1.2. of Division B ('See Article 9.7.1.3.'), which no regulation amends. The as-filed note shows the note number '(1)' in plain text; as of its April 2, 2007 re-render the e-Laws consolidation displays the note number in superscript, with no amending regulation making the change and the note text unchanged. This map preserves the as-filed rendering.

Text · e-Laws consolidated snapshot

Table 9.7.1.2. Glass Areas for Rooms of Residential Occupancy Forming Part of Sentence 9.7.1.2.(1)

Column 1

Column 2

Column 3

Location

Minimum Unobstructed Glass Area With No Electric Lighting

Minimum Unobstructed Glass Area With Electric Lighting

Laundry, basement recreation room, unfinished basement

4% of area served

Windows not required

Water closet room

0.37 m²

Windows not required

Kitchen,

10% of area served

Windows not required

kitchen space,

kitchen alcove

Living rooms and dining rooms

10% of area served

10% of area served

Bedrooms and other finished rooms not mentioned above

5% of area served(1)

5% of area served(1)

Notes to Table 9.7.1.2.:

(1) See Article 9.7.1.3.

9.7.1.3. — Bedroom Windows

(1) Except where a door on the same floor level as the bedroom provides direct access to the exterior, every floor level containing a bedroom in a suite shall be provided with at least 1 outside window that,

(a) is openable from the inside without the use of tools,

(b) provides an individual, unobstructed open portion having a minimum area of 0.35 m² with no dimension less than 380 mm, and

(c) maintains the required opening described in Clause (b) without the need for additional support.

(2) Except for basement areas, the window described in Sentence (1) shall have a maximum sill height of 1 000 mm above the floor.

(3) When sliding windows are used, the minimum dimension described in Sentence (1) shall apply to the openable portion of the window.

(4) Where the sleeping area within a live/work unit is on a mezzanine with no obstructions more than 1 070 mm above the floor, the window required in Sentence (1) may be provided on the main level of the live/work unit provided the mezzanine is not more than 25% of the area of the live/work unit or 20 m2 whichever is less and an unobstructed direct path of travel is provided from the mezzanine to this window.

Text · e-Laws consolidated snapshot

9.7.1.4. — Window Opening into a Window-Well

(1) Where a window required in Article 9.7.1.3. opens into a window-well, a clearance of not less than 550 mm shall be provided in front of the window.

(2) Where the sash of a window referred to in Sentence (1) swings towards the window-well, the operation of the sash shall not reduce the clearance in a manner that would restrict escape in an emergency.

(3) Where a protective enclosure is installed over the window-well referred to in Sentence (1), such enclosure shall be openable from the inside without the use of keys, tools or special knowledge of the opening mechanism.

Text · e-Laws consolidated snapshot

9.7.1.5. — Termites

(1) In localities where termites are known to occur and where windows or other openings at or below grade contain wood elements, the bottom of window wells or adjacent ground shall be at least 150 mm below the nearest wood unless the wood is pressure-treated with a chemical toxic to termites in accordance with Article 9.3.2.9.v1v2

Text · e-Laws consolidated snapshot

9.7.1.6. — Height of Window Sills above Floors or Ground

(1) Except as provided in Sentence (2), openable windows in buildings of residential occupancy shall be protected by,

(a) a guard in accordance with Subsection 9.8.8., or

(b) a mechanism capable of controlling the free swinging or sliding of the openable part of the window so as to limit any clear unobstructed opening to not more than 100 mm measured either vertically or horizontally where the other dimension is greater than 380 mm.

(2) Windows need not be protected in accordance with Sentence (1) where,

(a) the window serves a dwelling unit that is not located above another suite,

(b) the only opening greater than 100 mm by 380 mm is a horizontal opening at the top of the window,

(c) the top surface of the window sill is located more than 480 mm above the finished floor on one side of the window, or

(d) the window is located in a room or space with the finished floor described in Clause (c) located less than 1 800 mm above the floor or ground on the other side of the window.

Text · e-Laws consolidated snapshot

9.7.1.7. — Air Infiltration of Exterior Windows

(1) Air infiltration of exterior windows shall not exceed 0.775 L/s for each metre of sash crack when tested at a pressure differential of 75 Pa in conformance with ASTM E283, “Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen”.

Text · e-Laws consolidated snapshot

9.7.2. — Window Standards

Content not available for this version.

9.7.2.1. — Window Standard

(1) Windows shall conform to,

(a) CAN/CSA-A440, “Windows”, and

(b) the CAN/CSA-A440.1, “User Selection Guide to CSA Standard CAN/CSA-A440-00 Windows”.

Text · e-Laws consolidated snapshot

9.7.3. — Glass

Content not available for this version.

9.7.3.1. — Glass Standards

(1) Glass shall conform to,

(a) CAN/CGSB-12.1-M, “Tempered or Laminated Safety Glass”,

(b) CAN/CGSB-12.2-M, “Flat, Clear Sheet Glass”,

(c) CAN/CGSB-12.3-M, “Flat, Clear Float Glass”,

(d) CAN/CGSB-12.4-M, “Heat-Absorbing Glass”,

(e) CAN/CGSB-12.8, “Insulating Glass Units”,

(f) CAN/CGSB-12.10-M, “Glass, Light and Heat/Reflecting”,

(g) CAN/CGSB-12.11-M, “Wired Safety Glass”, or

(h) ASTM E2190, “Insulating Glass Unit Performance and Evaluation”.

Text · e-Laws consolidated snapshot

9.7.3.2. — Structural Design of Glass

(1) Glass in windows, sloped glazing and skylights shall be designed in conformance with CAN/CGSB-12.20-M, “Structural Design of Glass for Buildings”.

Text · e-Laws consolidated snapshot

9.7.4. — Caulking and Glazing

Content not available for this version.

9.7.4.1. — Sealing Compound

(1) The sealing compound used to seal the glass component of a factory-sealed double-glazed unit to the sash component shall be compatible with the material used to edge seal the glass component.

Text · e-Laws consolidated snapshot

9.7.4.2. — Caulking Compound

(1) Caulking shall be provided between window frames or trim and the exterior siding or masonry in conformance with Subsection 9.27.4.

Text · e-Laws consolidated snapshot

9.7.5. — Protection of Windows in Public Areas

Content not available for this version.

9.7.5.1. — Transparent Panels

(1) Except as provided in Article 9.7.5.2., transparent panels that could be mistaken as a means of egress shall be protected by barriers or railings.

Text · e-Laws consolidated snapshot

9.7.5.2. — Sliding Glass Partitions

(1) Sliding glass partitions that separate a public corridor from an adjacent occupancy and that are open during working hours need not conform to Article 9.7.5.1. and Sentence 9.6.6.2.(3)v1, except that such partitions shall be suitably marked to indicate their existence and position.

Text · e-Laws consolidated snapshot

9.7.5.3. — Windows over Stairs, Ramps and Landings

(1) Except as provided in Sentence (2), windows over stairs, ramps and landings that extend to less than 1 070 mm above the surface to the treads, ramp or landing shall be,

(a) protected by guards, in accordance with Subsection 9.8.8., or

(b) non-openable and designed to withstand the specified lateral loads for guards as provided in Articles 4.1.5.15.v1 or 9.8.8.2.v1

(2) In dwelling units, windows over stairs, ramps and landings that extend to less than 900 mm above the surface to the treads, ramp or landing shall be,

(a) protected by guards, in accordance with Subsection 9.8.8., or

(b) non-openable and designed to withstand the specified lateral loads for guards as provided in Articles 4.1.5.15.v1 or 9.8.8.2.v1

Editor's note

As filed in O. Reg. 350/06, this article cites 'Articles 4.1.5.15. or 9.8.8.2.' using the plural 'Articles'; the consolidated e-Laws text renders the reference word in the singular ('Article'). The as-filed wording is retained here.

9.7.5.4. — Windows above the Second Storey

(1) Windows in public areas that extend to less than 1 000 mm from the floor and are located above the second storey in buildings of residential occupancy shall be,

(a) protected by guards in accordance with Subsection 9.8.8., or

(b) non-openable and designed to withstand the lateral design loads for guards as provided in Articles 4.1.5.15.v1 or 9.8.8.2.v1

Editor's note

As filed in O. Reg. 350/06, Clause (1)(b) cites 'Articles 4.1.5.15. or 9.8.8.2.' using the plural 'Articles'; the consolidated e-Laws text renders the reference word in the singular ('Article'). No amending regulation makes this change; the as-filed wording is retained here.

9.7.6. — Resistance to Forced Entry

Content not available for this version.

9.7.6.1. — Forced Entry Through Windows

(1) In dwelling units, windows, any part of which is located within 2 000 mm of adjacent ground level, shall conform to the requirements for resistance to forced entry as described in Clause 10.13 of CAN/CSA-A440-M, “Windows”.

Text · e-Laws consolidated snapshot

9.7.7. — Skylights

Content not available for this version.

9.7.7.1. — Plastic Skylights

(1) Plastic skylights shall conform to CAN/CGSB-63.14-M, “Plastic Skylights”.

Text · e-Laws consolidated snapshot

9.7.7.2. — Glass Skylights

(1) Factory-built glass skylights shall meet the performance requirements of CAN/CGSB-63.14-M, “Plastic Skylights”.

Text · e-Laws consolidated snapshot

9.8. — Stairs, Ramps, Handrails and Guards

Content not available for this version.

9.8.1. — Application

Content not available for this version.

9.8.1.1. — General

(1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.

Text · e-Laws consolidated snapshot

9.8.1.2. — Exit Stairs, Ramps and Landings

(1) Where a stair, ramp or landing forms part of an exit, the appropriate requirements in Sections 9.9. and 9.10. shall also apply.

Text · e-Laws consolidated snapshot

9.8.1.3. — Escalators and Moving Walkways

(1) Escalators and moving walkways shall conform to the appropriate requirements in Part 3.

Text · e-Laws consolidated snapshot

9.8.2. — Stair Dimensions

Content not available for this version.

9.8.2.1. — Stair Width

(1) Required exit stairs and public stairs shall have a width, measured between wall faces or guards, of not less than 900 mm.

(2) At least 1 stair between each floor level within a dwelling unit, and exterior stairs serving a single dwelling unit except required exit stairs, shall have a width of not less than 860 mm.

Text · e-Laws consolidated snapshot

9.8.2.2. — Height over Stairs

(1) The clear height over stairs measured vertically from a line drawn through the leading edges of the treads, shall be not less than,

(a) 1 950 mm for stairs within dwelling units, and

(b) 2 050 mm for stairs not within dwelling units.

Text · e-Laws consolidated snapshot

9.8.3. — Stair Configurations

Content not available for this version.

9.8.3.1. — Straight and Curved Runs in Stairs

(1) Except as provided in Sentence (2), stairs shall consist of,

(a) straight-runs, or

(b) curved-runs.

(2) Stairs within dwelling units shall consist of,

(a) straight-runs,

(b) curved-runs,

(c) straight-runs with winders, or

(d) straight-runs with curved-runs.

Text · e-Laws consolidated snapshot

9.8.3.2. — Minimum Number of Risers

(1) Except for stairs within a dwelling unit, at least 3 risers shall be provided in interior flights.

Text · e-Laws consolidated snapshot

9.8.3.3. — Maximum Height of Stairs

(1) The vertical height between any landings shall not exceed 3.7 m.

Text · e-Laws consolidated snapshot

9.8.4. — Step Dimensions

Content not available for this version.

9.8.4.1. — Uniformity and Tolerances for Risers and Treads

(1) Except as provided in Sentence (2), risers shall have uniform height in any one flight with a maximum tolerance of,

(a) 6 mm between adjacent treads or landings, and

(b) 6 mm between the tallest and shortest risers in a flight.

(2) Except for required exit stairs, where the top or bottom riser in a stair adjoins a sloping finished walking surface such as a garage floor, driveway or sidewalk, the height of the riser across the stair shall vary by not more than 1 in 12.

(3) Treads shall have uniform run and tread depth, with a maximum tolerance of,

(a) 6 mm between adjacent treads, and

(b) 6 mm between the deepest and shallowest runs and treads in a flight.

(4) Where angled treads or winders are incorporated into a stair, the treads in all sets of angled treads or winders within a flight shall turn in the same direction.

(5) Cross-slope of treads shall not exceed 1 in 100.

Text · e-Laws consolidated snapshot

9.8.4.2. — Dimensions for Risers

(1) Risers shall conform to Table 9.8.4.2.

Editor's note

In the notes to Table-9.8.4.2., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.8.4.2. Riser Height, Run and Tread Depth for Rectangular Treads Forming Part of Sentences 9.8.4.2.(1) and 9.8.4.3.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Stair Type

All Steps

Rectangular Treads

Rise, mm

Run, mm

Tread Depth, mm

max.

min.

max.

min.

max.

min.

Service and mezzanines in live/work units(1)

no limit

125

355

no limit

355

no limit

Private(2)

200

125

355

210

355

235

Public(3)

200

125

355

230

355

250

Notes to Table 9.8.4.2.:

(1)Service stairs serve areas used only as service rooms or service spaces and stairs that serve mezzanines not exceeding 20 m2 within live/work units.

(2)Private stairs are interior stairs within dwelling units and exterior stairs serving a single dwelling unit.

(3)Public stairs are all stairs not described as service stair or private stairs.

9.8.4.3. — Dimensions for Rectangular Treads

(1) The run and tread depth of rectangular treads shall conform to Table 9.8.4.2.

(2) The depth of a rectangular tread shall be not less than its run and not more that its run plus 25 mm.

Text · e-Laws consolidated snapshot

9.8.4.4. — Dimensions for Angled Treads

(1) Angled treads in required exit stairs shall comply with Article 3.4.6.8.

(2) Except as provided in Article 9.8.4.5., angled treads in other than required exit stairs shall have an average run of not less than 200 mm and a minimum run of 150 mm.

(3) The depth of an angled tread shall be not less than its run at any point and not more than its run plus 25 mm.

Text · e-Laws consolidated snapshot

9.8.4.5. — Winders

(1) Stairs within dwelling units are permitted to contain winders that converge to a centre point provided,

(a) the winders turn through an angle of not more than 90°,

(b) individual treads turn through an angle of not less than 30° or not more than 45°, and

(c) adjacent winders turn through the same angle.

(2) Where more than one set of winders described in Sentence (1) is provided in a single stairway between adjacent floor levels, such winders shall be separated in plan by at least 1 200 mm.

Text · e-Laws consolidated snapshot

9.8.4.6. — Leading Edges of Treads

(1) Leading edges of treads that are bevelled or rounded shall,

(a) not reduce the required tread depth by more than 15 mm, and

(b) not, in any case, exceed 25 mm horizontally.

Text · e-Laws consolidated snapshot

9.8.4.7. — Interior Stairs Extending Through the Roof

(1) Interior stairways extending through the roof of a building shall be protected from ice and snow.

Text · e-Laws consolidated snapshot

9.8.5. — Ramps

Content not available for this version.

9.8.5.1. — Application

(1) This Subsection applies to pedestrian ramps except ramps in a barrier-free path of travel.

(2) Ramps in a barrier-free path of travel shall conform to the requirements in Article 3.8.3.4.v1

Text · e-Laws consolidated snapshot

9.8.5.2. — Ramp Width

(1) Except for required exit ramps, public ramps shall have a width of not less than 900 mm.

(2) Ramps within dwelling units, and exterior ramps serving a single dwelling unit except required exit ramps, shall have a width of not less than 860 mm.

Text · e-Laws consolidated snapshot

9.8.5.3. — Height over Ramps

(1) The clear height over ramps shall be not less than,

(a) 1 950 mm for ramps within dwelling units, and

(b) 2 050 mm for ramps not within dwelling units.

Text · e-Laws consolidated snapshot

9.8.5.4. — Slope

(1) The slope of ramps shall be not more than,

(a) 1 in 10 for exterior ramps,

(b) 1 in 10 for interior ramps serving residential occupancies,

(c) 1 in 6 for mercantile or industrial occupancies, and

(d) 1 in 8 for all other occupancies.

Text · e-Laws consolidated snapshot

9.8.5.5. — Maximum Rise

(1) Where the slope of the ramp is greater than 1 in 12, the maximum rise between floors or landings shall be 1 500 mm.

Text · e-Laws consolidated snapshot

9.8.6. — Landings

Content not available for this version.

9.8.6.1. — Application

(1) This Subsection applies to landings, except landings for ramps in a barrier-free path of travel.

(2) Landings for ramps in a barrier-free path of travel shall conform to the requirements in Article 3.8.3.4.v1

(3) Finished floors, and ground surfaces with a slope not exceeding 1 in 100, at the top and bottom of stairs or ramps shall be considered as landings.

Text · e-Laws consolidated snapshot

9.8.6.2. — Required Landings

(1) Except as provided in Sentences (2) to (4) and Sentence 9.9.6.6.(2), a landing shall be provided,

(a) at the top and bottom of each flight of interior and exterior stairs, including stairs in garages,

(b) at the top and bottom of every ramp with a slope greater than 1 in 50, and

(c) where a doorway opens onto a stair or ramp.

(2) Where a door at the top of a stair in a dwelling unit swings away from the stair, no landing is required between the doorway and the stair.

(3) Except for an entrance from an attached garage, a landing may be omitted at the top of an exterior stair serving a secondary entrance to a single dwelling unit, provided,

(a) the stair does not contain more than 3 risers,

(b) except as provided in Clause (c), the door is a sliding door or swings away from the stair, and

(c) where a storm or screen door is provided, it may swing over the stair if it is equipped with hardware to hold it open.

(4) A landing may be omitted at the bottom of an exterior stair or ramp provided there is no obstruction, such as a gate or door, within the lesser of the width of the stair or ramp or,

(a) 900 mm for stairs or ramps serving a single dwelling unit, and

(b) 1100 mm for stairs or ramps not serving a single dwelling unit.

Text · e-Laws consolidated snapshot

9.8.6.3. — Dimensions of Landings

(1) Except as provided in Sentences (2) to (4), the width and length of landings shall comply with Table 9.8.6.3.

(2) Where stairs or ramps of different widths adjoin a single landing, the width of the landing shall be,

(a) not less than the greater required stair or ramp width where one or more of the stair or ramp widths do not exceed their respective required widths, or

(b) not less than the lesser actual stair or ramp width where all of the widths of the stairs or ramps exceed their respective required widths.

(3) Where a door swings toward a stair, the full arc of the swing shall be over the landing.

(4) Where a doorway or stairway opens onto the side of a ramp, the landing shall extend for a distance of not less than 300 mm on either side of the doorway or stairway, except on a side abutting an end wall.

Text · e-Laws consolidated snapshot

Table 9.8.6.3. Dimensions of Landings Forming Part of Sentence 9.8.6.3.(1)

Column 1

Column 2

Column 3

Column 4

Application

Landing Configuration

Minimum Width, mm

Length, mm

Stairs and ramps serving a single dwelling unit

In straight-run stair or ramp, or landing turning through less than 30°, within a dwelling unit

Width of stair or ramp

Not less than 860

In straight-run exterior stair or ramp, or exterior landing turning through less than 30°

Width of stair or ramp

Not less than 900

Landing turning through an angle of 30° or more, but less than 90°

Width of stair or ramp measured at right angle to path of travel

    (a) Not less than 230 measured at the inside edge of the landing, and

    (b) Not less than 370 measured 230 mm from the inside edge of landing or handrail

Landing turning through not less than 90°

Width of stair or ramp measured at right angle to path of travel

Not less than width of landing

Stairs and ramps serving other than single dwelling units

In straight-run stair or ramp, or landing turning through less than 30°

Width of stair or ramp

Lesser of required width of stair or ramp, or 1 100

Landing turning through 30° or more

Width of stair or ramp measured at right angle to path of travel

Not less than width of stair or landing

9.8.6.4. — Height over Landings

(1) The clear height over landings shall be not less than,

(a) 1 950 mm for landings within dwelling units, and

(b) 2 050 mm for landings not within dwelling units.

Text · e-Laws consolidated snapshot

9.8.7. — Handrails

Content not available for this version.

9.8.7.1. — Required Handrails

(1) Except as permitted in Sentences (2) and (3), a handrail shall be provided,

(a) on at least one side of stairs or ramps less than 1 100 mm in width,

(b) on 2 sides of curved stairs or ramps of any width, except curved stairs within dwelling units, and

(c) on 2 sides of stairs or ramps 1 100 mm in width or greater.

(2) Handrails are not required for,

(a) interior stairs having not more than 2 risers and serving a single dwelling unit,

(b) exterior stairs having not more than 3 risers and serving a single dwelling unit,

(c) ramps with a slope of not less than 1 in 12, or

(d) ramps rising not more than 400 mm.

(3) Only one handrail is required on exterior stairs having more than 3 risers provided such stairs serve a single dwelling unit.

Text · e-Laws consolidated snapshot

9.8.7.2. — Continuity of Handrails

(1) Except as provided in Sentence (2), at least one required handrail shall be continuous throughout the length of the stair or ramp, including landings, except where interrupted by,

(a) doorways, or

(b) newel posts at changes in direction.

(2) For stairs or ramps serving a single dwelling unit, at least one handrail shall be continuous throughout the length of the stair or ramp, except where interrupted by,

(a) doorways,

(b) landings, or

(c) newel posts at changes in direction.

Text · e-Laws consolidated snapshot

9.8.7.3. — Termination of Handrails

(1) Handrails shall be terminated in a manner that will not obstruct pedestrian travel or create a hazard.

(2) Except for stairs and ramps serving a single dwelling unit, at least one handrail at the sides of a stair or ramp shall extend horizontally not less than 300 mm beyond the top and bottom of each stair or ramp.

Text · e-Laws consolidated snapshot

9.8.7.4. — Height of Handrails

(1) The height of handrails on stairs and ramps shall be measured vertically from the top of the handrail to,

(a) a line drawn through the leading edge of the stair treads served by the handrail, or

(b) the surface of the ramp, floor or landing served by the handrail.

(2) Except as provided in Sentence (3), the height of handrails on stairs and ramps shall be,

(a) not less than 800 mm, and

(b) not more than 965 mm.

(3) Where guards are required, handrails required on landings shall be not more than 1 070 mm in height.

Text · e-Laws consolidated snapshot

9.8.7.5. — Ergonomic Design

(1) A clearance of not less than 50 mm shall be provided between a handrail and any surface behind it.

(2) All handrails shall be constructed so as to be continually graspable along their entire length with no obstruction on or above them to break a handhold, except where the handrail is interrupted by newels at changes in direction.

Text · e-Laws consolidated snapshot

9.8.7.6. — Projections into Stairs and Ramps

(1) Handrails and projections below handrails, including handrail supports and stair stringers shall not project more than 100 mm into the required width of a stair or ramp.

Text · e-Laws consolidated snapshot

9.8.7.7. — Design and Attachment of Handrails

(1) Handrails and any building element that could be used as a handrail shall be designed and attached in such a manner to resist,

(a) a concentrated load at any point of not less than 0.9 kN, and

(b) for handrails other than those serving a single dwelling unit, a uniformly distributed load of 0.7 kN/m.

(2) Where a handrail serving a single dwelling unit is attached to wood studs or blocking, the attachment shall be deemed to comply with Sentence (1) where,

(a) the attachment points are spaced not more than 1.2 m apart,

(b) the first attachment point at either end is located not more than 300 mm from the end of the handrail, and

(c) the fasteners consist of no fewer than 2 wood screws at each point, penetrating not less than 32 mm into solid wood.

Text · e-Laws consolidated snapshot

9.8.8. — Guards

Content not available for this version.

9.8.8.1. — Required Guards

(1) Except as provided in Sentences (2) and (3), every surface to which access is provided for other than maintenance purposes, including but not limited to flights of steps and ramps, exterior landings, porches, balconies, mezzanines, galleries and raised walkways, shall be protected by a guard on each side that is not protected by a wall for the length where,

(a) there is a difference in elevation of more than 600 mm between the walking surface and the adjacent surface, or

(b) the adjacent surface within 1.2 m from the walking surface has a slope of more than 1 in 2.

(2) Guards are not required,

(a) at loading docks,

(b) at floor pits in repair garages, or

(c) where access is provided for maintenance purposes only.

(3) When an interior stair has more than 2 risers or an interior ramp rises more than 400 mm, the sides of the stair or ramp and the landing or floor level around the stairwell or ramp shall be protected by a guard on each side that is not protected by a wall.

Text · e-Laws consolidated snapshot

9.8.8.2. — Loads on Guards

(1) Except as provided in Sentence (5), guards shall be designed to resist the loads specified in Table 9.8.8.2.

(2) Where the width and spacing of balusters in guards within dwelling units, and exterior guards serving not more than 2 dwelling units is such that 3 balusters can be engaged by a load imposed over the 300 mm width, the load shall be imposed so as to engage 3 balusters.

(3) None of the loads specified in Table 9.8.8.2. need be considered to act simultaneously.

(4) For guards within dwelling units and for exterior guards serving not more than 2 dwelling units, Table 9.8.8.2. need not apply where the guard construction has been demonstrated to provide effective performance.

(5) Guards constructed in accordance with the requirements in Supplementary Standard SB-7 shall be deemed to satisfy the requirements of Sentence (1).

Text · e-Laws consolidated snapshot

Table 9.8.8.2. Specified Loads for Guards Forming Part of Sentence 9.8.8.2.(1)

Column 1

Column 2

Column 3

Column 4

Location of Guard

Minimum Design Loads

Horizontal Load Applied Inward or Outward at any Point at the Top of the Guard

Horizontal Load Applied Inward or Outward on Elements Within the Guard, Including Solid Panels and Pickets

Evenly Distributed Vertical Load Applied at the Top of the Guard

Guards within dwelling units and exterior guards serving not more than 2 dwelling units

0.5 kN/m or concentrated load of 1.0 kN applied at any point(1)

0.5 kN applied over a maximum width of 300 mm and a height of 300 mm(2)

1.5 kN/m

Guards serving access walkways to equipment platforms, contiguous stairs and similar areas

Concentrated load of 1.0 kN applied at any point

Concentrated load of 0.5 kN applied at any point on individual elements

1.5 kN/m

All other guards

0.75 kN/m or concentrated load of 1.0 kN applied at any point(1)

Concentrated load of 0.5 kN applied at any point on individual elements

1.5 kN/m

Notes to Table 9.8.8.2.:

(1)The load that creates the most critical condition shall apply.

(2)See Sentence (2).

9.8.8.3. — Height of Guards

(1) Except as provided in Sentences (2) to (4), all guards shall be not less than 1 070 mm high.

(2) All guards within dwelling units shall be not less than 900 mm high.

(3) Exterior guards serving not more than one dwelling unit shall be not less than 900 mm high where the walking surface served by the guard is not more than 1 800 mm above the finished ground level.

(4) Guards for flights of steps, except in required exit stairs, shall be not less than 900 mm high.

(5) The height of guards for flights of steps shall be measured vertically from a line drawn through the leading edge of the treads served by the guard.

Text · e-Laws consolidated snapshot

9.8.8.4. — Guards for Floors and Ramps in Garages

(1) Except for floors of garages referred to in Section 9.35., where garage floors or ramps are 600 mm or more above the adjacent ground or floor level, every opening through a garage floor and the perimeter of floors and ramps that have no exterior walls shall be provided with,

(a) a continuous curb not less than 150 mm in height, and

(b) a guard not less than 1 070 mm above the floor level.

Text · e-Laws consolidated snapshot

9.8.8.5. — Openings in Guards

(1) Except as provided in Sentence (2), openings through any guard that is required by Article 9.8.8.1. shall be of a size that will prevent the passage of a spherical object having a diameter of 100 mm unless it can be shown that the location and size of openings that exceed this limit do not represent a hazard.

(2) Openings through any guard that is required by Article 9.8.8.1. and that is installed in a building of industrial occupancy shall be of a size that will prevent the passage of a spherical object having a diameter of 200 mm unless it can be shown that the location and size of such openings that exceed this limit do not represent a hazard.

(3) Unless it can be shown that the location and size of openings that do not comply with the following limits do not represent a hazard, openings through any guard that is not required by Article 9.8.8.1. and that serves a building of other than industrial occupancy, shall be of a size that,

(a) will prevent the passage of a spherical object having a diameter of 100 mm, or

(b) will permit the passage of a spherical object having a diameter of 200 mm.

Text · e-Laws consolidated snapshot

9.8.8.6. — Design to Prevent Climbing

(1) Guards required by Article 9.8.8.1., except those in industrial occupancies and where it can be shown that the location and size of openings do not represent a hazard, shall be designed so that no member, attachment or opening will facilitate climbing.

(2) Guards shall be deemed to comply with Sentence (1) where any elements protruding from the vertical and located within the area between 140 mm and 900 mm above the floor or walking surface protected by the guard,

(a) are located more than 450 mm horizontally and vertically from each other,

(b) provide not more than 15 mm horizontal offset,

(c) do not provide a toe-space more than 45 mm horizontally and 20 mm vertically, or

(d) present more than a 1-in-2 slope on the offset.

Text · e-Laws consolidated snapshot

9.8.8.7. — Glass in Guards

(1) Glass in guards shall be,

(a) safety glass of the laminated or tempered type conforming to CAN/CGSB-12.1-M, “Tempered or Laminated Safety Glass”, or

(b) wired glass conforming to CAN/CGSB-12.11-M, “Wired Safety Glass”.

Text · e-Laws consolidated snapshot

9.8.9. — Construction

Content not available for this version.

9.8.9.1. — Loads on Stairs and Ramps

(1) Except as required in Articles 9.8.9.4. and 9.8.9.5., stairs and ramps shall be designed for strength and rigidity under uniform loading criteria to support specified loads of,

(a) 1.9 kPa for stairs and ramps serving a single dwelling unit, and

(b) 4.8 kPa for other stairs and ramps.

Text · e-Laws consolidated snapshot

9.8.9.2. — Exterior Concrete Stairs

(1) Exterior concrete stairs with more than 2 risers and 2 treads shall be,

(a) supported on unit masonry or concrete walls or piers not less than 150 mm in cross section, or

(b) cantilevered from the main foundation wall.

(2) Stairs described in Sentence (1), when cantilevered from the foundation wall, shall be constructed and installed in conformance with Subsection 9.8.10.

(3) The depth below ground level for foundations for exterior steps shall conform to the requirements in Section 9.12.

Text · e-Laws consolidated snapshot

9.8.9.3. — Exterior Wood Steps

(1) Exterior wood steps shall not be in direct contact with the ground unless suitably treated with a wood preservative.

Text · e-Laws consolidated snapshot

9.8.9.4. — Wooden Stair Stringers

(1) Wooden stair stringers shall,

(a) have a minimum effective depth of 90 mm, measured perpendicularly to the bottom of the stringer at the point of minimum cross-section, and an over-all depth of not less than 235 mm,

(b) be supported and secured top and bottom,

(c) be not less than 25 mm actual thickness if supported along their length and 38 mm actual thickness if unsupported along their length, and

(d) except as permitted in Sentence (2), be spaced not more than 900 mm o.c. for stairs serving not more than one dwelling unit, and 600 mm o.c. in other stairs.

(2) For stairs serving not more than one dwelling unit where risers support the front portion of the tread, the space between stringers shall be not more than 1 200 mm.

Text · e-Laws consolidated snapshot

9.8.9.5. — Treads

(1) Stair treads of lumber, plywood or O-2 grade OSB within dwelling units shall be not less than 25 mm actual thickness, except that if open risers are used and the distance between stringers exceeds 750 mm, the treads shall be not less than 38 mm actual thickness.

(2) Stair treads of plywood or OSB, that are not continuously supported by the riser shall have their face grain or direction of face orientation at right angles to the stringers.

Text · e-Laws consolidated snapshot

9.8.9.6. — Finish for Treads, Landings and Ramps

(1) Except as required in Sentence (4), the finish for treads, landings and ramps shall be,

(a) wear resistant,

(b) slip resistant, and

(c) smooth, even, and free from open defects.

(2) The finish for treads and landings of interior stairs in dwelling units, including those from an attached garage serving a single dwelling unit, shall be deemed to comply with Sentence (1) where these treads, landings, or ramps are finished with,

(a) hardwood,

(b) vertical grain softwood,

(c) resilient flooring,

(d) low-pile carpet,

(e) mat finish ceramic tile,

(f) concrete, or

(g) for stairs to unfinished basements and to garages, plywood.

(3) Stairs and ramps, except those serving a single dwelling unit or service rooms or spaces, shall have either a colour contrast or a distinctive pattern to demarcate,

(a) the leading edge of the treads,

(b) the leading edge of the landing, and

(c) the beginning and end of a ramp.

(4) Treads and landings of interior and exterior stairs and ramps, other than those within dwelling units, shall have a slip-resistant finish or be provided with slip-resistant strips that extend not more than 1 mm above the surface.

Text · e-Laws consolidated snapshot

9.8.10. — Cantilevered Precast Concrete Steps

Content not available for this version.

9.8.10.1. — Design

(1) Exterior concrete steps and their anchorage system that are cantilevered from a foundation wall shall be designed and installed to support the loads to which they may be subjected.

Text · e-Laws consolidated snapshot

9.8.10.2. — Anchorage

(1) Cantilevered concrete steps in Article 9.8.10.1. shall be anchored to concrete foundation walls at least 200 mm thick.

Text · e-Laws consolidated snapshot

9.8.10.3. — Prevention of Damage Due to Frost

(1) Suitable precautions shall be taken during backfilling and grading operations to ensure that subsequent freezing of the soil will not cause uplift forces on the underside of cantilevered concrete steps to the extent that the steps or the walls to which they are attached will be damaged.

Text · e-Laws consolidated snapshot

9.9. — Means of Egress

Content not available for this version.

9.9.1. — Scope

Content not available for this version.

9.9.1.1. — Application

(1) Stairways, handrails and guards in a means of egress shall conform to the requirements in Section 9.8. as well as to the requirements in this Section.

Text · e-Laws consolidated snapshot

9.9.1.2. — Fire Protection

(1) In addition to the fire protection requirements provided in Subsection 9.9.4., flame-spread ratings, fire-resistance ratings and fire-protection ratings for means of egress shall conform to Section 9.10.

Text · e-Laws consolidated snapshot

9.9.1.3. — Occupant Load

(1) The occupant load of a floor area or part of a floor area, or of a building or part of a building not having a floor area, shall be based on,

(a) 2 persons per sleeping room or sleeping area in a dwelling unit or suite, and

(b) for occupancies other than as described in Clause (a), the number of persons,

(i) for which the area is designed, or

(ii) determined from Table 3.1.17.1.

Text · e-Laws consolidated snapshot

9.9.2. — Types and Purpose of Exits

Content not available for this version.

9.9.2.1. — Types of Exits

(1) Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination:

(a) an exterior doorway,

(b) an exterior passageway,

(c) an exterior ramp,

(d) an exterior stairway,

(e) a fire escape (as described in Subsection 3.4.7.),

(f) a horizontal exit,

(g) an interior passageway,

(h) an interior ramp, or

(i) an interior stairway.

(2) Fire escapes are permitted to be used as exits on existing buildings provided they are designed and installed in conformance with Subsection 3.4.7.

(3) Fire escapes shall not be installed on any new building.

(4) Where a horizontal exit is used, it shall conform to Sentence 3.4.1.6.(1) and Article 3.4.6.9.

Text · e-Laws consolidated snapshot

9.9.2.2. — Purpose of Exits

(1) An exit shall be designed for no purpose other than for exiting except that an exit may also serve as an access to a floor area.

Text · e-Laws consolidated snapshot

9.9.2.3. — Elevators, Slide Escapes and Windows as Means of Egress

(1) Elevators, slide escapes or windows shall not be considered as part of a required means of egress.

(2) Except for floor areas of mercantile occupancy, casement windows not less than 1 060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a required means of egress to provide access to fire escapes, when fire escapes are permitted.

Text · e-Laws consolidated snapshot

9.9.2.4. — Principal Entrances

(1) Except for doors serving a single dwelling unit, at least one door at every principal entrance to a building providing access from the exterior at ground level shall be designed in accordance with the requirements for exits.

Text · e-Laws consolidated snapshot

9.9.2.5. — Front Edge of Stair Treads

(1) Except for curved stairs the front edge of stair treads in exits and access to exits shall be at right angles to the direction of exit travel.

Text · e-Laws consolidated snapshot

9.9.2.6. — Exterior Exit Stairs that Serve a Hotel

(1) Treads and landings of exterior exit stairs that serve a hotel shall be designed to be free from ice and snow accumulation.

Text · e-Laws consolidated snapshot

9.9.3. — Dimensions of Means of Egress

Content not available for this version.

9.9.3.1. — Application

(1) This Subsection applies to every means of egress except exits that serve not more than one dwelling unit and access to exits within dwelling units.

Text · e-Laws consolidated snapshot

9.9.3.2. — Exit Width

(1) Except for doors and corridors, the width of every exit facility shall be not less than 900 mm.

Text · e-Laws consolidated snapshot

9.9.3.3. — Width of Corridors

(1) The width of every public corridor, corridor used by the public, and exit corridor shall be not less than 1 100 mm.

Text · e-Laws consolidated snapshot

9.9.3.4. — Clear Height

(1) Except for stairways, doorways and storage garages, the minimum clear height in exits and access to exits shall be 2 100 mm.

(2) The clear height in exits and access to exits in a storage garage shall be not less than 2 000 mm.

Text · e-Laws consolidated snapshot

9.9.4. — Fire Protection of Exits

Content not available for this version.

9.9.4.1. — Application

(1) Except as provided in Article 9.9.4.4., this Subsection applies to the fire protection of all exits except exits serving a single dwelling unit.

Text · e-Laws consolidated snapshot

9.9.4.2. — Fire Separation for Exits

(1) Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway, shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area.

(2) Where there is no floor assembly above, the fire-resistance rating required in Sentence (1) shall not be less than that required by Subsection 9.10.8. for the floor assembly below, but in no case shall the fire-resistance rating be less than 45 min.

(3) A fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any other opening that may affect the continuity of the separation.

(4) A fire separation that separates an exit from the remainder of the building shall have no openings except those for electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit and for standpipes, sprinkler piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.

(5) The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has at least 50 per cent of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.

Text · e-Laws consolidated snapshot

9.9.4.3. — Wired Glass or Glass Block

(1) This Article applies to wired glass in doors, and wired glass or glass block in sidelights, where these are installed in fire separations between exit enclosures and floor areas.

(2) Except as provided in Sentence (3), the combined area of glazing in doors and sidelights shall not exceed 0.8 m².

(3) Where an exit enclosure connects with a floor area through an enclosed vestibule or corridor separated from the floor area by fire separations having not less than a 45 min fire-resistance rating, the glazed areas described in Sentence (1) need not be limited as required in Sentence (2).

Text · e-Laws consolidated snapshot

9.9.4.4. — Openings Near Unenclosed Exit Stairs and Ramps

(1) Where an unenclosed exterior exit stair or ramp provides the only means of egress from a suite, and is exposed to fire from openings in the exterior walls of another fire compartment, the openings in the exterior walls of the building shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. when the openings in the exterior walls of the building are within 3 m horizontally and less than 10 m below or less than 5 m above the exit stair or ramp.

Text · e-Laws consolidated snapshot

9.9.4.5. — Openings in Exterior Walls of Exits

(1) Either openings in the exterior walls of an exit or openings in adjacent exterior walls of the building the exit serves shall be protected with wired glass in fixed steel frames or glass block installed in accordance with Articles 9.10.13.5. and 9.10.13.7., where,

(a) the exit enclosure has exterior walls that intersect the exterior walls of the building at an angle of less than 135° measured on the outside of the building, and

(b) the openings in the exterior walls of the building are within 3 m horizontally and less than 2 000 mm above the openings in the exterior walls of the exit.

Text · e-Laws consolidated snapshot

9.9.4.6. — Openings Near Exit Doors

(1) This Article applies to,

(a) exit doors serving other than single dwelling units, and

(b) exit doors serving single dwelling units where there is no second and separate exit from the dwelling unit.

(2) Where an exterior exit door described in Sentence (1) in one fire compartment is within 3 m horizontally of an unprotected opening in another fire compartment and the exterior walls of these fire compartments intersect at an exterior angle of less than 135°, the opening shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. or with a rated closure conforming to Table 9.10.13.1.v1 with respect to the rating of the fire separation between the two compartments.

Text · e-Laws consolidated snapshot

9.9.4.7. — Stairways in Group D or E Buildings

(1) Notwithstanding the requirements of Sentences 9.9.4.2.(1), 9.9.8.2.(1) and Article 9.10.9.5., where a suite of Group D or E occupancy is located partly on the first storey and partly on the second storey or partly on the second storey and partly on the third storey, stairways serving that suite need not be constructed as exit stairs provided,

(a) the building is not greater than 3 storeys in building height,

(b) the suite is separated from other occupancies by at least a 45 min fire separation,

(c) the area occupied by the suite is not greater than 100 m² per storey, other than the exit level storey,

(d) the maximum travel distance from any point in the suite to an exterior exit is not greater than 25 m,

(e) the floor assemblies have a fire-resistance rating of not less than 45 min or are of noncombustible construction,

(f) the basement and first storey are separated by a fire separation having a fire-resistance rating of not less than 45 min, and

(g) a smoke alarm is installed on each floor of the suite, including the basement, in accordance with Subsection 9.10.19.

(2) The requirements of Article 9.10.12.1., for separation of exterior openings, do not apply to an occupancy conforming with Sentence (1).

Text · e-Laws consolidated snapshot

9.9.5. — Obstructions and Hazards in Means of Egress

Content not available for this version.

9.9.5.1. — Application

(1) This Subsection applies to obstructions and hazards in every means of egress except those within a dwelling unit or serving a single dwelling unit.

Text · e-Laws consolidated snapshot

9.9.5.2. — Occupancies in Corridors

(1) Where a corridor contains an occupancy, the occupancy shall not reduce the unobstructed width of the corridor to less than the required width of the corridor.

Text · e-Laws consolidated snapshot

9.9.5.3. — Obstructions in Public Corridors

(1) Except as permitted in Sentence (2), obstructions located within 1 980 mm of the floor shall not project horizontally more than 100 mm into exit passageways, corridors used by the public or public corridors in a manner that would create a hazard for visually impaired persons travelling adjacent to walls.

(2) The horizontal projection of an obstruction in Sentence (1) is permitted to exceed 100 mm where the obstruction extends to less than 680 mm above the floor.

Text · e-Laws consolidated snapshot

9.9.5.4. — Obstructions in Exits

(1) Except as permitted in Subsection 9.9.6. and Article 9.8.7.6., no fixture, turnstile or construction shall project within the required width of an exit.

Text · e-Laws consolidated snapshot

9.9.5.5. — Obstructions in Means of Egress

(1) No obstructions such as posts or turnstiles shall be placed so as to restrict the width of a required means of egress from a floor area or part of a floor area to less than 750 mm unless an alternate unobstructed means of egress is provided adjacent to and plainly visible from the restricted egress.

(2) Except as provided in Sentence (3), no obstructions, such as counter gates, that do not meet the requirements for exit doors, shall be placed in a required means of egress from a floor area or part of a floor area unless an alternate unobstructed means of egress is provided adjacent to and plainly visible from the restricted egress.

(3) Obstructions, such as counter gates, that do not satisfy Sentence (2), are permitted to be placed in a required means of egress from a part of a floor area in mercantile occupancies and business and personal services occupancies, provided that the part of the floor area served by the unobstructed means of egress is not generally accessible to the public.

Text · e-Laws consolidated snapshot

9.9.5.6. — Mirrors or Draperies

(1) No mirror shall be placed in or adjacent to any exit so as to confuse the direction of exit, and no mirror or draperies shall be placed on or over exit doors.

Text · e-Laws consolidated snapshot

9.9.5.7. — Fuel-Fired Appliances

(1) Fuel-fired appliances shall not be installed in an exit or corridor serving as an access to exit.

Text · e-Laws consolidated snapshot

9.9.5.8. — Service Rooms

(1) Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits.

Text · e-Laws consolidated snapshot

9.9.5.9. — Ancillary Rooms

(1) Ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit.

Text · e-Laws consolidated snapshot

9.9.6. — Doors in a Means of Egress

Content not available for this version.

9.9.6.1. — Obstructions by Doors

(1) Except as provided in Sentence (4), swinging doors in their swing shall conform to Sentences (2) and (3),

(a) at exit doors,

(b) at doors that open into or are located within a public corridor, and

(c) at doors that open into or are located within another facility that provides access to exit from a suite.

(2) When fully open, doors described in Sentence (1) shall not decrease the required exit width by more than,

(a) 100 mm in exit corridors, and

(b) 50 mm for other exit facilities.

(3) The swing of doors described in Sentence (1), shall not reduce the width of the path of travel to less than,

(a) the required exit width in exit corridors and passageways, and

(b) 750 mm on exit stairs or landings.

(4) Doors serving a single dwelling unit need not comply with Sentences (2) and (3).

Text · e-Laws consolidated snapshot

9.9.6.2. — Clear Opening Height at Doorways

(1) Except as provided in Sentences (2) and (3), the clear opening height of doorways shall be not less than 2 030 mm high at,

(a) exit doors,

(b) doors that open into or are located within a public corridor, and

(c) doors that open into or are located within another facility that provides access to exit from a suite.

(2) The clear opening height under door closers and other devices in doorways described in Sentence (1) shall be not less than 1 980 mm.

(3) Doorways serving a single dwelling unit need not comply with Sentences (1) and (2).

Text · e-Laws consolidated snapshot

9.9.6.3. — Clear Opening Width at Doorways

(1) Except as provided in Sentence (4), the clear opening width of doorways shall comply with Sentence (2) at,

(a) exit doors, and

(b) doors that open into or are located within a public corridor, or

(c) doors that open into or are located within another facility that provides access to exit from a suite.

(2) Doorways described in Sentence (1) shall be not less than,

(a) 800 mm wide where there is only one door leaf,

(b) 800 mm wide where multiple-leaf doors are installed with only one active leaf with a latching mechanism described in Article 9.9.6.7, and

(c) 1210 mm wide where multiple-leaf doors are installed with two active leaves.

(3) In doorways described in Sentence (1) that have multiple-leaf doors installed,

(a) no active leaf shall be less than 810 mm wide where only one leaf is active, and

(b) no single leaf shall be less than 610 mm wide where two leaves are active.

(4) Doorways serving a single dwelling unit need not comply with Sentence (2).

Text · e-Laws consolidated snapshot

9.9.6.4. — Door Action

(1) Except as provided in Sentences (4) and (5), required exit doors and doors in required means of egress, except doors in means of egress within dwelling units, shall swing on the vertical axis.

(2) Except as provided in Sentence (5), breakaway sliding doors, installed as required exit doors or required doors in means of egress, shall be identified as swinging doors by means of a label or decal affixed to the door.

(3) Revolving doors shall comply with Article 3.4.6.14.

(4) Movable partitions used to separate a public corridor from an adjacent business and personal services occupancy or a mercantile occupancy need not conform to Sentence (1), provided the partitions are not located in the only means of egress.

(5) Exit doors need not conform to Sentences (1) or (2) where,

(a) the doors serve accessory buildings where life safety is not adversely affected, or

(b) the doors serve storage garages or other accessory buildings serving a single dwelling unit.

Editor's note

As filed in O. Reg. 350/06, Sentence (5) cites 'Sentences (1) or (2)' using the plural 'Sentences'; the consolidated e-Laws text renders the reference word in the singular ('Sentence'). No amending regulation makes this change; the as-filed wording is retained here.

9.9.6.5. — Direction of Door Swing

(1) Except for doors serving a single dwelling unit, exit doors that are required to swing shall swing in the direction of exit travel.

(2) Doors that open onto a corridor or other facility that provides access to exit from a room or suite having an occupant load of more than 60 persons shall swing on the vertical axis in the direction of exit travel.

(3) Doors that divide a corridor that is not wholly contained within a suite shall swing in the direction of exit travel.

(4) Where a pair of doors is installed in a corridor that provides access to exit in both directions, the doors shall,

(a) swing in opposite directions, with the door on the right hand side swinging in the direction of exit travel, or

(b) swing in both directions.

Text · e-Laws consolidated snapshot

9.9.6.6. — Proximity of Doors to Stairs

(1) Except as provided in Sentence (2), the distance between a stair riser and the leading edge of a door in its swing, except for doors serving a single dwelling unit, shall be not less than 300 mm.

(2) Where there is a danger of blockage from ice or snow, an exit door, including a door serving a single dwelling unit, may open onto not more than one step provided the riser of such step does not exceed 150 mm.

Text · e-Laws consolidated snapshot

9.9.6.7. — Door Latching, Locking and Opening Mechanisms

(1) Principal entrance doors, exit doors and doors to suites, including exterior doors to dwelling units, and other doors in an access to exit shall,

(a) be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door opening mechanism, or

(b) in the case of exit doors, be controlled by electromagnetic locking mechanisms in accordance with Sentence 3.4.6.15.(4)v1.

(2) Except for doors serving a single dwelling unit and doors to accessory buildings and garages serving a single dwelling unit, door release hardware on doors in a means of egress shall be operable with one hand and the door shall be openable with not more than one releasing operation.

(3) Door release hardware on doors in a means of egress shall be installed not more than 1 200 mm above the finished floor.

(4) Except for hotels, a door opening onto a public corridor that provides access to exit from suites shall be designed not to lock automatically when such doors are equipped with an automatic self-closing device.

Text · e-Laws consolidated snapshot

9.9.6.8. — Effort Required to Open

(1) Every exit door, except doors serving a single dwelling unit, shall be designed and installed so that when the latch is released the door will open in the direction of exit travel under a force of not more than 90 N applied to the door release hardware.

Text · e-Laws consolidated snapshot

9.9.7. — Access to Exits

Content not available for this version.

9.9.7.1. — Egress from Roof Area, Podiums, Terraces, Platforms and Contained Open Spaces

(1) An access to exit shall be provided from every roof intended for occupancy and from every podium, terrace, platform or contained open space.

(2) Where a roof is intended for an occupant load of more than 60 persons, at least 2 separate means of egress shall be provided from the roof to stairs designed in conformance with the requirements for exit stairs and located remote from each other.

(3) Where a podium, terrace, platform or contained open space is provided, egress requirements shall conform to the appropriate requirements for rooms or suites in Article 9.9.7.4.

Text · e-Laws consolidated snapshot

9.9.7.2. — Means of Egress from Suites

(1) Except as required in Sentence 9.9.9.3.(1), each suite in a floor area occupied by more than one suite shall have,

(a) an exterior exit doorway,

(b) a doorway to a public corridor, or

(c) a doorway to exterior passageway.

(2) Except as provided in Sentences 9.9.7.3.(1) and 9.9.8.2.(2), from the point where a doorway described in Clauses (1)(b) or (c) enters the public corridor or exterior passageway, it shall be possible to go in opposite directions to each of 2 separate exits.

Editor's note

As filed in O. Reg. 350/06, Sentence (2) cites 'Clauses (1)(b) or (c)' using the plural 'Clauses'; the consolidated e-Laws text renders the reference word in the singular ('Clause'). No amending regulation makes this change; the as-filed wording is retained here.

9.9.7.3. — Dead End Corridors

(1) A dead-end public corridor is permitted in an occupancy shown in Table 9.9.7.3. where,

(a) a dead-end corridor,

(i) does not exceed the distance of travel measured from the most remote point of the dead-end to a point where it is possible to go in opposite directions to each of two separate exits, and

(ii) is provided with doors equipped with self-closing devices, or

(b) there is a second and separate egress doorway from each room or suite not leading into the dead-end corridor.

(2) Dead-end public corridors in residential occupancies and business and personal services occupancies shall contain only suite door openings arranged so that not more than 2 such doors have to be passed to reach the nearest exit.

(3) The area of wired glass in doors required by Sentence (2) shall not exceed 645 cm².

Text · e-Laws consolidated snapshot

Table 9.9.7.3. Dead End Public Corridors Forming Part of Sentence 9.9.7.3.(1)

Column 1

Column 2

Column 3

Occupancy

Maximum Length of Dead-End Public Corridor, m

Maximum Occupant Load or Suites Served by Dead-End Public Corridor

Group C

6

4 suites

Group D

6

30

Group E

9

30

Group F

9

30

9.9.7.4. — Number and Spacing of Egress Doors

(1) Except for dwelling units, at least 2 egress doors shall be provided where,

(a) the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or

(b) the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m.

(2) Doors in Sentence (1) shall be spaced so that in the event one door is made inaccessible by a fire within such a room or suite, the other door will provide safe egress.

Text · e-Laws consolidated snapshot

9.9.7.5. — Independent Access to Exit

(1) Required access to exit from suites shall not be through any other dwelling unit, service room or other occupancy.

Text · e-Laws consolidated snapshot

9.9.7.6. — Travel Distance within Rooms and Suites

(1) Except for dwelling units, the travel distance from any point within the room or suite to the nearest egress door shall not exceed the maximum travel distance in Article 9.9.8.2.

Text · e-Laws consolidated snapshot

9.9.8. — Exits From Floor Areas

Content not available for this version.

9.9.8.1. — Measurement of Travel Distance

(1) Except as provided in Sentences (2) and (3), for the purposes of this Subsection, travel distance means the distance from any point in the floor area to an exit measured along the path of exit travel.

(2) Where a room or suite is separated from the remainder of the floor area by a fire separation having a fire-resistance rating of at least 45 min, or in a sprinklered building, by a fire separation that is not required to have a fire-resistance rating, the travel distance is permitted to be measured from an egress door of the room or suite to the nearest exit.

(3) Where a public corridor is not less than 9 m wide and conforms to Clause 3.4.2.5.(1)(d), the travel distance is permitted to be determined in accordance with that Clause.

Text · e-Laws consolidated snapshot

9.9.8.2. — Number of Required Exits

(1) Except as provided in Sentences (2) and (3) and Subsection 9.9.9., no fewer than 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than,

(a) 40 m in the case of business and personal services occupancies,

(b) 45 m for all occupancies where the floor area is sprinklered, and

(c) 30 m for all other occupancies.

(2) Except as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.

(3) In boarding, lodging or rooming houses,

(a) where sleeping accommodation is provided for not more than 8 persons, a single exit is permitted from each floor area, or

(b) where sleeping accommodation is not provided in the basement, a single exit is permitted from the basement floor area.

Text · e-Laws consolidated snapshot

9.9.8.3. — Contribution of Each Exit

(1) Where more than 1 exit is required from a floor area, each exit shall be considered as contributing not more than half the required exit width.

Text · e-Laws consolidated snapshot

9.9.8.4. — Location of Exits

(1) Where more than 1 exit is required from a floor area, no fewer than 2 exits shall be independent of each other and be placed remote from each other along the path of travel between them.

Text · e-Laws consolidated snapshot

9.9.8.5. — Exiting through a Lobby

(1) Not more than one exit from a floor area is permitted to lead through a lobby.

(2) The floor of the lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the lobby to the outdoors shall not exceed 15 m.

(3) The lobby referred to in Sentence (1) shall conform in all respects with the requirements for exits, except that rooms other than service rooms, storage rooms and rooms of residential or industrial occupancy are permitted to open directly onto such lobby.

(4) Except as required in Sentence (6), an exit is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space other than as described in Sentence 3.2.8.2.(6)v1v2.

(5) Passenger elevator entrances are permitted to open onto the lobby referred to in Sentence (1) provided the elevator doors are designed to remain closed except while loading and unloading.

(6) An exit that serves a hotel is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space.

(7) Where the lobby referred to in Sentence (1) and adjacent occupancies that are permitted to open into the lobby are sprinklered, the fire separation between such occupancies and the lobby need not have a fire-resistance rating.

Text · e-Laws consolidated snapshot

9.9.8.6. — Mezzanine Means of Egress

(1) Except as permitted by Sentences (2) and (3), the space above a mezzanine shall be served by no fewer than 2 means of egress leading to exits accessible at the mezzanine level on the same basis as floor areas.

(2) One means of egress from a mezzanine is permitted where,

(a) the mezzanine is not required to terminate at a vertical fire separation, as permitted by Sentence 9.10.12.1.(2),

(b) the occupant load of the mezzanine is not more than 60,

(c) the area of the mezzanine does not exceed the area limits of Clause 9.9.7.4.(1)(a), and

(d) the distance limits of Clause 9.9.7.4.(1)(b) measured along the path of travel, are not exceeded from any point on the mezzanine to,

(i) an egress door serving the space that the mezzanine overlooks if the space is served by a single egress door, or

(ii) an egress stairway leading to an access to exit in the space below if that space is required to be served by two or more egress doorways in conformance with Sentence 9.9.7.4.(1).

(3) One of the means of egress from a mezzanine that is not required to terminate at a fire separation as permitted by Sentence 9.10.12.1.(2) and that exceeds the limits of Sentence (2), is permitted to lead through the room in which the mezzanine is located provided all other means of egress from that mezzanine lead to exits accessible at the mezzanine level.

(4) Except as provided in Sentence (2), the maximum travel distance from any point on a mezzanine to the nearest exit shall be not more than,

(a) 40 m in a business and personal services occupancy,

(b) 45 m in a floor area that is sprinklered provided it does not contain a high hazard industrial occupancy, or

(c) 30 m in any floor area not referred to in Clauses (a) or (b).

Text · e-Laws consolidated snapshot

9.9.9. — Egress from Dwelling Units

Content not available for this version.

9.9.9.1. — Travel Limit to Exits or Egress Doors

(1) Except as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by,

(a) an egress door to a public corridor, enclosed exit stair or exterior passageway, or

(b) an exit doorway not more than 1 500 mm above adjacent ground level.

(2) Where a dwelling unit is not located above or below another suite, the travel limit from a floor level in the dwelling unit to an exit or egress door is permitted to exceed 1 storey where that floor level is served by an openable window or door,

(a) providing an unobstructed opening of not less than 1 000 mm in height and 550 mm in width, and

(b) located so that the sill is not more than,

(i) 1 000 mm above the floor, and

(ii) 7 m above adjacent ground level.

(3) The travel limit from a floor level in a dwelling unit to an exit or egress door is permitted to exceed 1 storey where that floor level has direct access to a balcony.

Text · e-Laws consolidated snapshot

9.9.9.2. — Two Separate Exits

(1) Except as provided in Sentence 9.9.7.2.(1), where an egress door from a dwelling unit opens onto a public corridor or exterior passageway it shall be possible from the location where the egress door opens onto the corridor or exterior passageway to go in opposite directions to 2 separate exits unless the dwelling unit has a second and separate means of egress.

Text · e-Laws consolidated snapshot

9.9.9.3. — Shared Egress Facilities

(1) A dwelling unit shall be provided with a second and separate means of egress where an egress door from the dwelling unit opens onto,

(a) an exit stairway serving more than 1 suite,

(b) a public corridor serving more than one suite served by a single exit stairway,

(c) an exterior passageway more than 1 500 mm above adjacent ground level, serving more than one suite and served by a single exit stairway, or

(d) a balcony more than 1 500 mm above adjacent ground level, serving more than one suite and served by a single exit stairway.

Text · e-Laws consolidated snapshot

9.9.10. — Signage

Content not available for this version.

9.9.10.1. — Application

(1) This Subsection applies to all exits except those serving not more than 1 dwelling unit.

Text · e-Laws consolidated snapshot

9.9.10.2. — Visibility of Exits

(1) Exits shall be located so as to be clearly visible or their locations shall be clearly indicated.

Text · e-Laws consolidated snapshot

9.9.10.3. — Required Exit Signs

(1) Except as required in Sentence (2), every exit door shall have an exit sign over or adjacent to it when the exit serves,

(a) a 3 storey building,

(b) a building with an occupant load greater than 150, or

(c) a room or floor area that has a fire escape as part of a required means of egress.

(2) Except for suite doors opening directly to the exterior, every exit serving a hotel shall have an exit sign placed over or adjacent to it.

Text · e-Laws consolidated snapshot

9.9.10.4. — Exit Direction Signs

(1) Exit direction signs shall be placed in corridors and passageways where necessary to indicate the direction of exit travel.

Text · e-Laws consolidated snapshot

9.9.10.5. — Visibility of Exit Signs

(1) Exit signs shall be installed so as to be visible from the exit approach.

Text · e-Laws consolidated snapshot

9.9.10.6. — Lettering

(1) Exit signs shall have the word EXIT or the words EXIT/SORTIE in red letters on a contrasting background or a red background with contrasting letters when the sign is internally lighted, and white letters on a red background or red letters on a white background when the sign is externally lighted.

(2) Lettering referred to in Sentence (1) shall be made with not less than 19 mm wide strokes and be not less than 150 mm high when the sign is externally lighted, and at least 114 mm high when the sign is internally lighted.

(3) Where an exit sign having the word EXIT is installed in conformance with Sentence (1), an additional sign having the word SORTIE is permitted to be installed.

Text · e-Laws consolidated snapshot

9.9.10.7. — Illumination

(1) Illumination of exit signs required in Article 9.9.10.3. shall conform to Sentences 9.9.11.3.(2) and (3).

(2) Where illumination of exit signs required in Article 9.9.10.3. is provided by an electrical circuit, that circuit shall serve no equipment other than emergency equipment.

Text · e-Laws consolidated snapshot

9.9.10.8. — Signs for Stairs and Ramps at Exit Level

(1) In buildings 3 storeys in building height, any part of an exit ramp or stairway that continues up or down past the lowest exit level shall be clearly marked to indicate that it does not lead to an exit where the portion below exit level may be mistaken as the direction of exit travel.

Text · e-Laws consolidated snapshot

9.9.10.9. — Floor Numbering

(1) Arabic numerals indicating the assigned floor number shall be,

(a) except in hotels, mounted permanently on the stair side of the wall at the latch side of doors to exit stair shafts,

(b) in hotels, mounted permanently on each side of the exit doors to the exit stair shaft,

(c) not less than 60 mm high, raised approximately 0.7 mm above the surface,

(d) located 1 500 mm from the finished floor and not more than 300 mm from the door, and

(e) contrasting in colour with the surface on which they are applied.

Text · e-Laws consolidated snapshot

9.9.11. — Lighting

Content not available for this version.

9.9.11.1. — Application

(1) This Subsection applies to the lighting of all exits except those serving not more than 1 dwelling unit.

Text · e-Laws consolidated snapshot

9.9.11.2. — Required Lighting in Egress Facilities

(1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.

Text · e-Laws consolidated snapshot

9.9.11.3. — Emergency Lighting

(1) Emergency lighting shall be provided in,

(a) exits,

(b) principal routes providing access to exit in an open floor area,

(c) corridors used by the public,

(d) underground walkways, and

(e) public corridors.

(2) Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.

(3) Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of not less than 30 min when the electric lighting in the affected area is interrupted.

(4) Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.

(5) Where incandescent lighting is provided, lighting equal to 1 W/m² of floor area shall be considered to meet the requirement in Sentence (4).

(6) Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141-M, “Unit Equipment for Emergency Lighting”.

Text · e-Laws consolidated snapshot

9.10. — Fire Protection

Content not available for this version.

9.10.1. — Definitions and Application

Content not available for this version.

9.10.1.1. — Support of Noncombustible Construction

(1) Where an assembly is required to be of noncombustible construction and to have a fire-resistance rating, it shall be supported by noncombustible construction.

Text · e-Laws consolidated snapshot

9.10.1.2. — Sloped Roofs

(1) For the purposes of this Section, roofs with slopes of 60° or more to the horizontal and that are adjacent to a room or space intended for occupancy shall be considered as a wall.

Text · e-Laws consolidated snapshot

9.10.1.3. — Items Under Part 3 Jurisdiction

(1) Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3.

(2) Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3.

(3) Basements containing more than 1 storey or exceeding 600 m2 in area shall conform to Part 3.

(4) Where rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall conform to Part 3.

(5) Reserved.

(6) Openings through floors that are not protected by shafts or closures shall be protected in conformance with Subsection 3.2.8.

(7) Chutes and shafts shall conform to Subsection 3.6.3. except where they are contained entirely within a dwelling unit.

(8) Where sprinkler, standpipe and hose systems are installed, they shall be installed in conformance with Part 3.

Editor's note

As filed in O. Reg. 350/06, Sentence (5) of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed text is retained here.

9.10.1.4. — Items Under Part 6 Jurisdiction

(1) In kitchens containing commercial cooking equipment used in processes producing grease-laden vapours, the equipment shall be designed and installed in conformance with Part 6

(2) Where fuel-fired appliances are installed on a roof, such appliances shall be installed in conformance with Part 6.

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 9.10.1.4. of Division B, in which Sentence (1) ('... shall be designed and installed in conformance with Part 6') ends without a sentence-ending period. The e-Laws consolidation editorially adds a terminal period, with no amending regulation making the change. This map preserves the as-filed wording.

9.10.2. — Occupancy Classification

Content not available for this version.

9.10.2.1. — Occupancy Classification

(1) Except as provided in Article 9.10.2.2., every building or part of it shall be classified according to its major occupancy as belonging to one of the groups or divisions described in Table 9.10.2.1.

Text · e-Laws consolidated snapshot

Table 9.10.2.1. Occupancy Classifications Forming Part of Sentence 9.10.2.1.(1)

Column 1

Column 2

Column 3

Group

Division

Description of Major Occupancies

C

Residential occupancy

D

Business and personal services occupancies

E

Mercantile occupancies

F

2

Medium hazard industrial occupancies

F

3

Low hazard industrial occupancies (Does not include storage garages serving individual dwelling units)

9.10.2.2. — Custodial and Convalescent Homes

(1) Children's custodial homes and convalescent homes for ambulatory occupants living as a single housekeeping unit in a suite with sleeping accommodation for not more than 10 persons are permitted to be classified as residential occupancies (Group C).

Text · e-Laws consolidated snapshot

9.10.2.3. — Major Occupancies above Other Major Occupancies

(1) Except as permitted in Article 9.10.2.4., in any building containing more than 1 major occupancy in which one major occupancy is located entirely above another, the requirements of Article 9.10.8.1. for each portion of the building containing a major occupancy shall be applied to that portion as if the entire building was of that major occupancy.

Text · e-Laws consolidated snapshot

9.10.2.4. — Buildings Containing More Than One Major Occupancy

(1) In a building containing more than 1 major occupancy, where the aggregate area of all major occupancies in a particular group or division does not exceed 10% of the floor area on the storey on which they are located, they need not be considered as major occupancies for the purposes of Articles 9.10.8.1. and 9.10.2.3. provided they are not classified as Group F, Division 2 occupancies.

Text · e-Laws consolidated snapshot

9.10.2.5. — Restaurants

(1) A restaurant is permitted to be classified as a Group E major occupancy provided such restaurant is designed to accommodate not more than 30 persons consuming food or drink.

Text · e-Laws consolidated snapshot

9.10.3. — Ratings

Content not available for this version.

9.10.3.1. — Fire-Resistance and Fire-Protection Ratings

(1) Where a fire-resistance rating or a fire-protection rating is required in this Section for an element of a building, such rating shall be determined in conformance with the test methods described in Part 3, or in accordance with Supplementary Standard SB-2.

Text · e-Laws consolidated snapshot

9.10.3.2. — Flame-Spread Rating

(1) Where a flame-spread rating is required in this Section for an element of a building, such rating shall be determined in accordance with the test methods described in Part 3, or in accordance with Supplementary Standard SB-2.

(2) Unless the flame-spread rating is referred to in this Part as a “surface flame-spread rating”, it shall apply to any surface of the element being considered that would be exposed by cutting through it as well as to the exposed surface of the element.

Text · e-Laws consolidated snapshot

9.10.3.3. — Fire Exposure

(1) Floor, roof and ceiling assemblies shall be rated for exposure to fire on the underside.

(2) Exterior walls shall be rated for exposure to fire from inside the building, except that such walls need not comply with the temperature rise limitations required by the standard tests referred to in Article 9.10.3.1.v1 if such walls have a limiting distance of not less than 1 200 mm, and due allowance is made for the effects of heat radiation in accordance with the requirements in Part 3.

(3) Firewalls and interior vertical fire separations required to have fire-resistance ratings shall be rated for exposure to fire on each side.

Text · e-Laws consolidated snapshot

9.10.3.4. — Suspended Membrane Ceiling

(1) Where a ceiling construction has a suspended membrane ceiling with lay-in panels or tiles that contribute to the required fire-resistance rating, hold down clips or other means shall be provided to prevent the lifting of such panels or tiles in the event of a fire.

Text · e-Laws consolidated snapshot

9.10.4. — Building Size Determination

Content not available for this version.

9.10.4.1. — Mezzanines not Considered as Storeys

(1) Mezzanines shall not be considered as storeys for the purpose of determining building height where the aggregate area of mezzanine floors does not exceed 10% of,

(a) the suite in which it is located, where there is more than one suite in the storey, or

(b) the storey in which it is located, in all other cases.

(2) Mezzanines shall not be considered as storeys for the purpose of determining building height where they occupy an aggregate area not exceeding 40% of the area of the room or the storey in which they are located provided the space above the mezzanine floor has no visual obstructions more than 1 070 mm above such floors.

Text · e-Laws consolidated snapshot

9.10.4.2. — More Than One Level of Mezzanine

(1) Where more than 1 level of mezzanine is provided in a storey, each level additional to the first shall be considered as a storey.

Text · e-Laws consolidated snapshot

9.10.4.3. — Basement Storage Garage

(1) Where a basement is used primarily as a storage garage, the basement is permitted to be considered as a separate building for the purposes of this Section provided the floor above the basement and the exterior walls of the basement above the adjoining ground level are constructed as fire separations of masonry or concrete having a fire-resistance rating of not less than 2 h.

Text · e-Laws consolidated snapshot

9.10.4.4. — Roof-Top Enclosures

(1) Roof-top enclosures provided for elevator machinery, stairways and service rooms, used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height.

Text · e-Laws consolidated snapshot

9.10.5. — Permitted Openings in Wall and Ceiling Assemblies

Content not available for this version.

9.10.5.1. — Permitted Openings in Wall and Ceiling Membranes

(1) Except as permitted in Sentences (2) and (4), a membrane forming part of an assembly required to have a fire-resistance rating shall not be pierced by openings into the assembly unless the assembly has been tested and rated for such openings.

(2) A wall or ceiling membrane forming part of an assembly required to have a fire-resistance rating is permitted to be pierced by openings for electrical and similar service outlet boxes provided such outlet boxes are tightly fitted.

(3) Where boxes referred to in Sentence (2) are located on both sides of walls required to provide a fire-resistance rating, they shall be offset where necessary to maintain the integrity of the fire separation.

(4) A membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of Table 1.2. in Supplementary Standard SB-3, is permitted to be pierced by openings leading to ducts within the ceiling space provided the ducts, the amount of openings and their protection conform to the requirements in Supplementary Standard SB-2.

Text · e-Laws consolidated snapshot

9.10.6. — Construction Types

Content not available for this version.

9.10.6.1. — Combustible Elements in Noncombustible Construction

(1) Where a building or part of a building is required to be of noncombustible construction, combustible elements shall be limited in conformance with the requirements in Subsection 3.1.5.

Text · e-Laws consolidated snapshot

9.10.6.2. — Heavy Timber Construction

(1) Heavy timber construction shall be considered to have a 45 min fire-resistance rating when it is constructed in accordance with the requirements for heavy timber construction in Article 3.1.4.6.

Text · e-Laws consolidated snapshot

9.10.7. — Steel Members

Content not available for this version.

9.10.7.1. — Protection of Structural Steel Members

(1) Except as permitted in Article 3.2.2.3., structural steel members used in construction required to have a fire-resistance rating shall be protected to provide the required fire-resistance rating.

Text · e-Laws consolidated snapshot

9.10.8. — Fire-Resistance and Combustibility in Relation to Occupancy, Height and Supported Elements

Content not available for this version.

9.10.8.1. — Fire-Resistance Ratings for Floors and Roofs

(1) Except as otherwise provided in this Subsection, the fire-resistance ratings of floors and roofs shall conform to Table 9.10.8.1.

Text · e-Laws consolidated snapshot

Table 9.10.8.1. Fire Resistance Ratings for Structural Members and Assemblies Forming Part of Sentence 9.10.8.1.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Major Occupancy

Maximum Building Height, Storeys

Minimum Fire-Resistance Rating by Building Element, min

Floors Except Floors over Crawl Spaces

Mezzanine Floors

Roofs

Residential (Group C)

3

45

45

All other occupancies

2

45

3

45

45

45

9.10.8.2. — Fire-Resistance Ratings in Sprinklered Buildings

(1) Except for roofs that support an occupancy, the requirements in Table 9.10.8.1. for roof assemblies to have a fire-resistance rating are permitted to be waived in sprinklered buildings where,

(a) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.9.(2)v1, and

(b) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4).

Text · e-Laws consolidated snapshot

9.10.8.3. — Fire-Resistance Ratings for Walls, Columns and Arches

(1) Except as otherwise provided in this Subsection, all loadbearing walls, columns and arches in the storey immediately below a floor or roof assembly shall have a fire-resistance rating of not less than that required for the supported floor or roof assembly.

Text · e-Laws consolidated snapshot

9.10.8.4. — Reserved.

Content not available for this version.

Editor's note

As filed in O. Reg. 350/06, the heading of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed heading is retained here.

9.10.8.5. — Service Rooms

(1) Construction supporting a service room need not conform to Article 9.10.8.3.

Text · e-Laws consolidated snapshot

9.10.8.6. — Mezzanines

(1) Mezzanines required to be counted as storeys in Articles 9.10.4.1. and 9.10.4.2. shall be constructed in conformance with the requirements for “Floors Except Floors over Crawl Spaces” in Table 9.10.8.1.

Text · e-Laws consolidated snapshot

9.10.8.7. — Roofs Supporting an Occupancy

(1) Where a portion of a roof supports an occupancy, that portion shall be constructed as a fire separation having a fire-resistance rating conforming to the rating for “Floors Except Floors over Crawl Spaces” in Table 9.10.8.1.

Text · e-Laws consolidated snapshot

9.10.8.8. — Floors of Exterior Passageways

(1) Except as provided in Sentences (2) and (3), the floor assembly of every exterior passageway used as part of a means of egress shall have a fire-resistance rating of not less than 45 min or be of noncombustible construction.

(2) No fire-resistance rating is required for floors of exterior passageways serving buildings of Group D, E or F major occupancy that are not more than 2 storeys in building height.

(3) No fire-resistance rating is required for floors of exterior passageways serving a single dwelling unit where no suite is located above or below the dwelling unit.

Text · e-Laws consolidated snapshot

9.10.8.9. — Crawl Spaces

(1) Where a crawl space exceeds 1 800 mm in height or is used for any occupancy or as a plenum in combustible construction or for the passage of flue pipes, it shall be considered as a basement in applying the requirements in Article 9.10.8.1.

Text · e-Laws consolidated snapshot

9.10.8.10. — Application to Houses

(1) Table 9.10.8.1. does not apply to a dwelling unit that has no other dwelling unit above or below it or to a dwelling unit that is not above or below another major occupancy.

Text · e-Laws consolidated snapshot

9.10.8.11. — Part 3 as an Alternative

(1) The fire-resistance ratings of floors, roofs, loadbearing walls, columns and arches need not conform to this Subsection if such assemblies conform in all respects to the appropriate requirements in Section 3.2.

Text · e-Laws consolidated snapshot

9.10.9. — Fire Separations Between Rooms and Spaces Within Buildings

Content not available for this version.

9.10.9.1. — Application

(1) This Subsection applies to fire separations required between rooms and spaces in buildings except between rooms and spaces within a dwelling unit.

Text · e-Laws consolidated snapshot

9.10.9.2. — Continuous Barrier

(1) Except as permitted in Article 9.10.9.3., a wall or floor assembly required to be a fire separation shall be constructed as a continuous barrier against the spread of fire.

(2) The continuity of a fire separation shall be maintained where it abuts another fire separation, a floor, a ceiling, a roof or an exterior wall assembly.

Text · e-Laws consolidated snapshot

9.10.9.3. — Openings to be Protected With Closures

(1) Except as permitted in Articles 9.10.9.5. to 9.10.9.7., openings in required fire separations shall be protected with closures conforming to Subsection 9.10.13.

Text · e-Laws consolidated snapshot

9.10.9.4. — Floor Assemblies

(1) Except as permitted in Sentences (2) to (4), all floor assemblies shall be constructed as fire separations.

(2) Floor assemblies contained within dwelling units need not be constructed as fire separations.

(3) Floor assemblies for which no fire-resistance rating is required by Subsection 9.10.8. and floors of mezzanines not required to be counted as storeys in Articles 9.10.4.1. and 9.10.4.2. need not be constructed as fire separations.

(4) Where a crawl space is not required by Article 9.10.8.8. to be constructed as a basement, the floor above it need not be constructed as a fire separation.

Text · e-Laws consolidated snapshot

9.10.9.5. — Interconnected Floor Spaces

(1) Except as permitted in Article 9.9.4.7., interconnected floor spaces shall conform to the requirements of Subsection 3.2.8.

Text · e-Laws consolidated snapshot

9.10.9.6. — Service Equipment Penetrating a Fire Separation

(1) Piping, tubing, ducts, chimneys, wiring, conduit, electrical outlet boxes and other similar service equipment that penetrate a required fire separation shall be tightly fitted or fire stopped to maintain the integrity of the separation.

(2) Except as provided in Sentences (3) to (9) and Article 9.10.9.7., pipes, ducts, electrical outlet boxes, totally enclosed raceways or other similar service equipment that partly or wholly penetrate an assembly required to have a fire-resistance rating shall be noncombustible unless the assembly has been tested incorporating such equipment.

(3) Electrical wires or other similar wiring enclosed in noncombustible totally enclosed raceways are permitted to partly or wholly penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (2).

(4) Electrical wires or cables, single or grouped, with combustible insulation or jacketing that is not totally enclosed in raceways of noncombustible material, are permitted to partly or wholly penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (2) provided the overall diameter of the wiring is not more than 25 mm.

(5) Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (2), where the concrete provides at least 50 mm of cover between the raceway and the bottom of slab.

(6) Combustible outlet boxes are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (2) provided the opening through the membrane into the box does not exceed 160 cm².

(7) Combustible water distribution piping that has an outside diameter not more than 30 mm is permitted to partly or wholly penetrate a vertical fire separation that is required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (2) provided the piping is sealed in conformance with Article 3.1.9.1.

(8) Combustible sprinkler piping is permitted to penetrate a fire separation provided the fire compartments on each side of the fire separation are sprinklered.

(9) Combustible piping for central vacuum systems is permitted to penetrate a fire separation provided the installation conforms to the requirements that apply to combustible piping in Sentences 9.10.9.7.(2) to (6).

Text · e-Laws consolidated snapshot

9.10.9.7. — Combustible Piping

(1) Except as permitted in Sentences (2) to (6), combustible piping shall not be used where any part of a piping system partly or wholly penetrates a fire separation required to have a fire-resistance rating or penetrates a membrane that contributes to the required fire-resistance rating of an assembly.

(2) Combustible piping not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating provided the piping is sealed at the penetration by a firestop system that has an F rating not less than the fire-resistance rating required for the fire separation.

(3) The rating referred to in Sentence (2) shall be based on ULC-S115, “Fire Tests for Firestop Systems”, with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side.

(4) Combustible drain piping is permitted to penetrate a horizontal fire separation or a membrane that contributes to the required fire-resistance rating of a horizontal fire separation provided it leads directly from a noncombustible water closet through a concrete floor slab.

(5) Combustible piping is permitted,

(a) on one side of a vertical fire separation provided it is not located in a vertical shaft, and

(b) to penetrate a vertical or horizontal fire separation when the fire compartment on each side of the fire separation is sprinklered.

(6) In buildings containing 2 dwelling units only, combustible piping is permitted on one side of a horizontal fire separation.

Text · e-Laws consolidated snapshot

9.10.9.8. — Collapse of Combustible Construction

(1) Combustible construction that abuts on or is supported by a noncombustible fire separation shall be constructed so that its collapse under fire conditions will not cause collapse of the fire separation.

Text · e-Laws consolidated snapshot

9.10.9.9. — Reduction in Thickness of Fire Separation by Beams and Joists

(1) Where pockets for the support of beams or joists are formed in a masonry or concrete fire separation, the remaining total thickness of solid masonry and/or grout and/or concrete shall be not less than the required equivalent thickness shown for type S monolithic concrete in Table 2.1.1. of the Supplementary Standard SB-2 for the required fire-resistance rating.

Text · e-Laws consolidated snapshot

9.10.9.10. — Concealed Spaces above Fire Separations

(1) Except as provided in Sentence (2), a horizontal service space or other concealed space located above a required vertical fire separation shall be divided at the fire separation by an equivalent fire separation within the space.

(2) Where a horizontal service space or other concealed space is located above a required vertical fire separation other than a vertical shaft, such space need not be divided as required in Sentence (1) provided the construction between such space and the space below is constructed as a fire separation having a fire-resistance rating not less than that required for the vertical fire separation, except that where the vertical fire separation is not required to have a fire-resistance rating greater than 45 min, the fire-resistance rating of the ceiling is permitted to be reduced to 30 min.

Text · e-Laws consolidated snapshot

9.10.9.11. — Separation of Residential Occupancies

(1) Except as provided in Sentences (2) and (4), residential occupancies shall be separated from all other major occupancies by a fire separation having a fire-resistance rating of not less than 1 h.

(2) Except as provided in Sentence (3), a major occupancy classified as a residential occupancy, including live/work units, shall be separated from other major occupancies classified as mercantile or medium hazard industrial occupancies by a fire separation having a fire-resistance rating of not less than 2 h.

(3) Where not more than 2 dwelling units or live/work units are located in a building containing a mercantile occupancy, such mercantile occupancy shall be separated from the dwelling units or live/work units by a fire separation having not less than 1 h fire-resistance rating.

(4) The requirement for fire separations between major occupancies in Sentence (1) is waived for the occupancies allowed within live/work units.

Text · e-Laws consolidated snapshot

9.10.9.12. — Residential Suites, Live/Work Units and Industrial Buildings

(1) Except as provided in Sentence (2), not more than 1 suite of residential occupancy shall be contained within a building classified as a Group F, Division 2 major occupancy.

(2) Except where a Group F Division 2 major occupancy is directly related to live/work units, not more than one suite of residential occupancy shall be contained within a building classified as Group F, Division 2 major occupancy.

Text · e-Laws consolidated snapshot

9.10.9.13. — Separation of Suites

(1) Except as required in Article 9.10.9.14., and as permitted by Sentence (2), each suite in other than business and personal services occupancies shall be separated from adjoining suites by a fire separation having a fire-resistance rating of not less than 45 min.

(2) In sprinklered buildings, suites of business and personal services occupancy and mercantile occupancy that are served by public corridors conforming with Sentence 3.3.1.4.(4)v1 are not required to be separated from each other by fire separations.

Text · e-Laws consolidated snapshot

9.10.9.14. — Separation of Residential Suites

(1) Except as provided in Sentences (2) and (3) and Article 9.10.21.2., suites in residential occupancies shall be separated from adjacent rooms and suites by a fire separation having a fire-resistance rating of not less than 45 min.

(2) Sleeping rooms in boarding, lodging or rooming houses where sleeping accommodation is provided for not more than 8 boarders or lodgers shall be separated from the remainder of the floor area by a fire separation having a fire-resistance rating of not less than 30 min where the sleeping rooms form part of the proprietor’s residence and do not contain cooking facilities.

(3) Dwelling units that contain 2 or more storeys including basements shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h.

Text · e-Laws consolidated snapshot

9.10.9.15. — Separation of Public Corridors

(1) Except as provided in Sentences (2) and (3), public corridors shall be separated from the remainder of the building by a fire separation having not less than a 45 min fire-resistance rating.

(2) In other than residential occupancies, no fire-resistance rating is required for fire separations between a public corridor and the remainder of the building if,

(a) the floor area is sprinklered,

(b) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.9.(2)v1, and

(c) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4).

(3) In other than residential occupancies, no fire separation is required between a public corridor and the remainder of the building if,

(a) the floor area is sprinklered,

(b) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.9.(2)v1,

(c) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4), and

(d) the corridor exceeds 5 m in width.

Text · e-Laws consolidated snapshot

9.10.9.16. — Separation of Storage Garages

(1) Except as provided in Sentences (2) and (3), a storage garage shall be separated from other occupancies by a fire separation having not less than a 1.5 h fire-resistance rating.

(2) Except as permitted in Sentence (3), storage garages containing 5 motor vehicles or fewer shall be separated from other occupancies by a fire separation of not less than 1 h.

(3) Where a storage garage serves only the dwelling unit to which it is attached or in which it is built, it shall be considered as part of that dwelling unit and the fire separation required in Sentence (2) need not be provided between the garage and the dwelling unit.

(4) Where a storage garage is attached to or built into a building of residential occupancy,

(a) an air barrier system conforming to Subsection 9.25.3v1, shall be installed between the garage and the remainder of the building to provide an effective barrier to gas and exhaust fumes, and

(b) every door between the garage and the remainder of the building shall conform to Article 9.10.13.15.

(5) Where membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.

Text · e-Laws consolidated snapshot

9.10.9.17. — Separation of Repair Garages

(1) Except as provided in Sentences (2) and (3), a repair garage shall be separated from other occupancies by a fire separation having a fire-resistance rating of not less than 2 h.

(2) Ancillary spaces directly serving a repair garage, including waiting rooms, reception rooms, tool and parts storage areas and supervisory office space need not be separated from the repair garage but shall be separated from other occupancies as required in Sentence (1).

(3) The fire separation referred to in Sentence (1) shall have a fire-resistance rating of not less than 1 h, where,

(a) the building is not more than one storey in building height,

(b) the building is operated as a single suite, and

(c) the only occupancy other than the repair garage is a mercantile occupancy.

(4) Where a building containing a repair garage also contains a dwelling unit, an air barrier system conforming to Subsection 9.25.3.v1 shall be installed between the dwelling unit and the suite containing the garage to provide an effective air barrier to gas and exhaust fumes.

(5) Where membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.

Text · e-Laws consolidated snapshot

9.10.9.18. — Exhaust Ducts Serving More Than One Fire Compartment

(1) Where a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure.

(2) Individual fire compartments referred to in Sentence (1) shall not have fans that exhaust directly into the duct in the vertical service space.

Text · e-Laws consolidated snapshot

9.10.9.19. — Central Vacuum Systems

(1) A central vacuum system shall serve not more than one suite.

Text · e-Laws consolidated snapshot

9.10.10. — Service Rooms

Content not available for this version.

9.10.10.1. — Application

(1) This Subsection applies to service rooms in all buildings except rooms located within a dwelling unit.

Text · e-Laws consolidated snapshot

9.10.10.2. — Service Room Floors

(1) The fire-resistance rating requirements in this Subsection do not apply to the floor assembly immediately below a service room.

Text · e-Laws consolidated snapshot

9.10.10.3. — Separation of Service Rooms

(1) Except as required in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered.

(2) Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements in Sentence (1) shall not apply.

Text · e-Laws consolidated snapshot

9.10.10.4. — Appliances and Equipment to be Located in a Service Room

(1) Except as provided in Sentence (2) and Article 9.10.10.5., fuel-fired appliances other than fireplaces shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating.

(2) Except as required in the appliance installation standards referenced in Sentences 6.2.1.4.(1) and 9.33.1.2.(1), fuel-fired space-heating appliances, space-cooling appliances and service water heaters need not be separated from the remainder of the building as required in Sentence (1) where the equipment serves,

(a) not more than one room or suite, or

(b) a building with a building area of not more than 400 m² and a building height of not more than 2 storeys.

Text · e-Laws consolidated snapshot

9.10.10.5. — Incinerators

(1) Service rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.

(2) The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, “Incinerators, Waste and Linen Handling Systems and Equipment”.

(3) Every incinerator shall be connected to a chimney flue conforming to the requirements in Section 9.21. and serving no other appliance.

(4) An incinerator shall not be located in a room with other fuel-fired appliances.

Text · e-Laws consolidated snapshot

9.10.10.6. — Storage Rooms

(1) Rooms for the temporary storage of combustible refuse in all occupancies or for public storage in residential occupancies shall be separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating, except that a 45 min fire separation is permitted where the fire-resistance rating of the floor assembly is not required to exceed 45 min, or where such rooms are sprinklered.

Text · e-Laws consolidated snapshot

9.10.10.7. — Emergency Power Installations

(1) A generator to supply emergency power for lighting and fire safety systems shall be located in a room that,

(a) is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than,

(i) 1 h, if the floor assembly is not required to have a fire-resistance rating of more than 1 h, and

(ii) 2 h, if the floor assembly is required to have a fire-resistance rating of more than 1 h, and

(b) contains only the generating set and equipment that is related to the emergency power supply system.

Text · e-Laws consolidated snapshot

9.10.11. — Firewalls

Content not available for this version.

9.10.11.1. — Required Firewalls

(1) Except as provided in Articles 9.10.11.2. and 9.10.11.4., a party wall on a property line shall be constructed as a firewall.

Text · e-Laws consolidated snapshot

9.10.11.2. — Firewalls Not Required

(1) In a building of residential occupancy in which there is no dwelling unit above another dwelling unit, a party wall on a property line between dwelling units need not be constructed as a firewall provided it is constructed as a fire separation having not less than a 1 h fire-resistance rating.

(2) The wall described in Sentence (1) shall provide continuous protection from the top of the footings to the underside of the roof deck.

(3) Any space between the top of the wall described in Sentence (1) and the roof deck shall be tightly filled with mineral wool or noncombustible material.

Text · e-Laws consolidated snapshot

9.10.11.3. — Construction of Firewalls

(1) Where firewalls are used, the requirements in Part 3 shall apply.

Text · e-Laws consolidated snapshot

9.10.11.4. — Firewalls in Detached Garages

(1) Where a garage is detached from the dwelling unit but attached to another garage on the adjacent property, the party wall so formed shall be constructed as a fire separation having a fire-resistance rating of not less than 45 min.

Text · e-Laws consolidated snapshot

9.10.12. — Prevention of Fire Spread at Exterior Walls and Between Storeys

Content not available for this version.

9.10.12.1. — Termination of Floors or Mezzanines

(1) Except as provided in Sentence (2) and in Articles 9.10.1.3. and 9.10.9.5., the portions of a floor area or mezzanine that do not terminate at an exterior wall, a firewall or a vertical shaft, shall terminate at a vertical fire separation having a fire-resistance rating not less than that required for the floor assembly that terminates at the separation.

(2) A mezzanine need not terminate at a vertical fire separation where the mezzanine is not required to be considered as a storey in Articles 9.10.4.1. and 9.10.4.2.

Text · e-Laws consolidated snapshot

9.10.12.2. — Location of Skylights

(1) Where a wall in a building is exposed to a fire hazard from an adjoining roof of a separate unsprinklered fire compartment in the same building, the roof shall contain no skylights within a horizontal distance of 5 m of the windows in the exposed wall.

Text · e-Laws consolidated snapshot

9.10.12.3. — Exterior Walls Meeting at an Angle

(1) Except as provided in Article 9.9.4.5., where exterior walls of a building meet at an external angle of less than 135°, the horizontal distance from an opening in one wall to an opening in the other wall shall be not less than 1 200 mm where the openings are in different fire compartments.

(2) The exterior wall of each fire compartment referred to in Sentence (1) within the 1 200 mm distance, shall have a fire-resistance rating not less than that required for the interior vertical fire separation between the compartment and the remainder of the building.

Text · e-Laws consolidated snapshot

9.10.12.4. — Protection of Soffits

(1) This Article applies to the portion of any soffit enclosing a projection that is,

(a) less than 2.5 m vertically above a window or door, and

(b) less than 1.2 m from either side of the window or door.

(2) Except as provided in Sentences (4) and (5), the soffit described in Sentence (1) and shall be protected in accordance with Sentence (3) where the soffit encloses,

(a) a common attic or roof space that spans more than 2 suites of residential occupancy and projects beyond the exterior wall of the building,

(b) a floor space where an upper storey projects beyond the exterior wall of a lower storey and a fire separation is required at the floor between the two storeys, or

(c) a floor space where an upper storey projects beyond the exterior wall of a lower storey, and the projection is continuous across a vertical fire separation separating two suites.

(3) Protection required by Sentence (2) shall be provided by,

(a) noncombustible material having a minimum thickness of 0.38 mm and a melting point not below 650°C,

(b) not less than 12.7 mm thick gypsum soffit board or gypsum wallboard installed according to CSA A82.31-M, “Gypsum Board Application,”

(c) not less than 11 mm thick plywood,

(d) not less than 12.5 mm thick OSB or waferboard, or

(e) not less than 11 mm thick lumber.

(4) In the case of a soffit described in Sentence (1) that is at the edge of an attic or roof space, and completely separated from the remainder of the attic or roof space by fire stopping, the requirements in Sentence (2) do not apply.

(5) Where all suites spanned by a common attic or roof space or situated above or below the projecting floor are sprinklered, the requirements in Sentence (2) do not apply provided that all rooms, including closets and bathrooms, having openings in the wall beneath the soffit are sprinklered, notwithstanding any exceptions in the sprinkler standards referenced in Article 3.2.5.13.

Text · e-Laws consolidated snapshot

9.10.13. — Doors, Dampers and Other Closures in Fire Separations

Content not available for this version.

9.10.13.1. — Closures

(1) Except as provided in Article 9.10.13.2.v1, openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with Chapters 2 to 14 of NFPA 80, “Fire Doors and Windows”, unless otherwise specified in this Part.

Text · e-Laws consolidated snapshot

Table 9.10.13.1. Fire-Protection Ratings for Closures Forming Part of Sentence 9.10.13.1.(1)

Column 1

Column 2

Required Fire-Resistance Rating of Fire Separation

Required Fire-Protection Rating of Closure

30 or 45 min

20 min(1)

1 h

45 min(1)

1.5 h

1 h

2 h

1.5 h

3 h

2 h

4 h

3 h

Notes to Table 9.10.13.1.:

(1) See Article 9.10.13.2.v1

9.10.13.2. — Solid Core Wood Door as a Closure

(1) A 45 mm thick solid core wood door is permitted to be used where a minimum fire-protection rating of 20 min is permitted or between a public corridor and a suite provided the door conforms to CAN4-S113, “Wood Core Doors Meeting the Performance Required by CAN4-S104-77 for Twenty Minute Fire-Rated Closure Assemblies”.

(2) Doors described in Sentence (1) shall have not more than a 6 mm clearance beneath and not more than 3 mm at the sides and top.

Text · e-Laws consolidated snapshot

9.10.13.3. — Unrated Wood Door Frames

(1) Doors required to provide a 20 min fire-protection rating or permitted to be 45 mm solid core wood shall be mounted in a wood frame of at least 38 mm thickness where the frame has not been tested and rated.

Text · e-Laws consolidated snapshot

9.10.13.4. — Doors as a Means of Egress

(1) Doors forming part of an exit or a public means of egress shall conform to Subsection 9.9.6. in addition to this Subsection.

Text · e-Laws consolidated snapshot

9.10.13.5. — Wired Glass as a Closure

(1) Wired glass conforming to Article 9.7.3.1. that has not been tested in accordance with Article 9.10.3.1.v1 is permitted as a closure in a vertical fire separation required to have a fire-resistance rating of not more than 1 h provided such glass is not less than 6 mm thick and is mounted in conformance with Sentence (2).

(2) Wired glass described in Sentence (1) shall be mounted in fixed steel frames having a minimum metal thickness of not less than 1.35 mm and a glazing stop of not less than 20 mm on each side of the glass.

(3) Individual panes of glass described in Sentence (1) shall not exceed 0.8 m² in area or 1 400 mm in height or width, and the area of glass not structurally supported by mullions shall not exceed 7.5 m².

Text · e-Laws consolidated snapshot

9.10.13.6. — Steel Door Frames

(1) Steel door frames forming part of a closure in a fire separation, including anchorage requirements, shall conform to CAN4-S105-M, “Fire Door Frames Meeting the Performance Required by CAN4-S104”.

Text · e-Laws consolidated snapshot

9.10.13.7. — Glass Block as a Closure

(1) Glass block that has not been tested in accordance with Article 9.10.3.1.v1 is permitted as a closure in a fire separation required to have a fire-resistance rating of not more than 1 h.

Text · e-Laws consolidated snapshot

9.10.13.8. — Maximum Size of Opening

(1) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m², with no dimension greater than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.

(2) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 22 m², with no dimension greater than 6 m, when the fire compartments on both sides of the fire separation are sprinklered.

Text · e-Laws consolidated snapshot

9.10.13.9. — Door Latch

(1) Every swing type door in a fire separation shall be equipped with a latch.

Text · e-Laws consolidated snapshot

9.10.13.10. — Self-Closing Device

(1) Except as described in Sentence (2), every door in a fire separation shall have a self-closing device.

(2) Self-closing devices are not required between public corridors and suites in business and personal services occupancies, except in,

(a) dead-end corridors, or

(b) a corridor that serves a hotel.

Text · e-Laws consolidated snapshot

9.10.13.11. — Hold-Open Devices

(1) Where hold-open devices are used on doors in required fire separations, they shall be installed in accordance with Article 3.1.8.12.v1

Text · e-Laws consolidated snapshot

9.10.13.12. — Service Room Doors

(1) Swing-type doors shall open into service rooms containing fuel-fired equipment where such doors lead to public corridors or rooms used for assembly but shall swing outward from such rooms in all other cases.

Text · e-Laws consolidated snapshot

9.10.13.13. — Fire Dampers

(1) Except as permitted in Sentences (2) to (5) and Sentence 9.10.5.1.(4)v1, a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.9.

(2) A fire damper is not required where a noncombustible branch duct pierces a required fire separation provided the duct,

(a) has a melting point not below 760°C,

(b) has a cross-sectional area less than 0.013 m², and

(c) supplies only air-conditioning units or combined air-conditioning and heating units discharging air at not more than 1 200 mm above the floor.

(3) A fire damper is not required where a noncombustible branch duct pierces a required fire separation around an exhaust duct riser in which the air flow is upward provided,

(a) the melting point of the branch duct is not below 760°C,

(b) the branch duct is carried up inside the riser at least 500 mm, and

(c) the exhaust duct is under negative pressure as described in Article 9.10.9.18.

(4) Noncombustible ducts that penetrate a fire separation separating a vertical service space from the remainder of the building need not be equipped with a fire damper at the fire separation provided,

(a) the ducts have a melting point above 760°C, and

(b) each individual duct exhausts directly to the outside at the top of the vertical service space.

(5) A duct serving commercial cooking equipment and piercing a required fire separation need not be equipped with a fire damper at the fire separation.

Text · e-Laws consolidated snapshot

9.10.13.14. — Fire Stop Flaps

(1) Fire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(4)v1 shall be constructed in conformance with Supplementary Standard SB-2.

Text · e-Laws consolidated snapshot

9.10.13.15. — Doors Between Garages and Dwelling Units

(1) A door between an attached or built-in garage and a dwelling unit shall be tight-fitting and weatherstripped to provide an effective barrier against the passage of gases and exhaust fumes and shall be fitted with a self-closing device.

(2) A doorway between an attached or built-in garage and a dwelling unit shall not be located in a room intended for sleeping.

Text · e-Laws consolidated snapshot

9.10.13.16. — Door Stops

(1) Where a door is installed so that it may damage the integrity of a fire separation if its swing is unrestricted, door stops shall be installed to prevent such damage.

Text · e-Laws consolidated snapshot

9.10.14. — Spatial Separation Between Buildings

Content not available for this version.

9.10.14.1. — Application

(1) Except as permitted in Subsection 9.10.15., this Subsection applies to all buildings.

Text · e-Laws consolidated snapshot

9.10.14.2. — Area and Location of Exposing Building Face

(1) The area of an exposing building face shall be,

(a) taken as the exterior wall area facing in one direction on any side of a building, and

(b) calculated as,

(i) the total area measured from the finished ground level to the uppermost ceiling, or

(ii) the area for each fire compartment where a building is divided into fire compartments by fire separations with fire-resistance ratings not less than 45 min.

(2) For the purpose of using Table 9.10.14.4.v1 to determine the maximum aggregate area of unprotected openings permitted in an irregularly-shaped or skewed exterior wall, the location of the exposing building face shall be taken as a vertical plane located so that there are no unprotected openings between the vertical plane and the line to which limiting distance is measured.

(3) For the purpose of using Table 9.10.14.5. to determine the required type of construction, cladding and fire-resistance rating for an irregularly-shaped or skewed exterior wall,

(a) the exposing building face is permitted to be divided into any number of portions and the fire-resistance rating, type of cladding and percentage of unprotected openings limitations is permitted to be determined individually for each portion based on the limiting distance for each portion so divided,

(b) the exposing building face shall be taken as the projection of the exterior wall onto a vertical plane located so that no portion of the exterior wall of the building is between the vertical plane and the line to which the limiting distance is established in Clause (a), and

(c) for the purpose of determining the actual area of unprotected openings permitted in an exterior wall, the unprotected openings shall be projected onto the vertical plane established in Clause (b).

(4) The required limiting distance for an exposing building face is permitted to be measured to a point beyond the property line that is not the centre line of a street, lane or public thoroughfare if,

(a) the owners of the properties on which the limiting distance is measured and the municipality enter into an agreement in which such owners agree that,

(i) each owner covenants that, for the benefit of land owned by the other covenantors, the owner will not construct a building on his or her property unless the limiting distance for exposing building faces in respect of the proposed construction is measured in accordance with the agreement,

(ii) the covenants contained in the agreement are intended to run with the lands, and the agreement shall be binding on the parties and their respective heirs, executors, administrators, successors and assigns,

(iii) the agreement shall not be amended or deleted from title without the consent of the municipality, and

(iv) they will comply with such other conditions as the municipality considers necessary, including indemnification of the municipality by the other parties, and

(b) the agreement referred to in Clause (a) is registered against the title of the properties to which it applies.

(5) Where an agreement referred to in Sentence (4) is registered against the title of a property, the limiting distance for exposing building faces in respect of the construction of any buildings on the property shall be measured to the point referred to in the agreement.

Text · e-Laws consolidated snapshot

9.10.14.3. — Inadequate Fire Fighting Facilities

(1) Where there is no fire department or where a fire department is not organized, trained and equipped to meet the needs of the community, the required limiting distance determined from Sentences 9.10.14.4.(2)v1, (5) and (6) and Sentence 9.10.14.5.(6), shall be doubled for a building that is not sprinklered.

Text · e-Laws consolidated snapshot

9.10.14.4. — Openings in Exposing Building Face

(1) Except as provided in Sentences (3) to (7) and Sentence 9.10.14.6.(1), the maximum aggregate area of unprotected openings in an exposing building face shall,

(a) conform to Table 9.10.14.4.,

(b) conform to Subsection 3.2.3., or

(c) be equal to or less than,

(i) the limiting distance squared, for residential occupancies, business and personal services occupancies and low hazard industrial occupancies, and

(ii) twice the limiting distance squared, for mercantile occupancies and medium hazard industrial occupancies.

(2) Openings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire protection rating is in conformance with the fire-resistance rating required for the wall.

(3) The maximum aggregate area of unprotected openings shall be not more than twice the area determined according to Sentence (1) where the unprotected openings are glazed with,

(a) wired glass in steel frames as described in Article 9.10.13.5., or

(b) glass blocks, as described in Article 9.10.13.7.

(4) Where the building is sprinklered, the maximum aggregate area of unprotected openings shall be not more than twice the area determined according to Sentence (1) provided all rooms, including closets and bathrooms, that are adjacent to the exposing building face and that have unprotected openings are sprinklered, notwithstanding any exemptions in the sprinkler standards referenced in Article 3.2.5.13.

(5) The maximum aggregate area of unprotected openings in an exposing building face of a storage garage need not comply with Sentence (1) where,

(a) all storeys are constructed as open-air storeys, and

(b) the storage garage has a limiting distance of not less than 3 m.

(6) The maximum aggregate area of unprotected openings in an exposing building face of a storey that faces a street and is the same level as the street need not comply with Sentence (1) where the limiting distance is not less than 9 m.

(7) The limits on area of unprotected openings need not apply to the exposing building face of a detached garage or accessory building facing a dwelling unit, where,

(a) the detached garage or accessory building serves a single dwelling unit,

(b) the detached garage or accessory building is located on the same property as that dwelling unit, and

(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

Text · e-Laws consolidated snapshot

Table 9.10.14.4. Maximum Aggregate Area of Unprotected Openings in Exterior Walls Forming Part of Sentence 9.10.14.4.(1)

Column 1

Column 2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Occupancy Classification of Building

Maximum Total Area of Exposing Building Face, m²

Maximum Aggregate Area of Unprotected Openings, % of Exposing Building Face Area

Limiting Distance, m

Less than 1.2

1.2

1.5

2

2.5

3

4

6

8

10

12

16

20

25

Residential, business and personal services and low-hazard industrial

10

0

8

12

21

33

55

96

100

15

0

8

10

17

25

37

67

100

20

0

8

10

15

21

30

53

100

25

0

8

9

13

19

26

45

100

30

0

7

9

12

17

23

39

88

100

40

0

7

8

11

15

20

32

69

100

50

0

7

8

10

14

18

28

57

100

100

0

7

8

9

11

13

18

34

56

84

100

Over 100

0

7

7

8

9

10

12

19

28

40

55

92

100

Mercantile and medium-hazard industrial

10

0

4

6

10

17

25

48

100

15

0

4

5

8

13

18

34

82

100

20

0

4

5

7

11

15

27

63

100

25

0

4

5

7

9

13

22

51

94

100

30

0

4

4

6

9

12

20

44

80

100

40

0

4

4

6

8

10

16

34

61

97

100

50

0

4

4

5

7

9

14

29

50

79

100

100

0

4

4

4

5

6

9

17

28

42

60

100

Over 100

0

4

4

4

4

5

6

10

14

20

27

46

70

100

9.10.14.5. — Construction of Exposing Building Face and Walls above Exposing Building Face

(1) Except as permitted in Sentences (2) to (7), each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with Table 9.10.14.5. and Subsection 9.10.8.

(2) Cladding on exposing building faces and exterior walls located above exposing building faces need not conform to the type of cladding required by Table 9.10.14.5. where,

(a) the exposing building face is constructed with no unprotected openings,

(b) the limiting distance is not less than 0.6 m, and

(c) the cladding,

(i) conforms to Subsection 9.27.13.,

(ii) is installed without furring members over not less than 12.7 mm thick gypsum sheathing or over masonry,

(iii) has a flame-spread rating not more than 25 when tested in accordance with Sentence 3.1.12.1.(2), and

(iv) is not more than 2 mm in thickness exclusive of fasteners, joints and local reinforcements.

(3) Except as provided in Sentence (4), where a garage or accessory building serves a single dwelling unit and is detached from any building, the exposing building face,

(a) need not conform to the minimum required fire-resistance rating in Table 9.10.14.5., where the limiting distance is 0.6 m or more,

(b) shall have a fire-resistance rating of not less than 45 min where the limiting distance is less than 0.6 m, and

(c) need not conform to the type of cladding required in Table 9.10.14.5. regardless of the limiting distance.

(4) The requirements for fire-resistance rating, type of construction and type of cladding need not apply to the exposing building faces of a dwelling unit and a detached garage or accessory building that face each other, where,

(a) the detached garage or accessory building serves a single dwelling unit,

(b) the detached garage or accessory building is located on the same property as that dwelling unit, and

(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

(5) Except for buildings containing 1 or 2 dwelling units only, combustible projections on the exterior of a wall that are more than 1 000 mm above ground level, such as balconies, platforms, canopies, eave projections and stairs, and that could expose an adjacent building to fire spread, shall not be permitted within,

(a) 1.2 m of a property line or the centre line of a public way, or

(b) 2.4 m of a combustible projection on another building on the same property.

(6) Heavy timber and steel columns need not conform to the requirements of Sentence (1) provided the limiting distance is not less than 3 m.

(7) Non-loadbearing wall components need not have a minimum fire-resistance rating where,

(a) the building is 1 storey in building height,

(b) the building is of noncombustible construction,

(c) the building is classified as low hazard industrial occupancy and is used only for low fire load occupancies such as power generating plants or plants for the manufacture or storage of noncombustible materials, and

(d) the exposing building face has a limiting distance of 3 m or more.

Text · e-Laws consolidated snapshot

Table 9.10.14.5. Minimum Construction Requirements for Exposing Building Faces Forming Part of Sentence 9.10.14.5.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Occupancy Classification of Building

Maximum Area of Unprotected Openings Permitted, % of Exposing Building Face Area

Minimum Required Fire-Resistance Rating

Type of Construction Required

Type of Cladding Required

Residential, business and personal services, and low-hazard industrial

0 - 10

1 h

Noncombustible

Noncombustible

>10 but ≤25

1 h

Combustible or noncombustible

Noncombustible

>25 but <100

45 min

Combustible or noncombustible

Combustible or noncombustible

Mercantile and medium-hazard industrial

0 - 10

2 h

Noncombustible

Noncombustible

>10 but ≤25

2 h

Combustible or noncombustible

Noncombustible

>25 but <100

1 h

Combustible or noncombustible

Combustible or noncombustible

9.10.14.6. — Minor Openings in Exposing Building Face

(1) An opening in an exposing building face not more than 130 cm2 shall not be considered an unprotected opening.

Text · e-Laws consolidated snapshot

9.10.15. — Spatial Separation Between Houses

Content not available for this version.

9.10.15.1. — Application

(1) This Subsection applies to buildings that,

(a) contain only dwelling units and have no dwelling unit above another dwelling unit, and

(b) are not designed in accordance with Subsection 9.10.14.

Text · e-Laws consolidated snapshot

9.10.15.2. — Area and Location of Exposing Building Face

(1) The area of an exposing building face shall be,

(a) taken as the exterior wall area facing in one direction on any side of a building, and

(b) calculated as,

(i) the total area measured from the finished ground level to the uppermost ceiling,

(ii) the area for each fire compartment where a building is divided into fire compartments by fire separations with fire-resistance ratings not less than 45 min, or

(iii) where Table 9.10.15.4.v1 is used to determine maximum area of glazed openings, the area of any number of individual vertical portions of the wall measured from the finished ground level to the uppermost ceiling.

(2) For the purpose of using Table 9.10.15.4.v1 to determine the maximum permitted area of glazed openings in an irregularly-shaped or skewed exterior wall, the location of the exposing building face shall be taken as a vertical plane located so that there are no glazed openings between the vertical plane and the line to which the limiting distance is measured.

(3) For the purpose of using Table 9.10.15.5. to determine the required type of construction, cladding and fire-resistance rating for an irregularly-shaped or skewed exterior wall,

(a) the location of the exposing building face shall be taken as a vertical plane located so that no portion of the actual exposing building face is between the vertical plane and the line to which the limiting distance is measured, and

(b) the value for the maximum aggregate area of glazed openings in Table 9.10.15.5. shall be determined using the limiting distance measured from the location described in Clause (a).

(4) The required limiting distance for an exposing building face is permitted to be measured to a point beyond the property line that is not the centre line of a street, lane or public thoroughfare if,

(a) the owners of the properties on which the limiting distance is measured and the municipality enter into an agreement in which such owners agree that,

(i) each owner covenants that, for the benefit of land owned by the other covenantors, the owner will not construct a building on his or her property unless the limiting distance for exposing building faces in respect of the proposed construction is measured in accordance with the agreement,

(ii) the covenants contained in the agreement are intended to run with the lands, and the agreement shall be binding on the parties and their respective heirs, executors, administrators, successors and assigns,

(iii) the agreement shall not be amended or deleted from title without the consent of the municipality, and

(iv) they will comply with such other conditions as the municipality considers necessary, including indemnification of the municipality by the other parties, and

(b) the agreement referred to in Clause (a) is registered against the title of the properties to which it applies.

(5) Where an agreement referred to in Sentence (4) is registered against the title of a property, the limiting distance for exposing building faces in respect of the construction of any buildings on the property shall be measured to the point referred to in the agreement.

Text · e-Laws consolidated snapshot

9.10.15.3. — Inadequate Firefighting Facilities

(1) Where there is no fire department or where a fire department is not organized, trained and equipped to meet the needs of the community, the required limiting distance determined from Sentences 9.10.15.4.(2)v1, (5) and (6) and Sentence 9.10.15.5.(6), shall be doubled for a building that is not sprinklered.

Editor's note

As filed in O. Reg. 350/06, this heading reads 'Inadequate Firefighting Facilities'; the consolidated e-Laws text renders 'Firefighting' as two words ('Inadequate Fire fighting Facilities'). The as-filed heading is retained here.

Text · e-Laws consolidated snapshot

9.10.15.4. — Glazed Openings in Exposing Building Face

(1) Except as provided in Sentences (3) to (5), the maximum area of glazed openings in an exposing building face shall,

(a) conform to Table 9.10.15.4.,

(b) conform to Subsection 3.2.3., or

(c) be equal to or less than the limiting distance squared.

(2) Where the exposing building face is divided into individual portions as described in Subclause 9.10.15.2.(1)(b)(iii),

(a) the maximum glazed area of each individual portion shall be determined in accordance with Sentence (1),

(b) the maximum aggregate glazed area for the entire exposing building face shall be the sum of the individual maximum glazed areas determined from Clause (a), and

(c) except as required in Sentence (4), the maximum aggregate glazed area determined in Clause (b) is permitted to be distributed anywhere on the exposing building face.

(3) The limits on area of glazed openings shall not apply to the exposing building face of a dwelling unit facing a detached garage or accessory building where,

(a) the detached garage or accessory building serves only one dwelling unit,

(b) the detached garage or accessory building is located on the same property as that dwelling unit, and

(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

(4) Except as permitted in Sentence (5), openings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire-protection rating is in conformance with the fire-resistance rating required for the wall.

(5) An opening in an exposing building face not more than 130 cm2 shall not be considered an unprotected opening.

Text · e-Laws consolidated snapshot

Table 9.10.15.4. Maximum Area of Glazed Openings in Exterior Walls of Buildings Containing Only Dwelling Units Forming Part of Sentence 9.10.15.4.(1)

Column 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Maximum Total Area of Exposing Building Face, m²

Maximum Aggregate Area of Glazed Openings, % of Exposing Building Face Area

Limiting Distance, m

Less than 1.2

1.2

1.5

2

2.5

3

4

6

8

10

12

16

20

25

10

0

8

12

21

33

55

96

100

15

0

8

10

17

25

37

67

100

20

0

8

10

15

21

30

53

100

25

0

8

9

13

19

26

45

100

30

0

7

9

12

17

23

39

88

100

40

0

7

8

11

15

20

32

69

100

50

0

7

8

10

14

18

28

57

100

100

0

7

8

9

11

13

18

34

56

84

100

Over 100

0

7

7

8

9

10

12

19

28

40

55

92

100

9.10.15.5. — Construction of Exposing Building Face of Houses

(1) Except as provided in Sentences (2) to (4) and (6), each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with Table 9.10.15.5. and Subsection 9.10.8.,

(a) for the exposing building face as a whole, or

(b) for any number of separate portions of the exposing building face.

(2) Sentence (1) does not apply where,

(a) the limiting distance is not less than1.2 m,

(b) the limiting distance is less than 1.2 m but not less than 0.6 m, provided that the exposing building face has a fire-resistance rating of not less than 45 min, or

(c) the limiting distance is less than 0.6 m, provided that the exposing building face has a fire-resistance rating of not less than 45 min and is clad with noncombustible material.

(3) Where the limiting distance is less than 0.6 m, cladding on the exposing building face and on exterior walls located above the exposing building face that enclose an attic or roof spaces need not be noncombustible, provided the cladding,

(a) conforms to Subsection 9.27.13.,

(b) is installed without furring members over not less than 12.7 mm thick gypsum sheathing or over masonry,

(c) has a flame-spread rating not more than 25 when tested in accordance with Sentence 3.1.12.1.(2), and

(d) is not more than 2 mm in thickness exclusive of fasteners, joints and local reinforcements.

(4) The requirements for fire-resistance rating, type of construction and type of cladding need not apply to the exposing building faces of a dwelling unit and a detached garage or accessory building that face each other, where,

(a) the detached garage or accessory building serves a single dwelling unit,

(b) the detached garage or accessory building is located on the same property as that dwelling unit, and

(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

(5) Except for buildings containing 1 or 2 dwelling units only, combustible projections on the exterior of a wall that are more than 1 000 mm above ground level, such as balconies, platforms, canopies, eave projections and stairs, and that could expose an adjacent building to fire spread, shall not be permitted within,

(a) 1.2 m of a property line or the centre line of a public way, or

(b) 2.4 m of a combustible projection on another building on the same property.

(6) Heavy timber and steel columns need not conform to the requirements of Sentence (1) provided the limiting distance is not less than 3 m.

Text · e-Laws consolidated snapshot

Table 9.10.15.5. Minimum Construction Requirements for Exposing Building Faces of Buildings Containing only Dwelling Units Forming Part of Sentence 9.10.15.5.(1)

Column 1

Column 2

Column 3

Column 4

Maximum Area of Glazed Openings Permitted, % of Exposing Building Face Area

Minimum Required Fire-Resistance Rating

Type of Construction Required

Type of Cladding Required

0 - 10

1 h

Noncombustible

Noncombustible

>10 but ≤25

1 h

Combustible or noncombustible

Noncombustible

>25 but <100

45 min

Combustible or noncombustible

Combustible or noncombustible

9.10.16. — Fire Stops

Content not available for this version.

9.10.16.1. — Required Fire Stops in Concealed Spaces

(1) Concealed spaces in interior walls, ceilings and crawl spaces shall be separated by fire stops from concealed spaces in exterior walls and attic or roof spaces.

(2) Fire stops shall be provided at all interconnections between concealed vertical and horizontal spaces in interior coved ceilings, drop ceilings and soffits where the exposed construction materials within the concealed spaces have a surface flame-spread rating greater than 25.

(3) Fire stops shall be provided at the top and bottom of each run of stairs where they pass through a floor containing concealed space in which the exposed construction materials within the space have a surface flame-spread rating greater than 25.

(4) In unsprinklered buildings of combustible construction, every concealed space created by a ceiling, roof space or unoccupied attic space shall be separated by fire stops into compartments of not more than not more than 300 m² in area where such space contains exposed construction materials having a surface flame-spread rating greater than 25.

(5) No dimension of the concealed space described in Sentence (4) shall exceed 20 m.

(6) Concealed spaces in mansard or gambrel style roofs, exterior cornices, balconies and canopies of combustible construction in which the exposed construction materials within the space have a surface flame-spread rating exceeding 25 shall have vertical fire stops at intervals of not more than 20 m and at points where such concealed spaces extend across the ends of required vertical fire separations.

Text · e-Laws consolidated snapshot

9.10.16.2. — Required Fire Stops in Wall Assemblies

(1) Except as permitted in Sentences (2) and (3), fire stops shall be provided to block off concealed spaces within wall assemblies, including spaces created by furring,

(a) at each floor level,

(b) at each ceiling level where the ceiling contributes to part of the required fire-resistance rating, and

(c) at other locations within the wall, so that the distance between fire stops does not exceed 20 m horizontally and 3 m vertically.

(2) Fire stops required in Sentence (1) are not required provided,

(a) the width of the concealed wall space does not exceed 25 mm,

(b) the exposed construction materials within the space are noncombustible, or

(c) the exposed construction materials within the space, including insulation, but not including wiring, piping or similar services, have a flame-spread rating of not more than 25.

(3) Fire stops required in Sentence (1) are not required provided the wall space is filled with insulation.

Text · e-Laws consolidated snapshot

9.10.16.3. — Fire Stop Materials

(1) Except as permitted in Sentence (2), fire stops shall be constructed of,

(a) not less than 0.38 mm sheet steel,

(b) not less than 6 mm asbestos board,

(c) not less than 12.7 mm gypsum wallboard,

(d) not less than 12.5 mm plywood, OSB or waferboard, with joints having continuous support,

(e) no fewer than 2 layers of 19 mm lumber with joints staggered,

(f) not less than 38 mm lumber, or

(g) materials conforming to Sentence 3.1.11.7.(1).

(2) In a building permitted to be of combustible construction, semi-rigid fibre insulation board produced from glass, rock or slag, is permitted to be used to block the vertical space in a double-frame wall assembly formed at the intersection of the floor assembly and the walls, provided the width of the vertical space is not more than 25 mm and the insulation board,

(a) has a density not less than 45 kg/m3,

(b) is securely fastened to one set of studs,

(c) extends from below the bottom of the top plates in the lower storey to above the top of the bottom plate in the upper storey, and

(d) completely fills the nominal gap of 25 mm between the headers and between the wall plates.

Text · e-Laws consolidated snapshot

9.10.16.4. — Penetration of Fire Stops

(1) Where fire stops are pierced by pipes, ducts or other elements, the effectiveness of the fire stops shall be maintained around such elements.

Text · e-Laws consolidated snapshot

9.10.17. — Flame Spread Limits

Content not available for this version.

9.10.17.1. — Flame Spread Rating of Interior Surfaces

(1) Except as otherwise provided in this Subsection, the exposed surface of every interior wall and ceiling, including skylights and glazing, shall have a surface flame-spread rating of not more than 150.

(2) Except as permitted in Sentence (3), doors need not conform to Sentence (1) provided they have a surface flame-spread rating of not more than 200.

(3) Doors within dwelling units, other than vehicle garage doors, need not conform to Sentences (1) and (2).

Text · e-Laws consolidated snapshot

9.10.17.2. — Ceilings in Exits or Public Corridors

(1) At least 90% of the exposed surface of every ceiling in an exit or unsprinklered ceiling in a public corridor shall have a surface flame-spread rating of not more than 25.

Text · e-Laws consolidated snapshot

9.10.17.3. — Walls in Exits

(1) Except as provided in Sentence (2), at least 90% of the exposed surfaces of every wall in an exit shall have a surface flame-spread rating of not more than 25.

(2) At least 75% of the wall surface of a lobby used as an exit in Article 9.9.8.5. shall have a surface flame-spread rating of not more than 25.

Text · e-Laws consolidated snapshot

9.10.17.4. — Exterior Exit Passageways

(1) Where an exterior exit passageway provides the only means of egress from the rooms or suites it serves, the wall and ceiling finishes of that passageway, including the soffit beneath and the guard on the passageway, shall have a surface flame-spread rating of not more than 25, except that up to 10% of the total wall area and 10% of the total ceiling area is permitted to have a surface flame-spread rating of not more than 150.

Text · e-Laws consolidated snapshot

9.10.17.5. — Walls in Public Corridors

(1) At least 90% of the total wall surface in any unsprinklered public corridor shall have a surface flame-spread rating of not more than 75, or at least 90% of the upper half of such walls shall have a surface flame-spread rating of not more than 25.

Text · e-Laws consolidated snapshot

9.10.17.6. — Calculation of Wall and Ceiling Areas

(1) Skylights, glazing, combustible doors, and combustible light diffusers and lenses shall not be considered in the calculation of wall and ceiling areas in this Subsection.

Text · e-Laws consolidated snapshot

9.10.17.7. — Corridors Containing an Occupancy

(1) Where a public corridor or a corridor used by the public contains an occupancy, the interior finish materials used on the walls or ceiling of such occupancy shall have a surface flame-spread rating in conformance with that required for public corridors.

Text · e-Laws consolidated snapshot

9.10.17.8. — Light Diffusers and Lenses

(1) Light diffusers and lenses having flame-spread ratings that exceed those permitted for the ceiling finish, shall conform to the requirements of Sentence 3.1.13.4.(1).

Text · e-Laws consolidated snapshot

9.10.17.9. — Combustible Skylights

(1) Individual combustible skylights in corridors required to be separated from the remainder of the building by fire separations shall not exceed 1 m² in area and shall be spaced not less than 1 200 mm apart.

Text · e-Laws consolidated snapshot

9.10.17.10. — Protection of Foamed Plastics

(1) Except as provided in Sentence (2), foamed plastics that form part of a wall or ceiling assembly in combustible construction shall be protected from adjacent space in the building other than adjacent concealed spaces within attic or roof spaces, crawl spaces, and wall assemblies, by,

(a) one of the finishes described in Subsections 9.29.4. to 9.29.9.,

(b) sheet metal mechanically fastened to the supporting assembly independent of the insulation and having a thickness of not less than 0.38 mm and a melting point not below 650°C provided the building does not contain a Group C major occupancy, or

(c) any thermal barrier that meets the requirements of Clause 3.1.5.11.(2)(e).

(2) Foamed plastic insulation having a flame-spread rating of not more than 500 is permitted to be used in factory-assembled doors in storage garages serving buildings of residential occupancy provided that,

(a) the insulation is covered on the interior with a metallic foil,

(b) the assembly has a surface flame-spread rating of not more than 200, and

(c) the assembly incorporates no air spaces.

Text · e-Laws consolidated snapshot

9.10.17.11. — Walls and Ceilings in Bathrooms

(1) The interior finish of walls and ceilings in bathrooms within suites of residential occupancy shall have a surface flame-spread rating of not more than 200.

Text · e-Laws consolidated snapshot

9.10.17.12. — Coverings or Linings of Ducts

(1) Where a covering or a lining is used with a duct, such lining or covering shall have a flame-spread rating conforming to Part 6.

Text · e-Laws consolidated snapshot

9.10.18. — Alarm and Detection Systems

Content not available for this version.

9.10.18.1. — Access Provided through a Firewall

(1) Where access is provided through a firewall, the requirements in this Subsection shall apply to the floor areas on both sides of the firewall as if they were in the same building.

Text · e-Laws consolidated snapshot

9.10.18.2. — Fire Alarm System Required

(1) Except as provided in Sentence (2), a fire alarm system shall be installed,

(a) in every building that contains more than 3 storeys, including storeys below the first storey,

(b) where the total occupant load exceeds 300, or

(c) when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.

(2) A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.

Text · e-Laws consolidated snapshot

Table 9.10.18.2. Maximum Occupant Load for Buildings without Fire Alarm Systems Forming Part of Sentence 9.10.18.2.(1)

Column 1

Column 2

Major Occupancy Classification

Occupant Load Above which

Fire Alarm System is Required

Residential

10 (sleeping accommodation)

Business and personal services, mercantile

150 above or below the first storey

Low- or medium-hazard industrial

75 above or below the first storey

9.10.18.3. — Rooms and Spaces Requiring Heat Detectors or Smoke Detectors

(1) Where a fire alarm system is required, every public corridor in buildings of residential occupancy and every exit stair shaft shall be provided with smoke detectors.

(2) Except as provided in Sentence (3), buildings required to have a fire alarm system shall be equipped with heat detectors or smoke detectors in storage rooms, service rooms, elevator shafts, chutes, janitors closets and any other rooms where hazardous substances are intended to be used or stored.

(3) Except as required in Sentence (4), heat detectors and smoke detectors described in Sentence (2), are not required in dwelling units or in sprinklered buildings in which the sprinkler system is electrically supervised and equipped with a water flow alarm.

(4) Where a fire alarm system is required in a hotel, heat detectors shall be installed in every room in a suite and in every room not located in a suite in a floor area containing a hotel other than washrooms within a suite, saunas, refrigerated areas and swimming pools.

Text · e-Laws consolidated snapshot

9.10.18.4. — Smoke Detectors in Recirculating Air Handling Systems

(1) Except for a recirculating air system serving not more than 1 dwelling unit, where a fire alarm system is required to be installed, every recirculating air handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector where such system supplies more than one suite on the same floor or serves more than 1 storey.

Text · e-Laws consolidated snapshot

9.10.18.5. — Portions of Buildings Considered as Separate Buildings

(1) Except as provided in Sentence (2), where a vertical fire separation having a fire-resistance rating of at least 1 h separates a portion of a building from the remainder of the building and there are no openings through the fire separation other than those for piping, tubing, wiring and conduit, the requirements for fire alarm and detection systems is permitted to be applied to each portion so separated as if it were a separate building.

(2) The permission in Sentence (1) to consider separated portions of a building as separate buildings does not apply to service rooms and storage rooms.

Text · e-Laws consolidated snapshot

9.10.18.6. — Design and Installation Requirements

(1) Fire alarm, fire detection and smoke detection devices and systems, and their installation, shall conform to Subsection 3.2.4.

Text · e-Laws consolidated snapshot

9.10.18.7. — Reserved.

Content not available for this version.

Editor's note

As filed in O. Reg. 350/06, the heading of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed heading is retained here.

9.10.18.8. — Open-Air Storage Garages

(1) Except as required in Article 9.10.18.1., a fire alarm system is not required in a storage garage conforming to Article 3.2.2.83. provided there are no other occupancies in the building.

Text · e-Laws consolidated snapshot

9.10.18.9. — Fire Alarm System in a Hotel

(1) If a fire alarm system is required in a building containing a hotel, a single stage fire alarm system shall be provided.

Text · e-Laws consolidated snapshot

9.10.19. — Smoke Alarms

Content not available for this version.

9.10.19.1. — Required Smoke Alarms

(1) Smoke alarms conforming to CAN/ULC-S531, “Smoke Alarms”, shall be installed in each dwelling unit and in each sleeping room not within a dwelling unit.

Text · e-Laws consolidated snapshot

9.10.19.2. — Location of Smoke Alarms

(1) Within dwelling units, sufficient smoke alarms shall be installed so that,

(a) there is at least one smoke alarm on each floor level, including basements, that is 900 mm or more above or below an adjacent floor level,

(b) each bedroom is protected by a smoke alarm either inside the bedroom or, if outside, within 5 m, measured following corridors and doorways, of the bedroom door, and

(c) the distance, measured following corridors and doorways, from any point on a floor level to a smoke alarm on the same level does not exceed 15 m.

(2) Smoke alarms required in Article 9.10.19.1. and Sentence (1) shall be installed on or near the ceiling.

(3) Smoke alarms required in Sentences (1) and (2) shall be audible within the bedrooms when the intervening doors are closed.

(4) Smoke alarms required in Sentences (1) and (2) shall be installed in conformance with the manufacturers instructions.

Text · e-Laws consolidated snapshot

9.10.19.3. — Power Supply

(1) Except as permitted in Sentence (2), smoke alarms shall be installed by permanent connections to an electrical circuit and shall have no disconnect switch between the overcurrent circuit device and the smoke alarm.

(2) Where the building is not supplied with electrical power, smoke alarms are permitted to be battery operated.

Text · e-Laws consolidated snapshot

9.10.19.4. — Interconnection of Smoke Alarms

(1) Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound.

Text · e-Laws consolidated snapshot

9.10.19.5. — Instructions for Maintenance and Care

(1) Where instructions are necessary to describe the maintenance and care required for smoke alarms to ensure continuing satisfactory performance, they shall be posted in a location where they will be readily available to the occupants for reference.

Text · e-Laws consolidated snapshot

9.10.19.6. — Silencing of Alarm Noise

(1) A manually operated device is permitted to be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that it will silence the signal emitted by the smoke alarm for a period of not more than 10 min, after which the smoke alarm will reset and again sound the alarm if the level of smoke in the vicinity is sufficient to reactuate the smoke alarm.

Text · e-Laws consolidated snapshot

9.10.20. — Firefighting

Content not available for this version.

Editor's note

As filed in O. Reg. 350/06, this heading reads 'Firefighting' (a single word); the consolidated e-Laws text renders it as two words ('Fire fighting'). The as-filed heading is retained here.

9.10.20.1. — Windows or Access Panels Required

(1) Except as provided in Sentence (3), a window or access panel providing an opening not less than 1 100 mm high and 550 mm wide and having a sill height of not more than 900 mm above the floor shall be provided on the second and third storeys of every building in at least one wall facing on a street if such storeys are not sprinklered.

(2) Access panels required in Sentence (1) shall be readily openable from both inside and outside or be glazed with plain glass.

(3) Access panels required in Sentence (1) need not be provided in buildings containing only dwelling units where there is no dwelling unit above another dwelling unit.

Text · e-Laws consolidated snapshot

9.10.20.2. — Access to Basements

(1) Except in basements serving not more than one dwelling unit, each unsprinklered basement exceeding 25 m in length or width shall be provided with direct access to the outdoors to at least one street.

(2) Access required in Sentence (1) is permitted to be provided by a door, window or other means that provides an opening not less than 1 100 mm high and 550 mm wide, the sill height of which shall not be more than 900 mm above the floor.

(3) Access required in Sentence (1) is also permitted to be provided by an interior stair accessible from the outdoors.

Text · e-Laws consolidated snapshot

9.10.20.3. — Fire Department Access to Buildings

(1) Access for fire department equipment shall be provided to each building by means of a street, private roadway or yard

(2) Where access to a building as required in Sentence (1) is provided by means of a roadway or yard, the design and location of such roadway or yard shall take into account connection with public thoroughfares, weight of fire fighting equipment, width of roadway, radius of curves, overhead clearance, location of fire hydrants, location of fire department connections and vehicular parking.

Text · e-Laws consolidated snapshot

9.10.20.4. — Portable Extinguishers

(1) Portable extinguishers shall be installed in all buildings, except within dwelling units, in conformance with the provisions of the Fire Code made under the Fire Protection and Prevention Act, 1997.

Text · e-Laws consolidated snapshot

9.10.20.5. — Freeze Protection for Fire Protection Systems

(1) Equipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.

Text · e-Laws consolidated snapshot

9.10.21. — Fire Protection for Construction Camps

Content not available for this version.

9.10.21.1. — Requirements for Construction Camps

(1) Except as provided in Articles 9.10.21.2. to 9.10.21.9., camps for housing of workers shall conform to Subsections 9.10.1. to 9.10.20.

Text · e-Laws consolidated snapshot

9.10.21.2. — Separation of Sleeping Rooms

(1) Except for sleeping rooms within dwelling units, sleeping rooms in a building in a camp for housing of workers shall be separated from each other and from the remainder of the building by a fire separation having not less than a 30 min fire-resistance rating.

Text · e-Laws consolidated snapshot

9.10.21.3. — Floor Assemblies Between the First and Second Storey

(1) Except in a dwelling unit, a floor assembly in a building in a camp for housing of workers separating the first storey and the second storey shall be constructed as a fire separation having not less than a 30 min fire-resistance rating.

Text · e-Laws consolidated snapshot

9.10.21.4. — Walkways Connecting Buildings

(1) Walkways of combustible construction connecting buildings shall be separated from each connected building by a fire separation having not less than a 45 min fire-resistance rating.

Text · e-Laws consolidated snapshot

9.10.21.5. — Spatial Separations

(1) Buildings in a camp for housing of workers shall be separated from each other by a distance of not less than 10 m unless otherwise permitted in Subsection 9.10.14.

Text · e-Laws consolidated snapshot

9.10.21.6. — Flame Spread Ratings

(1) Except in dwelling units and except as provided in Sentence (2), the surface flame-spread rating of wall and ceiling surfaces in corridors and walkways, exclusive of doors, shall not exceed 25 over not less than 90 per cent of the exposed surface area and not more than 150 over the remaining surface area.

(2) Except within dwelling units, corridors that provide access to exit from sleeping rooms and having a fire-resistance rating of not less than 45 min shall have a flame-spread rating conforming to the appropriate requirements in Subsection 9.10.16.

Text · e-Laws consolidated snapshot

9.10.21.7. — Smoke Detectors

(1) Except in dwelling units, corridors providing access to exit from sleeping rooms in every building in a camp for housing of workers with sleeping accommodation for more than 10 persons shall have a smoke detector connected to the building alarm system.

Text · e-Laws consolidated snapshot

9.10.21.8. — Portable Fire Extinguishers

(1) Each building in a camp for housing of workers shall be provided with portable fire extinguishers in conformance with the provisions of the Fire Code made under the Fire Protection and Prevention Act, 1997.

Text · e-Laws consolidated snapshot

9.10.21.9. — Hose Stations

(1) Every building in a camp for housing of workers providing sleeping accommodation for more than 30 persons shall be provided with a hose station that is protected from freezing and equipped with a hose of sufficient length so that every portion of the building is within the range of a hose stream.

(2) Hose stations required in Sentence (1) shall be located near an exit.

(3) Hoses referred to in Sentence (1) shall be not less than 19 mm inside diam and shall be connected to a central water supply or to a storage tank having a capacity of at least 4 500 L with a pumping system capable of supplying a flow of at least 5 L/s at a gauge pressure of 300 kPa.

Text · e-Laws consolidated snapshot

9.10.22. — Fire Protection for Gas, Propane and Electric Ranges

Content not available for this version.

9.10.22.1. — Installation of Ranges

(1) Reserved.

(2) Clearances for and protection around gas, propane and electric ranges shall be not less than those provided in Articles 9.10.22.2. and 9.10.22.3.

Editor's note

As filed in O. Reg. 350/06, Sentence (1) of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed text is retained here.

9.10.22.2. — Vertical Clearances above Ranges

(1) Except as provided in Sentence (2), framing, finishes and cabinetry installed directly above the location of the range shall be not less than 750 mm above the level of range burners or elements.

(2) The vertical clearance described in Sentence (1) for framing, finishes and cabinets located directly above the location of the range is permitted to be reduced to 600 mm above the level of the elements or burners provided the framing, finishes and cabinets,

(a) are noncombustible, or

(b) are protected by,

(i) asbestos millboard not less than 6 mm thick, covered with sheet metal not less than 0.33 mm thick, or

(ii) a metal hood with a 125 mm projection beyond the framing, finishes and cabinets.

Text · e-Laws consolidated snapshot

9.10.22.3. — Protection Around Ranges

(1) Except as provided in Sentences (2) and (3), combustible wall framing, finishes or cabinets within 450 mm of the area where the range is to be located shall be protected above the level of the heating elements or burners by material providing fire resistance not less than that of a 9.5 mm thickness of gypsum board.

(2) Counter-top splash boards or back plates that extend above the level of the heating elements or burners need not be protected as described in Sentence (1).

(3) Except for cabinetry described in Article 9.10.22.2., cabinetry located not less than 450 mm above the level of the heating elements or burners need not be protected as described in Sentence (1).

Text · e-Laws consolidated snapshot

9.11. — Sound Control

Content not available for this version.

9.11.1. — Sound Transmission Class Rating (Airborne Sound)

Content not available for this version.

9.11.1.1. — Determination of Sound Transmission Class Rating

(1) Sound transmission class ratings shall be determined in accordance with ASTM E413, “Classification for Rating Sound Insulation”, using results from measurements in accordance with,

(a) ASTM E90, “Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”, or

(b) ASTM E336, “Measurement of Airborne Sound Insulation in Buildings”.

Text · e-Laws consolidated snapshot

9.11.2. — Required Sound Control Locations (Airborne Sound)

Content not available for this version.

9.11.2.1. — Minimum Sound Transmission Class Rating

(1) Except as provided in Sentence (2), every dwelling unit and every suite in hotels shall be separated from every other space in a building in which noise may be generated, by a construction providing a sound transmission class rating of at least 50, measured in accordance with Subsection 9.11.1. or as listed in Tables 1.1 and 1.2 of Supplementary Standard SB-3.

(2) Where a dwelling unit or suite in a hotel is adjacent to an elevator shaft or a refuse chute, the separating construction shall have a sound transmission class rating of at least 55, measured in accordance with Subsection 9.11.1. or as listed in Tables 1.1 and 1.2 of Supplementary Standard SB-3.

Text · e-Laws consolidated snapshot

9.11.2.2. — Building Services in an Assembly

(1) Building services located in an assembly required to have a sound transmission class rating shall be installed in a manner that will not decrease the required rating of the assembly.

Text · e-Laws consolidated snapshot

9.12. — Excavation

Content not available for this version.

9.12.1. — General

Content not available for this version.

9.12.1.1. — Removal of Topsoil and Organic Matter

(1) The topsoil and vegetable matter in all unexcavated areas under a building shall be removed.

(2) In localities where termite infestation is known to be a problem, all stumps, roots and other wood debris shall be removed from the soil to a depth of not less than 300 mm in unexcavated areas under a building.

(3) The bottom of every excavation shall be free of all organic material.

Text · e-Laws consolidated snapshot

9.12.1.2. — Standing Water

(1) Excavations shall be kept free of standing water.

Text · e-Laws consolidated snapshot

9.12.1.3. — Protection from Freezing

(1) The bottom of excavations shall be kept from freezing throughout the entire construction period.

Text · e-Laws consolidated snapshot

9.12.1.4. — Precautions During Excavation

(1) Every excavation shall be undertaken in such a manner to prevent damage to adjacent property, existing structures, utilities, roads and sidewalks at all stages of construction.

(2) Material shall not be placed nor shall equipment be operated or placed in or adjacent to an excavation in a manner that may endanger the integrity of the excavation or its supports.

Text · e-Laws consolidated snapshot

9.12.2. — Depth

Content not available for this version.

9.12.2.1. — Excavation to Undisturbed Soil

(1) Excavations for foundations shall extend to undisturbed soil.

Text · e-Laws consolidated snapshot

9.12.2.2. — Minimum Depth of Foundations

(1) Except as provided in Sentences (4) and (5), the minimum depth of foundations below finished ground level shall conform to Table 9.12.2.2.

(2) Where a foundation is insulated in a manner that will reduce the heat flow to the soil beneath the footings, the foundation depth shall conform to that required for foundations containing no heated space.

(3) The minimum depth of foundations for exterior concrete steps with more than 2 risers shall conform to Sentences (1), (2) and (5).

(4) Concrete steps with 1 and 2 risers are permitted to be laid on ground level.

(5) The foundation depths required in Sentence (1) are permitted to be decreased where experience with local soil conditions shows that lesser depths are satisfactory, or where the foundation is designed for lesser depths.

(6) The foundation depths required in Sentence (1) do not apply to foundations for,

(a) buildings,

(i) that are not of masonry or masonry veneer construction, and

(ii) whose superstructure conforms with the requirements of the deformation resistance test in CAN/CSA-Z240.2.1, “Structural Requirements for Mobile Homes”, or

(b) accessory buildings,

(i) that are not of masonry or masonry veneer construction.,

(ii) not more than 1 storey in building height,

(iii) not more than 55 m² in building area, and

(iv) where the distance from the finished ground to the underside of the floor joists is not more than 600 mm.

(7) The foundation depths required in Sentence (1) do not apply to foundations for decks and other accessible exterior platforms,

(a) that are of not more than 1 storey,

(b) that are not more than 55 m² in area,

(c) where the distance from the finished ground to the underside of the floor joists is not more than 600 mm,

(d) that are not supporting a roof, and

(e) that are not attached to another structure, unless it can be demonstrated that differential movement will not adversely affect the performance of that structure.

Editor's note

In the notes to Table-9.12.2.2., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Note As filed, the footnote markers in the notes of Table-9.12.2.2. are set with a following space (e.g. '(5) "N" is…'); the e-Laws consolidation renders them without it. The note text is otherwise identical between the two renderings.

Text · e-Laws consolidated snapshot

Table 9.12.2.2. Minimum Depths of Foundations Forming Part of Sentence 9.12.2.2.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Type of Soil

Minimum Depth of Foundation Containing Heated Basement or Crawl Space(1)

Minimum Depth of Foundation Containing no Heated Space(2)

Good Soil Drainage(3)

Poor Soil Drainage

Good Soil Drainage(3)

Poor Soil Drainage

Rock

No limit

No limit

No limit

No limit

Coarse grained soils

No limit

No limit

No limit

Below the depth of frost penetration

Silt

No limit

No limit

Below the depth of frost penetration

Below the depth of frost penetration

Clay or soils not clearly defined

1.2 m

1.2 m

1.2 m but not less than the depth of frost penetration

1.2 m but not less than the depth of frost penetration

Notes to Table 9.12.2.2.:

(1) Foundation not insulated to reduce heat loss through the footings.

(2) Including foundations containing heated space insulated to reduce heat loss through the footings.

(3) Good soil drainage to not less than the depth of frost penetration.

9.12.3. — Backfill

Content not available for this version.

9.12.3.1. — Placement of Backfill

(1) Backfill shall be placed to avoid damaging the foundation wall, the drainage tile, drainage layer, externally applied thermal insulation, waterproofing and dampproofing of the wall.

Text · e-Laws consolidated snapshot

9.12.3.2. — Grading of Backfill

(1) Backfill shall be graded to prevent drainage towards the foundation after settling.

Text · e-Laws consolidated snapshot

9.12.3.3. — Deleterious Debris and Boulders

(1) Backfill within 600 mm of the foundation shall be free of deleterious debris and boulders larger than 250 mm diam.

(2) Except as permitted in Sentence (3), backfill shall not contain pyritic material or material that is susceptible to ice lensing in concentrations that will damage the building to a degree that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

(3) Backfill with material of any concentration that is susceptible to ice lensing is permitted where foundation walls are cast-in-place concrete, concrete block insulated on the exterior or concrete block protected from the backfill by a material that serves as a slip plane.

Text · e-Laws consolidated snapshot

9.12.3.4. — Lateral Support of Foundation Wall

(1) Where the height of foundation wall is such that lateral support is required, or where the required concrete strength of the wall has not been reached, the wall shall be braced or laterally supported before backfilling.

Text · e-Laws consolidated snapshot

9.12.4. — Trenches Beneath Footings

Content not available for this version.

9.12.4.1. — Compacting or Filling With Concrete

(1) The soil in trenches beneath footings for sewers and watermains shall be compacted by tamping up to the level of the footing base, or shall be filled with concrete having a strength not less than 10 MPa to support the footing.

Text · e-Laws consolidated snapshot

9.13. — Dampproofing, Waterproofing and Soil Gas Control

Content not available for this version.

9.13.1. — General

Content not available for this version.

9.13.1.1. — Application

(1) This Section applies to the control of moisture and soil gas ingress through walls, floors, and roofs in contact with the ground.

Text · e-Laws consolidated snapshot

9.13.2. — Dampproofing

Content not available for this version.

9.13.2.1. — Dampproofing

(1) Except as provided in Article 9.13.3.1., where the exterior finished ground level is at a higher elevation than the ground level inside the foundation walls, exterior surfaces of foundation walls below ground level shall be dampproofed.

(2) Except as provided in Sentence (3) and Article 9.13.3.1., floors-on-ground shall be dampproofed.

(3) Floors in garages, floors in unenclosed portions of buildings and floors installed over granular fill in conformance with Article 9.16.2.1. need not be dampproofed.

(4) Dampproofing in Sentence (1) is not required where the exterior surfaces of foundation walls below ground level are waterproofed.

Text · e-Laws consolidated snapshot

9.13.2.2. — Material Standards

(1) Except as otherwise specified in this Section, materials used for exterior dampproofing shall conform to,

(a) CAN/CGSB-37.1-M, “Chemical Emulsified Type, Emulsified Asphalt for Dampproofing”,

(b) CAN/CGSB-37.2-M, “Emulsified Asphalt, Mineral Colloid Type, Unfilled, for Dampproofing and Waterproofing and for Roof Coatings”,

(c) CGSB 37-GP-6Ma, “Asphalt, Cutback, Unfilled, for Dampproofing”,

(d) CAN/CGSB-37.16-M, “Filled, Cutback Asphalt for Dampproofing and Waterproofing”,

(e) CGSB 37-GP-18Ma, “Tar, Cutback, Unfilled, for Dampproofing”,

(f) CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet, for Use in Building Construction”, or

(g) CAN/CSA-A123.4, “Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems.”

Text · e-Laws consolidated snapshot

9.13.2.3. — Standards for Application

(1) The method of application of all bituminous dampproofing materials shall conform to,

(a) CAN/CGSB 37.3-M, “Application of Emulsified Asphalts for Dampproofing or Waterproofing”,

(b) CGSB 37-GP-12Ma, “Application of Unfilled Cutback Asphalt for Dampproofing”, or

(c) CAN/CGSB-37.22-M, “Application of Unfilled, Cutback Tar Foundation Coating for Dampproofing”.

Text · e-Laws consolidated snapshot

9.13.2.4. — Preparation of Surface

(1) Unit masonry walls that are to be dampproofed shall be,

(a) parged on the exterior face below ground level with not less than 6 mm of mortar conforming to Section 9.20., and

(b) coved over the footing when the first course of block is laid.

(2) Concrete walls to be dampproofed shall have holes and recesses resulting from the removal of form ties sealed with cement mortar or dampproofing material.

(3) The surface of insulating concrete form walls that are to be dampproofed shall be repaired and free of projections and depressions that could lead to detrimental to the performance of the membrane to be applied.

Text · e-Laws consolidated snapshot

9.13.2.5. — Application of Dampproofing Material

(1) Dampproofing material shall be applied over the parging or concrete below ground level.

Text · e-Laws consolidated snapshot

9.13.2.6. — Interior Dampproofing of Walls

(1) Where a separate interior finish is applied to a concrete or unit masonry wall that is in contact with the soil, or where wood members are placed in contact with such walls for the installation of insulation or finish, the interior surface of the foundation wall below ground level shall be dampproofed.

(2) The dampproofing required in Sentence (1) shall extend from the basement floor and terminate at ground level.

(3) No membrane or coating with a permeance less than 170 ng/(Pa.s.m2) shall be applied to the interior surface of the foundation wall above ground level between the insulation and the foundation wall.

Text · e-Laws consolidated snapshot

9.13.2.7. — Dampproofing of Floors-on-Ground

(1) Where floors are dampproofed, the dampproofing shall be installed below the floor, except that where a separate floor is provided over a slab, the dampproofing is permitted to be applied to the top of the slab.

(2) Where installed below the floor, dampproofing membranes shall consist of polyethylene not less than 0.15 mm thick, or type S roll roofing.

(3) Joints in dampproofing membranes described in Sentence (2) shall be lapped not less than 100 mm.

(4) Where installed above the slab, dampproofing shall consist of,

(a) no fewer than 2 mopped-on coats of bitumen,

(b) not less than 0.05 mm polyethylene, or

(c) other material providing equivalent performance.

Text · e-Laws consolidated snapshot

9.13.2.8. — Dampproofing of Preserved Wood Foundation Walls

(1) Preserved wood foundation walls shall be dampproofed as described in CAN/CSA-S406, “Construction of Preserved Wood Foundations”.

Text · e-Laws consolidated snapshot

9.13.3. — Waterproofing

Content not available for this version.

9.13.3.1. — Required Waterproofing

(1) Where hydrostatic pressure occurs, waterproofing is required for exterior surfaces of,

(a) floors-on-ground, and

(b) below ground walls, where the exterior finished ground level is at a higher elevation than the ground level inside the foundation walls.

(2) Roofs of underground structures shall be waterproofed to prevent the entry of water into the structure.

Text · e-Laws consolidated snapshot

9.13.3.2. — Material Standards

(1) Except as otherwise specified in this Section, materials used for exterior waterproofing shall conform to,

(a) CAN/CGSB-37.2-M, “Emulsified Asphalt, Mineral-Colloid Type, Unfilled, for Dampproofing and Waterproofing and for Roof Coatings”,

(b) CAN/CGSB-37.16-M, “Filled, Cutback Asphalt for Dampproofing and Waterproofing”, or

(c) CAN/CSA-A123.4, “Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems”.

Text · e-Laws consolidated snapshot

9.13.3.3. — Standards for Application

(1) The method of application of all bituminous waterproofing materials shall conform to CAN/CGSB-37.3-M, “Application of Emulsified Asphalts for Dampproofing or Waterproofing”.

Text · e-Laws consolidated snapshot

9.13.3.4. — Preparation of Surface

(1) Unit masonry walls that are to be waterproofed shall be parged on exterior surfaces below ground level with not less than 6 mm of mortar conforming to Section 9.20.

(2) Concrete walls that are to be waterproofed shall have all holes and recesses resulting from removal of form ties sealed with mortar or waterproofing material.

(3) The surface of insulating concrete form walls that are to be waterproofed shall be repaired and free of projections and depressions that could be detrimental to the performance of the membrane to be applied.

Text · e-Laws consolidated snapshot

9.13.3.5. — Application of Waterproofing Membranes

(1) Concrete or unit masonry walls to be waterproofed shall be covered with no fewer than 2 layers of bitumen-saturated membrane, with each layer cemented in place with bitumen and coated overall with a heavy coating of bitumen.

Text · e-Laws consolidated snapshot

9.13.3.6. — Floor Waterproofing System

(1) Basement floors-on-ground to be waterproofed shall have a system of membrane waterproofing provided between 2 layers of concrete, each of which shall be not less than 75 mm thick, with the floor membrane mopped to the wall membrane to form a complete seal.

Text · e-Laws consolidated snapshot

9.13.4. — Soil Gas Control

Content not available for this version.

9.13.4.1. — Soil Gas Control

(1) Where methane or radon gases are known to be a problem, construction shall comply with the requirements for soil gas control in Supplementary Standard SB-9.

Text · e-Laws consolidated snapshot

9.13.4.2. — Required Soil Gas Control

(1) Except as provided in Sentence (2), all wall, roof and floor assemblies in contact with the ground shall be constructed to resist the leakage of soil gas from the ground into the building.

(2) Construction to resist leakage of soil gas into the building is not required for,

(a) garages and unenclosed portions of buildings,

(b) buildings constructed in areas where it can be demonstrated that soil gas does not constitute a hazard, or

(c) buildings that contain a single dwelling unit and are constructed to provide for subfloor depressurization in accordance with Supplementary Standard SB-9.

(3) Where soil gas control is required, a soil gas barrier shall be installed at walls and roofs in contact with the ground according to Supplementary Standard SB-9.

(4) Where soil gas control is required, it shall consist of one of the following at floors in contact with the ground:

(a) a soil gas barrier installed according to Supplementary Standard SB-9 , or

(b) where the building contains a single dwelling unit only, a subfloor depressurization system installed according to Supplementary Standard SB-9.

Text · e-Laws consolidated snapshot

9.13.4.3. — Material Standards

(1) Materials used to provide a barrier to soil gas ingress through floors-on-ground shall conform to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet, for Use in Building Construction”.

Text · e-Laws consolidated snapshot

9.14. — Drainage

Content not available for this version.

9.14.1. — Scope

Content not available for this version.

9.14.1.1. — Application

(1) This Section applies to subsurface drainage and to surface drainage.

Text · e-Laws consolidated snapshot

9.14.1.2. — Crawl Spaces

(1) Drainage for crawl spaces shall conform to Section 9.18.

Text · e-Laws consolidated snapshot

9.14.1.3. — Floors-on-Ground

(1) Drainage requirements beneath floors-on-ground shall conform to Section 9.16.

Text · e-Laws consolidated snapshot

9.14.2. — Foundation Drainage

Content not available for this version.

9.14.2.1. — Foundation Wall Drainage

(1) Unless it can be shown to be unnecessary, drainage shall be provided at the bottom of every foundation wall that contains the building interior.

(2) Except as permitted in Sentences (4) to (6), where the insulation on a foundation wall extends to more than 900 mm below the adjacent exterior ground level,

(a) a drainage layer shall be installed adjacent to the exterior surface of a foundation wall consisting of,

(i) not less than 19 mm mineral fibre insulation with a density of not less than 57 kg/m3, or

(ii) not less than 100 mm of free draining granular material, or

(b) a system shall be installed that can be shown to provide equivalent performance to that provided by the materials described in Clause (a).

(3) Where mineral fibre insulation, crushed rock backfill or other drainage layer medium is provided adjacent to the exterior surface of a foundation wall,

(a) the insulation, backfill or other drainage layer medium shall extend to the footing level to facilitate drainage of ground water to the foundation drainage system, and

(b) any pyritic material in the crushed rock shall be limited to a concentration that will not damage the building to a degree that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

(4) Except when the insulation provides the drainage layer required in Clause (2)(a), when exterior insulation is provided, the drainage layer shall be installed on the exterior face of the insulation.

(5) The drainage layer required in Sentence (2) is not required,

(a) when the foundation wall is not required to be dampproofed, or

(b) when the foundation wall is waterproofed.

(6) The drainage layer in Sentence (2) is only required where the foundation wall is constructed after the day this Regulation comes into force.

(7) Where drainage is required in Sentence (1), the drainage shall conform to Subsection 9.14.3. or 9.14.4.

Text · e-Laws consolidated snapshot

9.14.3. — Drainage Tile and Pipe

Content not available for this version.

9.14.3.1. — Material Standards

(1) Drain tile and drain pipe for foundation drainage shall conform to,

(a) ASTM C4, “Clay Drain Tile and Perforated Clay Drain Tile”,

(b) ASTM C412M, “Concrete Drain Tile (Metric)”,

(c) ASTM C444M, “Perforated Concrete Pipe (Metric)”,

(d) ASTM C700, “Vitrified Clay Pipe, Extra Strength, Standard Strength and Perforated”,

(e) CAN/CGSB-34.22, “Asbestos-Cement Drain Pipe”,

(f) CAN/CSA-B182.1, “Plastic Drain and Sewer Pipe and Pipe Fittings”,

(g) CSA G401, “Corrugated Steel Pipe Products”, or

(h) NQ 3624-115, “Polythylene (PE) Pipe and Fittings – Flexible Corrugated Pipes for Drainage – Characteristics and Test Methods”.

Text · e-Laws consolidated snapshot

9.14.3.2. — Minimum Size

(1) Drain tile or pipe used for foundation drainage shall be not less than 100 mm in diam.

Text · e-Laws consolidated snapshot

9.14.3.3. — Installation

(1) Drain tile or pipe shall be laid on undisturbed or well-compacted soil so that the top of the tile or pipe is below the bottom of the floor slab or crawl space.

(2) Drain tile or pipe with butt joints shall be laid with 6 mm to 10 mm open joints.

(3) The top half of joints referred to in Sentence (2) shall be covered with sheathing paper, 0.10 mm polyethylene or No.15 asphalt or tar-saturated felt.

(4) The top and sides of drain pipe or tile shall be covered with not less than 150 mm of crushed stone or other coarse clean granular material containing not more than 10% of material that will pass a 4 mm sieve.

Text · e-Laws consolidated snapshot

9.14.4. — Granular Drainage Layer

Content not available for this version.

9.14.4.1. — Type of Granular Material

(1) Granular material used to drain the bottom of a foundation shall consist of a continuous layer of crushed stone or other coarse clean granular material containing,

(a) not more than 10% of material that will pass a 4 mm sieve, and

(b) no pyritic material in a concentration that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

Text · e-Laws consolidated snapshot

9.14.4.2. — Installation

(1) Granular material described in Article 9.14.4.1. shall be laid on undisturbed or compacted soil to a minimum depth of not less than 125 mm beneath the building and extend not less than 300 mm beyond the outside edge of the footings.

Text · e-Laws consolidated snapshot

9.14.4.3. — Grading

(1) The bottom of an excavation drained by a granular layer shall be graded so that the entire area described in Article 9.14.4.2. is drained to a sump conforming to Article 9.14.5.2.

Text · e-Laws consolidated snapshot

9.14.4.4. — Wet Site Conditions

(1) Where because of wet site conditions soil becomes mixed with the granular drainage material, sufficient additional granular material shall be provided so that the top 125 mm is kept free of soil.

Text · e-Laws consolidated snapshot

9.14.5. — Drainage Disposal

Content not available for this version.

9.14.5.1. — Drainage Disposal

(1) Foundation drains shall drain to a sewer, drainage ditch or dry well.

Text · e-Laws consolidated snapshot

9.14.5.2. — Sump Pits

(1) Where gravity drainage is not practical, a covered sump with an automatic pump shall be installed to discharge the water into a sewer, drainage ditch or dry well.

(2) Covers for sump pits shall be designed to resist removal by children.

Text · e-Laws consolidated snapshot

9.14.5.3. — Dry Wells

(1) Dry wells are permitted to be used only when located in areas where the natural groundwater level is below the bottom of the dry well.

(2) Dry wells shall be not less than 5 m from the building foundation and located so that drainage is away from the building.

Text · e-Laws consolidated snapshot

9.14.6. — Surface Drainage

Content not available for this version.

9.14.6.1. — Surface Drainage

(1) The building shall be located or the building site graded so that water will not accumulate at or near the building and will not adversely affect adjacent properties.

Text · e-Laws consolidated snapshot

9.14.6.2. — Drainage away from Wells or Septic Disposal Beds

(1) Surface drainage shall be directed away from the location of a water supply well or septic tank disposal bed.

Text · e-Laws consolidated snapshot

9.14.6.3. — Window Wells

(1) Every window well shall be drained to the footing level or other suitable location.

Text · e-Laws consolidated snapshot

9.14.6.4. — Catch Basin

(1) Where runoff water from a driveway is likely to accumulate or enter a garage, a catch basin shall be installed to provide adequate drainage.

Text · e-Laws consolidated snapshot

9.14.6.5. — Downspouts

(1) Downspouts shall conform to Article 9.26.18.2.

Text · e-Laws consolidated snapshot

9.15. — Footings and Foundations

Content not available for this version.

9.15.1. — Application

Content not available for this version.

9.15.1.1. — General

(1) Except as provided in Articles 9.15.1.2. and 9.15.1.3., this Section applies to,

(a) concrete or unit masonry foundation walls and concrete footings not subject to surcharge,

(i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and

(ii) for buildings of wood frame or masonry construction,

(b) wood frame foundation walls and wood or concrete footings not subject to surcharge,

(i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and

(ii) for buildings of wood frame construction, and

(c) flat insulating concrete form foundation walls and concrete footings not subject to surcharge,

(i) on stable soils with an allowable bearing pressure of 100 kPa or greater, and

(ii) for buildings of light frame or flat insulated concrete form construction that are not more than 2 storeys in building height, with a maximum floor to floor height of 3 m, and containing only a single dwelling unit.

(2) Foundations for applications other than as described in Sentence (1) shall be designed in accordance with Section 9.4.

(3) Where a foundation is erected on filled ground, peat or sensitive clay, the footing sizes shall be designed in conformance with Section 4.2.

(4) For the purpose of Sentence (3), sensitive clay means the grain size of the majority of the particles is smaller than 0.002 mm, including leda clay.

Text · e-Laws consolidated snapshot

9.15.1.2. — Permafrost

(1) Buildings erected on permafrost shall have foundations designed by a designer competent in this field in accordance with the appropriate requirements of Part 4.

Text · e-Laws consolidated snapshot

9.15.1.3. — Foundations for Deformation Resistant Buildings

(1) Where the superstructure of a detached building conforms to the requirements of the deformation resistance test in CAN/CSA-Z240.2.1, “Structural Requirements for Mobile Homes”, the foundation shall be constructed in conformance with,

(a) the remainder of this Section, or

(b) CSA Z240.10.1, “Site Preparation, Foundation, and Anchorage of Mobile Homes”.

Text · e-Laws consolidated snapshot

9.15.2. — General

Content not available for this version.

9.15.2.1. — Concrete

(1) Concrete shall conform to Section 9.3.

Text · e-Laws consolidated snapshot

9.15.2.2. — Unit Masonry Construction

(1) Concrete block shall conform to CSA A165.1, “Concrete Block Masonry Units”, and shall have a compressive strength over the average net cross-sectional area of the block of not less than 15 MPa.

(2) Mortar, grout, mortar joints, corbelling and protection for unit masonry shall conform to Section 9.20.

(3) For concrete block foundation walls required to be reinforced,

(a) mortar shall be Type S, conforming to CSA A179, “Mortar and Grout for Unit Masonry”,

(b) grout shall be coarse, conforming to CSA A179, “Mortar and Grout for Unit Masonry”, and

(c) placement of grout shall conform to CSA A371, “Masonry Construction for Buildings”.

Text · e-Laws consolidated snapshot

9.15.2.3. — Pier Type Foundations

(1) Where pier type foundations are used, the piers shall be designed to support the applied loads from the superstructure.

(2) Where piers are used as a foundation system in a building of 1 storey in building height, the piers shall be installed to support the principal framing members and shall be spaced not more than 3.5 m apart along the framing, unless the piers and their footings are designed for larger spacings.

(3) The height of piers described in Sentence (2) shall not exceed 3 times their least dimension at the base of the pier.

(4) Where concrete block is used for piers described in Sentence (2), they shall be laid with cores placed vertically, and where the width of the building is 4.3 m or less, placed with their longest dimension at right angles to the longest dimension of the building.

Text · e-Laws consolidated snapshot

9.15.2.4. — Wood Frame Foundations

(1) Foundations of wood frame construction shall conform to,

(a) CAN/CSA-S406, “Construction of Preserved Wood Foundations”, or

(b) Part 4.

Text · e-Laws consolidated snapshot

9.15.3. — Footings

Content not available for this version.

9.15.3.1. — Footings Required

(1) Footings shall be provided under walls, pilasters, columns, piers, fireplaces and chimneys that bear on soil or rock, except that footings are permitted to be omitted under piers or monolithic concrete walls if the safe loadbearing capacity of the soil or rock is not exceeded.

Text · e-Laws consolidated snapshot

9.15.3.2. — Support of Footings

(1) Footings shall rest on undisturbed soil, rock or compacted granular fill.

(2) Granular fill shall not contain pyritic material in a concentration that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

Text · e-Laws consolidated snapshot

9.15.3.3. — Application of Footing Width and Area Requirements

(1) Except as provided in Sentence 9.15.3.4.(2), the minimum footing width or area requirements provided in Articles 9.15.3.4. to 9.15.3.7. shall apply to footings where,

(a) the footings support,

(i) foundation walls of masonry, concrete, or flat insulating form foundation walls,

(ii) above ground walls of masonry, flat insulating form foundation walls or light wood frame construction, and

(iii) floors and roofs of light wood frame construction,

(b) the span of supported joists does not exceed 4.9 m, and

(c) the specified live load on any floor supported by the footing does not exceed 2.4 kPa.

(2) Except as provided in Sentence 9.15.3.4.(2), where the span of the supported joists exceeds 4.9 m, footings shall be designed in accordance with Section 4.2.

(3) Where the specified live load exceeds 2.4 kPa footings shall be designed in accordance with Section 4.2.

Text · e-Laws consolidated snapshot

9.15.3.4. — Basic Footing Widths and Areas

(1) Except as provided in Sentences (2) and (3) and in Articles 9.15.3.5. to 9.15.3.7., the minimum footing width or area shall comply with Table 9.15.3.4.

(2) Where the supported joist span exceeds 4.9 m in buildings with light wood-framed walls, floors and roofs, footing widths shall be determined according to,

(a) Section 4.2., or

(b) the following formula:

W = w • [∑ sjs / (storeys • 4.9)]

where,

W = minimum footing width,

w = minimum width of footings supporting joists not exceeding 4.9 m, as defined by Table 9.15.3.4.,

∑ sjs = the sum of the supported joist lengths on each storey whose load is transferred to the footing, and

storeys = number of storeys supported by the footing

(3) Where a foundation rests on gravel, sand or silt in which the water table level is less than the width of the footings below the bearing surface,

(a) the footing width for walls shall be not less than twice the width required by Sentences (1) and (2), and Articles 9.15.3.5. and 9.15.3.6., and

(b) the footing area for columns shall be not less than twice the area required by Sentences (1) and (2), and Article 9.15.3.7.

Editor's note

In the notes to Table-9.15.3.4., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.15.3.4. Minimum Footing Sizes Forming Part of Sentence 9.15.3.4.(1)

Column 1

Column 2

Column 3

Column 4

Number of Floors Supported

Minimum Width of Strip Footings, mm

Minimum Footing Area for Columns Spaced 3 m o.c.(1), m2

Supporting Exterior Walls(2)

Supporting Interior Walls(3)

1

250

200

0.40

2

350

350

0.75

3

450

500

1.0

Notes to Table 9.15.3.4.:

(1)See Sentence 9.15.3.7.(1).

(2)See Sentences 9.15.3.5.(1).

(3)See Sentence 9.15.3.6.(1).

9.15.3.5. — Adjustments to Footing Widths for Exterior Walls

(1) The strip footing widths for exterior walls shown in Table 9.15.3.4.v1 shall be increased by,

(a) 65 mm for each storey of masonry veneer over wood frame construction supported by the foundation wall,

(b) 130 mm for each storey of masonry construction supported by the foundation wall, and

(c) 150 mm for each storey of flat insulating concrete form wall construction supported by the foundation wall.

Text · e-Laws consolidated snapshot

9.15.3.6. — Adjustments to Footing Widths for Interior Walls

(1) The minimum strip footing widths for interior loadbearing masonry walls shown in Table 9.15.3.4.v1 shall be increased by 100 mm for each storey of masonry construction supported by the footing.

(2) Footings for interior non-loadbearing masonry walls shall be not less than 200 mm wide for walls up to 5.5 m high and the width shall be increased by 100 mm for each additional 2.7 m of height.

Text · e-Laws consolidated snapshot

9.15.3.7. — Adjustments to Footing Area for Columns

(1) The footing area for column spacings other than shown in Table 9.15.3.4.v1 shall be adjusted in proportion to the distance between columns.

Text · e-Laws consolidated snapshot

9.15.3.8. — Footing Thickness

(1) Footing thickness shall be not less than the greater of,

(a) 100 mm, or

(b) the width of the projection of the footing beyond the supported element.

Text · e-Laws consolidated snapshot

9.15.3.9. — Step Footings

(1) Where step footings are used,

(a) the vertical rise between horizontal portions shall not exceed 600 mm, and

(b) the horizontal distance between risers shall be not less than 600 mm.

Text · e-Laws consolidated snapshot

9.15.4. — Foundation Walls

Content not available for this version.

9.15.4.1. — Permanent Form Material

(1) Insulating concrete form units shall be manufactured of polystyrene conforming to the performance requirements of CAN/ULC-S701, “Thermal Insulation, Polystyrene, Boards and Pipe Covering”, for Type 2, 3 or 4 polystyrene.

Text · e-Laws consolidated snapshot

9.15.4.2. — Foundation Wall Thickness and Required Lateral Support

(1) Except as required in Sentence (2), the thickness of foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A. for walls not exceeding 2.5 m in unsupported height.

(2) The thickness of concrete in flat insulating concrete form foundation walls shall be not less than the greater of,

(a) 140 mm, or

(b) the thickness of the concrete in the wall above.

(3) Foundation walls made of flat insulating concrete form units shall be laterally supported at the top and at the bottom.

(4) Where average stable soils are encountered and wind loads on the exposed portion of the foundation are no greater than 0.70 kPa, the thickness and reinforcing of foundation walls made of reinforced concrete block and subject to lateral earth pressure shall conform to Table 9.15.4.2.B. and Sentences (5) to (10).

(5) For concrete block walls required to be reinforced, continuous vertical reinforcement shall,

(a) be provided at wall corners, wall ends, wall intersections, at changes in wall height, at the jambs of all openings and at movement joints,

(b) extend from the top of the footing to the top of the foundation wall,

(c) where foundation walls are laterally unsupported at the top, have not less than 600 mm embedment into the footing, and

(d) where foundation walls are laterally supported at the top, have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.

(6) Where foundation walls are laterally unsupported, the footing shall be designed according to Part 4 to resist overturning and sliding, if the maximum height of finished ground above the basement floor or crawl space ground cover exceeds 1.50 m.

(7) At the base of concrete block walls required to be reinforced and where the height of finished ground above the basement floor or crawl space ground cover exceeds 2.0 m, not less than one 15M intermediate vertical bar reinforcement shall be installed midway between adjacent continuous vertical reinforcement, and shall,

(a) extend to not less than 600 mm above the top of the footing, and

(b) have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.

(8) For concrete block walls required to be reinforced, a continuous horizontal bond beam containing at least one 15M bar shall be installed,

(a) along the top of the wall,

(b) at the sill and head of all openings greater than 1.20 m in width, and

(c) at structurally connected floors.

(9) In concrete block walls required to be reinforced, all vertical bar reinforcement shall be installed along the centre line of the wall.

(10) In concrete block walls required to be reinforced, ladder or truss type lateral reinforcement not less than 3.8 mm (No. 9 ASWG) shall be installed in the bed joint of every second masonry course.

Editor's note

As filed in O. Reg. 350/06, Table 9.15.4.2.B. heads its second column 'Colun 2' — an apparent typographical error for 'Column 2' — italicizes the headings of Columns 3 to 6, leaves the heading of the table's notes unbolded, and numbers the notes '(1)', '(2)' and '(3)'. The current e-Laws consolidation corrects the spelling to 'Column 2', removes the italics, bolds the notes heading, and renders the note numbers as superscripts, with no amending regulation making any of these changes. This map preserves the table as filed.

Text · e-Laws consolidated snapshot

Table 9.15.4.2.A. Thickness of Solid Concrete and Unreinforced Concrete Block Foundation Walls Forming Part of Sentence 9.15.4.2.(1)

Column 1

Column 2

Column 3

Column 4

Type of Foundation Wall

Minimum Wall Thickness, Mm

Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m

Foundation Wall Laterally Unsupported at the Top(1)

Foundation Wall Laterally Supported at the Top(1)

Solid concrete, 15 Mpa min. strength

150

0.8

1.5

200

1.2

2.15

250

1.4

2.3

300

1.5

2.3

Solid concrete, 20 Mpa min. strength

150

0.8

1.8

200

1.2

2.3

250

1.4

2.3

300

1.5

2.3

Unreinforced Concrete Block

140

0.6

0.8

190

0.9

1.2

240

1.2

1.8

290

1.4

2.2

Note to Table 9.15.4.2.A.:

(1)See Article 9.15.4.3.

Table 9.15.4.2.B. Reinforced Concrete Block Foundation Walls Forming Part of Sentence 9.15.4.2.(4)

Column 1

Colun 2

Column 3

Column 4

Column 5

Column 6

Minimum Wall Thickness, mm

Maximum Height of Finished Ground above Basement Floor or Crawl Space Ground Cover, m

Foundation Wall Laterally Unsupported at Top (1)

Foundation Wall Laterally Supported at Top (1)

Continuous Vertical Reinforcement

Continuous Vertical Reinforcement

Minimum Bar Size

Maximum Bar Spacing, m

Minimum Bar Size

Maximum Bar Spacing, m

190

1.0

25M

1.2

(2)

(2)

1.2

25M

1.2

(2)

(2)

1.4

25M

1.2

15M

1.2

1.6

25M

0.8

15M

1.2

1.8

25M

0.6

20M

1.2

2.0

25M

0.4

20M

1.2

2.2

(3)

(3)

25M

1.2

2.4

(3)

(3)

25M

1.2

240

1.4

25M

1.0

(2)

(2)

1.6

25M

1.0

(2)

(2)

1.8

25M

0.8

(2)

(2)

2.0

25M

0.8

20M

1.8

2.2

25M

0.8

25M

1.8

2.4

25M

0.6

25M

1.8

Notes to Table 9.15.4.2.B.:

(1)See Article 9.15.4.3.

(2)No reinforcement required.

(3)Design to Part 4.

9.15.4.3. — Foundation Walls Considered to be Laterally Supported at the Top

(1) Sentences (2) to (4) apply to lateral support for walls described in Sentence 9.15.4.2.(1)v1.

(2) Foundation walls shall be considered to be laterally supported at the top if,

(a) such walls support solid masonry superstructure,

(b) the floor joists are embedded in the top of the foundation walls, or

(c) the floor system is anchored to the top of the foundation walls with anchor bolts, in which case the joists may run either parallel or perpendicular to the foundation walls.

(3) Unless the wall around an opening is reinforced to withstand earth pressure, the portion of the foundation wall beneath an opening shall be considered laterally unsupported, if,

(a) the opening is more than 1.2 m wide, or

(b) the total width of the openings in the foundation wall constitutes more than 25% of the length of the wall.

(4) For the purposes of Sentence (3), the combined width of the openings shall be considered as a single opening if the average width is greater than the width of solid wall between them.

(5) Flat insulating concrete form foundation walls shall be considered to be laterally supported at the top if the floor joists are installed according to Article 9.20.17.5.v1

Text · e-Laws consolidated snapshot

9.15.4.4. — Foundation Walls Considered to be Laterally Supported at the Bottom

(1) Flat insulating concrete form foundation walls shall be considered to be laterally supported at the bottom where the foundation wall,

(a) supports backfill not more than 1.2 m in height,

(b) is supported at the footing by a shear key and is supported at the top by the ground floor framing, or

(c) is dowelled to the footing with not less than 15M bars spaced not more than 1.2 m o.c.

Text · e-Laws consolidated snapshot

9.15.4.5. — Reinforcement for Flat Insulating Concrete Form Foundation Walls

(1) Horizontal reinforcement in flat insulating concrete form foundation walls shall,

(a) consist of,

(i) one 10M bar placed not more than 300 mm from the top of the wall, and

(ii) 10M bars spaced not more than 600 mm o.c., and

(b) be located,

(i) in the inside half of the wall section, and

(ii) with a minimum cover of 30 mm from the inside face of the concrete.

(2) Vertical wall reinforcement in flat insulating concrete form foundation walls shall,

(a) conform to,

(i) Table 9.15.4.5.A. for 140 mm walls,

(ii) Table 9.15.4.5.B. for 190 mm walls, and

(iii) Table 9.15.4.5.C. for 240 mm walls,

(b) be located in the inside half of the wall section with a minimum cover of 30 mm from the inside face of the concrete wall, and

(c) where interrupted by wall openings, be placed not more than 600 mm from each side of the openings.

(3) Cold joints in flat insulating concrete form foundation walls shall be reinforced with at least one 15M bar spaced not more than 600 mm o.c. and embedded not less than 300 mm on both sides of the joint.

(4) Reinforcing around openings in flat insulating concrete form foundation walls shall comply with Articles 9.20.17.3.v1v2 or 9.20.17.4.

Text · e-Laws consolidated snapshot

Table 9.15.4.5.A. Vertical Reinforcement for 140 mm Flat Insulating Concrete Form Foundation Walls Forming Part of Sentence 9.15.4.5.(2)

Column 1

Column 2

Column 3

Column 4

Maximum Height of Finished Ground Above Finished Basement Floor, m

Maximum Vertical Reinforcement

Maximum Unsupported Basement Wall Height

2.44 m

2.75 m

3.00 m

1.35

10M at 400 mm o.c.

10M at 400 mm o.c.

10M at 400 mm o.c.

1.60

10M at 400 mm o.c.

10M at 380 mm o.c.

10M at 380 mm o.c.

2.00

10M at 380 mm o.c.

10M at 380 mm o.c.

10M at 380 mm o.c.

2.20

10M at 250 mm o.c.

10M at 250 mm o.c.

10M at 250 mm o.c.

2.35

n/a

10M at 250 mm o.c.

10M at 250 mm o.c.

2.60

n/a

10M at 250 mm o.c.

10M at 250 mm o.c.

3.00

n/a

n/a

15M at 250 mm o.c.

Table 9.15.4.5.B. Vertical Reinforcement for 190 mm Flat Insulating Concrete Form Foundation Walls Forming Part of Sentence 9.15.4.5.(2)

Column 1

Column 2

Column 3

Column 4

Maximum Height of Finished Ground Above Finished Basement Floor, m

Maximum Vertical Reinforcement

Maximum Unsupported Basement Wall Height

2.44 m

2.75 m

3.00 m

2.20

none required

10M at 400 mm o.c.

10M at 400 mm o.c.

2.35

n/a

10M at 300 mm o.c.

10M at 300 mm o.c.

2.60

n/a

10M at 300 mm o.c.

15M at 400 mm o.c.

3.00

n/a

n/a

15M at 400 mm o.c.

Table 9.15.4.5.C. Vertical Reinforcement for 240 mm Flat Insulating Concrete Form Foundation Walls Forming Part of Sentence 9.15.4.5.(2)

Column 1

Column 2

Column 3

Column 4

Maximum Height of Finished Ground Above Finished Basement Floor, m

Maximum Vertical Reinforcement

Maximum Unsupported Basement Wall Height

2.44 m

2.75 m

3.00 m

2.20

none required

none required

none required

2.60

n/a

15M at 400 mm o.c.

15M at 400 mm o.c.

3.00

n/a

n/a

15M at 400 mm o.c.

9.15.4.6. — Extension above Ground Level

(1) Exterior foundation walls shall extend not less than 150 mm above finished ground level.

Text · e-Laws consolidated snapshot

9.15.4.7. — Reduction in Thickness

(1) Where the top of a foundation wall is reduced in thickness to permit the installation of floor joists, the reduced section shall be not more than 350 mm high and not less than 90 mm thick.

(2) Where the top of a foundation wall is reduced in thickness to permit the installation of a masonry exterior facing, the reduced section shall be,

(a) not less than 90 mm thick, and

(b) tied to the facing material with metal ties conforming to Sentence 9.20.9.4.(3) spaced not more than,

(i) 200 mm o.c. vertically, and

(ii) 900 mm o.c. horizontally.

(3) The space between wall and facing described in Sentence (2) shall be filled with mortar.

Text · e-Laws consolidated snapshot

9.15.4.8. — Corbelling

(1) Corbelling of masonry foundation walls supporting cavity walls shall conform to Article 9.20.12.2.

Text · e-Laws consolidated snapshot

9.15.4.9. — Crack Control Joints

(1) Crack control joints shall be provided in foundation walls more than 25 m long at intervals of not more than 15 m.

(2) Joints required in Sentence (1) shall be designed to resist moisture penetration and shall be keyed to prevent relative displacement of the wall portions adjacent to the joint.

Text · e-Laws consolidated snapshot

9.15.4.10. — Interior Masonry Walls

(1) Interior masonry foundation walls not subject to lateral earth pressure shall conform to Section 9.20.

Text · e-Laws consolidated snapshot

9.15.5. — Support of Joists and Beams on Masonry Foundation Walls

Content not available for this version.

9.15.5.1. — Support of Floor Joists

(1) Except as permitted in Sentence (2), foundation walls of hollow unit masonry supporting floor joists shall be,

(a) capped with not less than 50 mm of solid masonry or concrete, or

(b) have the top course filled with mortar or concrete.

(2) Capping required in Sentence (1) is permitted to be omitted,

(a) in localities where termites are not known to occur,

(b) when the joists are supported on a wood plate not less than 38 mm by 89 mm, and

(c) when the siding overlaps the foundation wall not less than 12 mm.

Text · e-Laws consolidated snapshot

9.15.5.2. — Support of Beams

(1) Not less than a 190 mm depth of solid masonry shall be provided beneath beams supported on masonry.

(2) Where the beam referred to in Sentence (1) is supported below the top of the foundation walls, the ends of such beams shall be protected from the weather.

Text · e-Laws consolidated snapshot

9.15.5.3. — Pilasters

(1) Pilasters shall be provided under beams that frame into unit masonry foundation walls 140 mm or less in thickness.

(2) Pilasters required in Sentence (1) shall be not less than 90 mm by 290 mm and shall be bonded or tied into the wall.

(3) The top 200 mm of pilasters required in Sentence (1) shall be solid.

Text · e-Laws consolidated snapshot

9.15.6. — Parging and Finishing of Foundation Walls

Content not available for this version.

9.15.6.1. — Foundation Walls Below Ground

(1) Concrete block foundation walls shall be parged on the exterior face below ground level as required in Section 9.13.

Text · e-Laws consolidated snapshot

9.15.6.2. — Foundation Walls Above Ground

(1) Exterior surfaces of concrete block foundation walls above ground level shall have tooled joints, or shall be rendered, parged or otherwise suitably finished.

Text · e-Laws consolidated snapshot

9.15.6.3. — Form Ties

(1) All form ties shall be removed at least flush with the concrete surface.

Text · e-Laws consolidated snapshot

9.16. — Floors-on-Ground

Content not available for this version.

9.16.1. — Scope

Content not available for this version.

9.16.1.1. — Application

(1) This Section applies to floors that are supported on ground or granular fill and that do not provide structural support for the superstructure.

Text · e-Laws consolidated snapshot

9.16.1.2. — Structural Floor Slabs

(1) Floors-on-ground that support loads from the superstructure shall be designed in conformance with Part 4.

Text · e-Laws consolidated snapshot

9.16.1.3. — Required Floors-on-Ground

(1) All spaces within dwelling units, except crawl spaces, shall be provided with a floor-on-ground, where,

(a) access is provided to the space, and

(b) a floor supported by the structure is not provided.

Text · e-Laws consolidated snapshot

9.16.1.4. — Dampproofing and Waterproofing

(1) Dampproofing and waterproofing shall conform to Section 9.13.

Text · e-Laws consolidated snapshot

9.16.2. — Material Beneath Floors

Content not available for this version.

9.16.2.1. — Required Installation of Granular Fill

(1) Except as provided in Sentence (2), not less than 100 mm of coarse clean granular material containing not more than 10% of material that will pass a 4 mm sieve shall be placed beneath floors-on-ground.

(2) Granular material need not be installed under,

(a) slabs in garages, carports or accessory buildings, or

(b) buildings of industrial occupancy where the nature of the process contained in the occupancy permits or requires the use of large openings in the building envelope even during the winter.

Text · e-Laws consolidated snapshot

9.16.2.2. — Support of Floors

(1) Material that is susceptible to changes in volume due to variations in moisture content or chemical-microbiological oxidation shall not be used as fill beneath floors-on-ground in a concentration that will damage the building to a degree that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

(2) Material that is susceptible to changes in volume due to freezing shall not be used as fill beneath floors-on-ground that will be subjected to freezing temperatures.

(3) Except as provided in Sentence (4), fill beneath floors-on-ground shall be compacted.

(4) Fill beneath floors-on-ground need not be compacted where the material is clean coarse aggregate containing not more than 10% of material that will pass a 4 mm sieve.

Text · e-Laws consolidated snapshot

9.16.3. — Drainage

Content not available for this version.

9.16.3.1. — Control of Water Ingress

(1) Except as provided in Article 9.16.3.2. or where it can be shown to be unnecessary, ingress of water underneath a floor-on-ground shall be prevented by grading or drainage.

Text · e-Laws consolidated snapshot

9.16.3.2. — Hydrostatic Pressure

(1) Where groundwater levels may cause hydrostatic pressure beneath a floor-on-ground, the floor-on-ground shall be,

(a) a cast-in-place concrete slab, and

(b) designed to resist such pressures.

Text · e-Laws consolidated snapshot

9.16.3.3. — Floor Drains

(1) When floor drains are required, the floor surface shall be sloped so that no water can accumulate.

Text · e-Laws consolidated snapshot

9.16.4. — Concrete

Content not available for this version.

9.16.4.1. — Surface Finish

(1) The finished surface of concrete floor slabs shall be trowelled smooth and even.

(2) Dry cement shall not be added to the floor surfaces to absorb surplus water.

Text · e-Laws consolidated snapshot

9.16.4.2. — Topping Course

(1) Where a topping course is provided for a concrete floor slab, it shall consist of 1 part cement to 2.5 parts clean, well graded sand by volume, with a water/cement ratio approximately equal to that of the base slab.

(2) When concrete topping is provided it shall not be less than 20 mm thick.

Text · e-Laws consolidated snapshot

9.16.4.3. — Thickness

(1) Concrete slabs shall be not less than 75 mm thick exclusive of concrete topping.

Text · e-Laws consolidated snapshot

9.16.4.4. — Bond Break

(1) A bond-breaking material shall be placed between the slab and footings or rock.

Text · e-Laws consolidated snapshot

9.16.4.5. — Compressive Strength

(1) Where dampproofing is not provided the concrete used for floors-on-ground shall have a compressive strength of not less than 25 MPa after 28 days.

(2) Where dampproofing is provided as described in Article 9.13.2.7., the concrete used for floors-on-ground shall have a compressive strength of not less than 15 MPa after 28 days.

Text · e-Laws consolidated snapshot

9.16.5. — Wood

Content not available for this version.

9.16.5.1. — Wood Frame Floors

(1) Floors-on-ground constructed of wood shall conform to CAN/CSA-S406, “Construction of Preserved Wood Foundations”.

Text · e-Laws consolidated snapshot

9.17. — Columns

Content not available for this version.

9.17.1. — Scope

Content not available for this version.

9.17.1.1. — Application

(1) This Section applies to columns used to support,

(a) beams carrying loads from not more than 2 wood frame floors where,

(i) the supported length of joists bearing on such beams does not exceed 5 m, and

(ii) the live load on any floor does not exceed 2.4 kPa, or

(b) beams or header joists carrying loads from not more than 2 levels of wood frame balconies, decks or other accessible exterior platforms, or 1 level and the roof, where,

(i) the supported length of joists bearing on such beams or joists does not exceed 5 m,

(ii) the sum of the specified snow load and the load due to use and occupancy does not exceed 4.8 kPa,

(iii) the platform serves only a single suite of residential occupancy, and

(iv) the platform does not serve as a required exit, or

(c) carport roofs.

(2) Columns for applications other than as described in Sentence (1) shall be designed in accordance with Part 4.

Text · e-Laws consolidated snapshot

9.17.2. — General

Content not available for this version.

9.17.2.1. — Location

(1) Columns shall be centrally located on a footing conforming to Section 9.15.

Text · e-Laws consolidated snapshot

9.17.2.2. — Lateral Support

(1) Columns shall be securely fastened to the supported member to reduce the likelihood of lateral differential movement between the column and the supported member.

(2) Except as permitted by Sentence (3), columns shall be laterally supported,

(a) directly, or

(b) by connection to the supported members.

(3) Columns need not be provided with lateral support as described in Sentence (2) where,

(a) the length of the columns are not more than 600 mm measured from the finished ground to the underside of the supported member, and

(b) the columns support a deck with no superstructure.

Text · e-Laws consolidated snapshot

9.17.3. — Steel Columns

Content not available for this version.

9.17.3.1. — Size and Thickness

(1) Except as permitted in Sentence (2), steel pipe columns shall have an outside diameter of not less than 73 mm and a wall thickness of not less than 4.76 mm.

(2) Columns of sizes other than as specified in Sentence (1) are permitted to be used where the loadbearing capacities are shown to be adequate.

Text · e-Laws consolidated snapshot

9.17.3.2. — End Bearing Plates

(1) Except as permitted in Sentence (2), steel columns shall be fitted with not less than 100 mm by 100 mm by 6.35 mm thick steel plates at each end, and where the column supports a wooden beam, the top plate shall extend across the full width of the beam.

(2) The top plate required in Sentence (1) need not be provided where a column supports a steel beam and provision is made for the attachment of the column to the beam.

Text · e-Laws consolidated snapshot

9.17.3.3. — Paint

(1) Exterior steel columns susceptible to corrosion shall be treated on the outside surface with at least one coat of rust-inhibitive paint.

Text · e-Laws consolidated snapshot

9.17.3.4. — Design of Adjustable Steel Columns

(1) Where the imposed load does not exceed 36 kN, adjustable steel columns shall conform to CAN/CGSB-7.2, “Adjustable Steel Columns”.

(2) Adjustable steel columns other than those described in Sentence (1) shall be designed in accordance with Part 4.

Text · e-Laws consolidated snapshot

9.17.4. — Wood Columns

Content not available for this version.

9.17.4.1. — Column Sizes

(1) The width or diameter of a wood column shall be not less than the width of the supported member.

(2) Except as provided in Article 9.35.4.2., columns shall be not less than 184 mm for round columns and 140 mm by 140 mm for rectangular columns, unless calculations are provided to show that lesser sizes are adequate.

Text · e-Laws consolidated snapshot

9.17.4.2. — Materials

(1) Wood columns shall be either solid, glue-laminated or built-up.

(2) Built-up columns shall consist of not less than 38 mm thick full-length members,

(a) bolted together with not less than 9.52 mm diam bolts spaced not more than 450 mm o.c., or

(b) nailed together with not less than 76 mm nails spaced not more than 300 mm o.c.

(3) Glued-laminated columns shall conform to Section 4.3.

Text · e-Laws consolidated snapshot

9.17.4.3. — Columns in Contact with Concrete

(1) Wood columns shall be separated from concrete in contact with the ground by 0.05 mm polyethylene film or Type S roll roofing.

Text · e-Laws consolidated snapshot

9.17.4.4. — Wood Column Termite Protection

(1) Where termites are known to exist, exterior wood columns such as porch supports shall be,

(a) pressure-treated with a chemical that is toxic to such termites, in accordance with Article 9.3.2.9.v1v2, or

(b) supported on non-cellulosic material extending not less than 150 mm above grade and located not less than 50 mm from the exterior wall of an adjacent building.

Text · e-Laws consolidated snapshot

9.17.5. — Unit Masonry Columns

Content not available for this version.

9.17.5.1. — Materials

(1) Unit masonry columns shall be built of masonry units,

(a) conforming to CSA A165.1, “Concrete Block Masonry Units”, and

(b) have a compressive strength over the net area of the block of not less than 15 MPa.

Text · e-Laws consolidated snapshot

9.17.5.2. — Sizes

(1) Unit masonry columns shall be not less than 290 mm by 290 mm or 240 mm by 380 mm in size.

Text · e-Laws consolidated snapshot

9.17.6. — Solid Concrete Columns

Content not available for this version.

9.17.6.1. — Materials

(1) Concrete shall conform to Section 9.3.

Text · e-Laws consolidated snapshot

9.17.6.2. — Sizes

(1) Concrete columns shall be not less than 200 mm by 200 mm for rectangular columns and 230 mm diam for circular columns.

Text · e-Laws consolidated snapshot

9.18. — Crawl Spaces

Content not available for this version.

9.18.1. — General

Content not available for this version.

9.18.1.1. — Application

(1) In this Section, a crawl space refers to an enclosed space between the underside of a floor assembly and the ground cover directly below, with a clearance less than 1 800 mm in height.

Text · e-Laws consolidated snapshot

9.18.1.2. — Foundations

(1) Foundations enclosing crawl spaces shall conform to Section 9.15.

Text · e-Laws consolidated snapshot

9.18.1.3. — Heated and Unheated Crawl Spaces

(1) Crawl spaces shall be considered to be heated where the space,

(a) is used as a hot air plenum,

(b) contains heating ducts or heating pipes that are not sealed and insulated to minimize heat loss to the space, or

(c) is not separated from heated space in accordance with Section 9.25.

(2) Heating of heated crawl spaces shall conform to Section 9.33.

(3) Insulation, an air barrier system and a vapour barrier shall be installed in the walls of heated crawl spaces in accordance with Section 9.25.

Text · e-Laws consolidated snapshot

9.18.2. — Access

Content not available for this version.

9.18.2.1. — Access Openings

(1) An access opening of not less than 500 mm by 700 mm shall be provided to each crawl space where the crawl space serves a single dwelling unit, and not less than 550 mm by 900 mm for other crawl spaces.

(2) Access openings shall be fitted with a door or hatch, except when the crawl space is heated and the access opening into the crawl space is from the adjacent heated space.

Text · e-Laws consolidated snapshot

9.18.3. — Ventilation

Content not available for this version.

9.18.3.1. — Ventilation of Unheated Crawl Spaces

(1) Unheated crawl spaces shall be ventilated by natural or mechanical means.

(2) Where an unheated crawl space is ventilated by natural means, ventilation shall be provided to the outside air by not less than 0.1 m² of unobstructed vent area for every 50 m² of floor area.

(3) Vents shall be,

(a) uniformly distributed on opposite sides of the building, and

(b) designed to prevent the entry of snow, rain and insects.

Text · e-Laws consolidated snapshot

9.18.3.2. — Ventilation of Heated Crawl Spaces

(1) Heated crawl spaces shall be ventilated in accordance with Section 9.32.

Text · e-Laws consolidated snapshot

9.18.4. — Clearance

Content not available for this version.

9.18.4.1. — Access Way to Services

(1) Where equipment requiring service such as plumbing cleanouts, traps and burners is located in crawl spaces, an access way with a height and width of not less than 600 mm shall be provided from the access door to the equipment and for a distance of 900 mm on the side or sides of the equipment to be serviced.

Text · e-Laws consolidated snapshot

9.18.5. — Drainage

Content not available for this version.

9.18.5.1. — Drainage

(1) Except where it can be shown to be unnecessary, the ingress of water into a crawl space shall be controlled by grading or drainage.

(2) Drainage of foundation walls shall conform to Article 9.14.2.1.v1

(3) Drainage of the ground cover or floor-on-ground in the crawl space shall conform to Subsection 9.16.3.

(4) Drains shall conform to Section 9.14.

Text · e-Laws consolidated snapshot

9.18.6. — Ground Cover

Content not available for this version.

9.18.6.1. — Ground Cover in Unheated Crawl Spaces

(1) Where a crawl space is unheated, a ground cover shall be provided consisting of not less than,

(a) 50 mm of asphalt paving material,

(b) 100 mm of 15 MPa Portland cement concrete,

(c) Type S roll roofing, or

(d) 0.10 mm polyethylene.

(2) Joints in sheet-type ground cover required in Sentence (1) shall be lapped not less than 100 mm and weighted down.

Text · e-Laws consolidated snapshot

9.18.6.2. — Ground Cover in Heated Crawl Spaces

(1) Where a crawl space is heated, a ground cover consisting of not less than 0.15 mm polyethylene sheet conforming to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet, for Use in Building Construction”, shall be provided.

(2) The ground cover required in Sentence (1) shall,

(a) have its joints lapped not less than 300 mm, and sealed and weighted down, or

(b) be covered with a concrete skim coat not less than 50 mm thick.

(3) The perimeter of the ground cover required in Sentence (1) shall be sealed to the foundation wall.

Text · e-Laws consolidated snapshot

9.18.7. — Fire Protection

Content not available for this version.

9.18.7.1. — Crawl Spaces as Warm Air Plenums

(1) Only crawl spaces under 1-storey portions of dwelling units shall be used as warm-air plenums.

(2) Enclosing material in crawl spaces described in Sentence (1) including insulation shall have a surface flame-spread rating not greater than 150.

(3) Combustible ground cover used as enclosing material in Sentence (2) shall be covered with noncombustible material.

Text · e-Laws consolidated snapshot

9.19. — Roof Spaces

Content not available for this version.

9.19.1. — Venting

Content not available for this version.

9.19.1.1. — Required Venting

(1) Except where it can be shown to be unnecessary, where insulation is installed between a ceiling and the underside of the roof sheathing, a space shall be provided between the insulation and the sheathing, and vents shall be installed to permit the movement of air from the space to the exterior.

Text · e-Laws consolidated snapshot

9.19.1.2. — Vent Requirements

(1) Except as provided in Sentence (2), the unobstructed vent area shall be not less than 1/300 of the insulated ceiling area.

(2) Where the roof slope is less than 1 in 6 or in roofs that are constructed with roof joists, the unobstructed vent area shall be not less than 1/150 of the insulated ceiling area.

(3) Required vents are permitted to be roof type, eave type, gable-end type or any combination of them, and shall be distributed,

(a) uniformly on opposite sides of the building,

(b) with not less than 25% of the required openings located at the top of the space, and

(c) with not less than 25% of the required openings located at the bottom of the space.

(4) Except where each roof joist space referred to in Sentence (2) is separately vented, roof joist spaces shall be interconnected by installing purlins not less than 38 mm by 38 mm on the top of the roof joists.

(5) Vents shall comply with CAN3-A93-M, “Natural Airflow Ventilators for Buildings”.

Text · e-Laws consolidated snapshot

9.19.1.3. — Clearances

(1) Except as provided in Sentence (2), where venting is provided to a roof joist space, not less than 63 mm of space shall be provided between the top of the insulation and the underside of the roof sheathing.

(2) Where venting is provided at the junction of sloped roofs and exterior walls and where preformed baffles are used to contain the insulation, the baffles shall,

(a) provide an unobstructed air space between the insulation and the underside of the roof sheathing, that is,

(i) not less than 25 mm in dimension, and

(ii) of sufficient cross area to meet the attic or roof space venting requirements of Article 9.19.1.2., and

(b) extend vertically not less than 50 mm vertically above the top of the insulation.

(3) Ceiling insulation shall be installed in a manner that will not restrict a free flow of air through roof vents or through any portion of the attic or roof space.

Text · e-Laws consolidated snapshot

9.19.1.4. — Mansard or Gambrel Roof

(1) The lower portion of a mansard or gambrel style roof need not be ventilated.

(2) The upper portion of roofs described in Sentence (1) shall be ventilated in conformance with the requirements in Articles 9.19.1.1. to 9.19.1.3.v1

Text · e-Laws consolidated snapshot

9.19.2. — Access

Content not available for this version.

9.19.2.1. — Access

(1) Every attic or roof space shall be provided with an access hatch where the attic or roof space measures not less than,

(a) 10 m² in area,

(b) 1 000 mm in length or width, and

(c) 600 mm in height over at least the area described in Clauses (a) and (b).

(2) The hatch required in Sentence (1) shall be not less than 550 mm by 900 mm except that, where the hatch serves a single dwelling unit, the hatch the hatch may be reduced to 0.32 m2 in area with no dimension less than 545 mm.

(3) Hatchways to attic or roof spaces shall be fitted with doors or covers.

Text · e-Laws consolidated snapshot

9.20. — Masonry and Insulating Concrete Form Walls Not in Contact with the Ground

Content not available for this version.

9.20.1. — Application

Content not available for this version.

9.20.1.1. — General

(1) Except as provided in Article 9.20.1.2.v1, this Section applies to,

(a) unreinforced masonry and masonry veneer walls not in contact with the ground, where,

(i) the height of the walls constructed on the foundation walls does not exceed 11 m, and

(ii) the roof or floor assembly above the first storey is not of concrete construction, and

(b) flat insulating concrete form walls not in contact with the ground that,

(i) have a maximum floor to floor height of 3 m,

(ii) are erected in buildings not more than 2 storeys in building height and containing only a single dwelling unit, and

(iii) are erected in locations where the seismic spectral response acceleration, Sa(0.2) is not greater than 0.4.

(2) For walls other than those described in Sentence (1), or where the masonry walls or insulating concrete form walls not in contact with the ground are designed for specified loads on the basis of ultimate and serviceability limit states, Subsection 4.3.2. shall apply.

Text · e-Laws consolidated snapshot

9.20.1.2. — Earthquake Reinforcement

(1) In locations where the seismic spectral response acceleration, Sa(2.0), is greater than 0.55, loadbearing elements of masonry buildings more than 1 storey in building height shall be reinforced with not less than the minimum amount of reinforcement as required in Subsection 9.20.15.

(2) In locations where the seismic spectral response acceleration, Sa(2.0), is greater than 0.35, but less than or equal to 0.55, loadbearing elements of masonry buildings 3 storeys in building height shall be reinforced with not less than the minimum amount of reinforcement as required in Subsection 9.20.15.

Text · e-Laws consolidated snapshot

9.20.2. — Masonry Units

Content not available for this version.

9.20.2.1. — Masonry Unit Standards

(1) Masonry units shall comply with,

(a) ASTM C126, “Ceramic Glazed Structural Clay Facing Tile, Facing Brick, and Solid Masonry Units”,

(b) ASTM C212, “Structural Clay Facing Tile”,

(c) CAN/CSA-A82.1-M, “Burned Clay Brick (Solid Masonry Units Made from Clay or Shale)”,

(d) CSA A82.3-M, “Calcium Silicate (Sand-Lime) Building Brick”,

(e) CSA A82.4-M, “Structural Clay Load-Bearing Wall Tile”,

(f) CSA A82.5-M, “Structural Clay Non-Load-Bearing Tile”,

(g) CAN3-A82.8-M, “Hollow Clay Brick”,

(h) CSA A165.1, “Concrete Block Masonry Units”,

(i) CSA A165.2, “Concrete Brick Masonry Units”,

(j) CSA A165.3, “Prefaced Concrete Masonry Units”, or

(k) CAN3-A165.4-M, “Autoclaved Cellular Units”.

Text · e-Laws consolidated snapshot

9.20.2.2. — Used Brick

(1) Used bricks shall be free of old mortar, soot or other surface coating and shall conform to Article 9.20.2.1.

Text · e-Laws consolidated snapshot

9.20.2.3. — Glass Blocks

(1) Glass blocks shall not be used as loadbearing units or in the construction of fireplaces or chimneys.

Text · e-Laws consolidated snapshot

9.20.2.4. — Cellular Concrete

(1) Masonry made with cellular concrete shall not be used in contact with the soil or exposed to the weather.

Text · e-Laws consolidated snapshot

9.20.2.5. — Stone

(1) Stone shall be sound and durable.

Text · e-Laws consolidated snapshot

9.20.2.6. — Concrete Units Exposed to the Weather

(1) Concrete blocks exposed to the weather shall have weight and water absorption characteristics conforming to Classes A, B, C or D, described in CSA A165.1, “Concrete Block Masonry Units”.

Text · e-Laws consolidated snapshot

9.20.2.7. — Compressive Strength

(1) The compressive strength of concrete blocks shall conform to Table 9.20.2.7.

Text · e-Laws consolidated snapshot

Table 9.20.2.7. Compressive Strength of Concrete Blocks Forming Part of Sentence 9.20.2.7.(1)

Column 1

Column 2

Column 3

Type of Block

Minimum Compressive Strength Over Net Area, MPa

Exposed to Weather

Not Exposed to Weather

Solid or hollow concrete blocks

15

10

Solid loadbearing cellular blocks

Not permitted

5

Solid non-loadbearing cellular blocks

Not permitted

2

9.20.3. — Mortar

Content not available for this version.

9.20.3.1. — Mortar Materials

(1) Cementitious materials and aggregates for mortar and grout shall comply with CSA A179, “Mortar and Grout for Unit Masonry”.

(2) Water and aggregate shall be clean and free of significant amounts of deleterious materials.

(3) Lime used in mortar shall be hydrated.

(4) If lime putty is used in mortar, it shall be made by slaking quicklime in water for not less than 24 h or soaking hydrated lime in water for not less than 12 h.

Text · e-Laws consolidated snapshot

9.20.3.2. — Mortar and Grout Mixes

(1) Mortar types shall conform to Table 9.20.3.2.A.

(2) Mortar for glass block masonry shall be,

(a) Type S Portland cement-lime where exposed to the exterior, or

(b) Type S or N where protected from the exterior.

(3) Mortar mix proportions shall conform to Table 9.20.3.2.B., with sufficient water to bring the mixture to a consistency adequate for laying masonry units.

(4) Grout mix proportions shall conform to Table 9.20.3.2.C., with sufficient water to provide a suitable flow to fill all voids completely, without excessive segregation or bleeding.

(5) Except as provided in Sentence (6), mortar shall be used and placed in final position,

(a) within 1.5 h after mixing when the air temperature is 25°C or higher, and

(b) within 2.5 h after mixing when the air temperature is less than 25°C.

(6) Mortar and grout containing a set-control admixture shall be manufactured off-site in a batching plant and shall be used and placed in final position within a time not exceeding the useful life as stipulated by the manufacturer.

(7) Grout used for reinforced masonry shall be placed in accordance with the requirements of CSA A371, “Masonry Construction for Buildings”.

Text · e-Laws consolidated snapshot

Table 9.20.3.2.A. Mortar Use Forming Part of Sentence 9.20.3.2.(1)

Column 1

Column 2

Column 3

Location

Building Element

Mortar Type

Exterior, above ground

Loadbearing walls and columns

S

Non-loadbearing walls and columns

N or S

Parapets, chimneys and masonry veneer

N or S

Exterior, at or below ground

Foundation walls and chimneys

S

Interior

Loadbearing walls and columns

N

Non-loadbearing walls and columns

N

Table 9.20.3.2.B. Mortar Mix Proportions (by Volume) Forming Part of Sentence 9.20.3.2.(3)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Mortar Type

Portland Cement

Lime

Masonry Cement Type N

Masonry Cement Type S

Fine Aggregate (damp, loose-state sand)

S

1

½

-

-

3½ - 4½

-

-

-

1

2¼ - 3

½

-

1

-

3½ - 4½

N

1

1

-

-

4½ - 6

-

-

1

-

2¼ - 3

Table 9.20.3.2.C. Grout Mix Proportions (by Volume) Forming Part of Sentence 9.20.3.2.(4)

Column 1

Column 2

Column 3

Column 4

Portland Cement

Lime

Fine Aggregate (sand)

Coarse Aggregate

1

0 to 1/10

2¼ to 3 times the sum of the cement and lime volumes

1 to 2 times the sum of the cement and lime volumes

9.20.4. — Mortar Joints

Content not available for this version.

9.20.4.1. — Thickness

(1) Except as provided in Sentence (2), mortar joint thickness for burned clay brick and concrete masonry units shall be 10 mm.

(2) Permitted tolerances in head and bed joints shall be -5 mm to +10 mm.

Text · e-Laws consolidated snapshot

9.20.4.2. — Solid Masonry Units

(1) Except for head joints left open for weep holes and ventilation, solid masonry units shall be laid with full head and bed joints.

Text · e-Laws consolidated snapshot

9.20.4.3. — Hollow Masonry Units

(1) Hollow masonry units shall be laid with mortar applied to head and bed joints of both inner and outer face shells.

(2) Vertically aligned webs of hollow masonry units shall be laid in a full bed of mortar,

(a) under the starting course,

(b) in all courses of columns, and

(c) where adjacent to cells or cavities that are to be filled with grout.

Text · e-Laws consolidated snapshot

9.20.5. — Masonry Support

Content not available for this version.

9.20.5.1. — Masonry Support

(1) All masonry shall be supported on masonry, concrete or steel, except that masonry veneer walls are permitted to be supported on foundations of wood frame constructed in conformance with Sentence 9.15.2.4.(1).

(2) Every masonry wall shall be at least as thick as the wall it supports, except as otherwise permitted in Article 9.20.12.2.

Text · e-Laws consolidated snapshot

9.20.5.2. — Lintels or Arches

(1) Masonry over openings shall be supported by steel, reinforced concrete lintels or masonry arches designed to support the imposed loads.

(2) Except as permitted in Sentences (3) and (6), steel angle lintels supporting masonry above openings shall conform to Table 9.20.5.2.A.

(3) Steel angle lintels supporting masonry veneer above openings shall conform to Table 9.20.5.2.B.

(4) Steel lintels described in Sentences (2) and (3) shall,

(a) have even and level bearing and shall have not less than 150 mm length of bearing at end supports, and

(b) bear on masonry, concrete or steel.

(5) Steel angle lintels supporting masonry shall be primed or painted or otherwise protected from corrosion.

(6) Steel beams supporting masonry veneer and wood stud walls above openings shall conform to Table 9.20.5.2.C.

(7) Steel beams described in Sentence (6) shall be supported at each end by a steel column, and have a minimum 6 mm plate welded to the flange to support the masonry veneer.

Notes toTable 9.20.5.2.C.:

(1) These spans assume that the beam supports the veneer, a wood stud wall and a maximum specified roof live load of 2.3 kN/m.

(2) Where the steel beam carries floor loads or larger roof loads, refer to Article 9.23.4.3.v1

Editor's note

This map follows the as-filed text of O. Reg. 350/06, whose notes to Table 9.20.5.2.c. read '(1) these spans ...' (with a space after the note number) and whose steel-angle dimensions use the letter 'x' (e.g. '82 x 250'). The e-Laws consolidation editorially renders these as '(1)these' (no space) and with the multiplication sign '×'; no amending regulation makes these changes.

Text · e-Laws consolidated snapshot

Table 9.20.5.2.A. Loose Steel Lintels for Masonry – No. & Size of Angles Required(7) Forming Part of Sentence 9.20.5.2.(2)

Column 1

Column 2

Column 3

Column 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Clear Span(1)(3)

Exterior Angles

Wall Thickness,mm

Interior Angles

for Brick

for Stone

Maximum Floor Loads per Metre of Span in Newtons(2)(4)(5)

100 mm

100 mm + 50 mm stone facing

None

3 650

7 300

10 950

14 600

18 250

21 900

No Floor Load

1 200 mm or less

L-90 × 90 × 6

L-125 × 90 × 8

203

L-90

L-90

L-90

L-100

L-125

L-125

L-125

x 90

x 90

x 90

x 90

x 90

x 90

x 90

x6

x6

x8

x8

x8

x10

x13

305

2Ls-90

2Ls-90

2Ls-90

2Ls-90

2Ls-90

2Ls-100

2Ls-100

x 90

x 90

x 90

x 90

x 90

x 90

x 90

x 8

x 8

x 8

x 8

x 8

x 8

x 8

1 500 mm

L-90 × 90 × 8

L-125 × 90 × 8

203

L-90

L-90

L-125

L-125

L-125

L-150

x 90

x 90

x 90

x 90

x 90

x 90

x8

x8

x8

x10

x13

x10

305

2Ls-90

2Ls-90

2Ls-90

2Ls-125

2Ls-125

2Ls-125

2Ls-125

x 90

x 90

x 90

x 90

x 90

x 90

x 90

x 8

x 8

x 8

x 8

x 8

x 8

x 10

1 800 mm

L-100 × 90 × 8

L-125 × 125 × 8

203

L-100

L-125

L-125

L-150

x 90

x 90

x 90

x 100

x 8

x 8

x 8

x 10

305

2Ls-100

2Ls-100

2Ls-125

2Ls-125

2Ls-125

2Ls-150

2Ls-150

x 90

x 90

x 90

x 90

x 90

x 100

x 100

x 8

x 8

x 8

x 8

x 10

x 10

x 10

2 100 mm

L-100 × 90 × 8

L-125 × 125 × 8

203

L-100

L-125

L-150

x 90

x 90

x 100

x 8

x 10

x 10

305

2Ls-100

2Ls-125

2Ls-125

2Ls-150

2Ls-150

x 90

x 90

x 90

x 100

x 100

x 8

x 10

x 10

x 10

x 10

2 400 mm

L-125 × 90 × 8

L-125 × 125 × 8

203

L-125

L-150

x 90

x 100

x 8

x 10

305

2Ls-125

2Ls-125

2Ls-150

x 90

x 90

x 100

x 8

x 13

x 10

2 700 mm

L-125 × 90 × 10

L-125 × 125 × 10

203

L-125

x 90

x 10

305

2Ls-125

2Ls-150

x 150

x 100

x 10

x 10

3 000 mm

L-150 × 100 × 10

L-125 × 125 × 13

203

L-150

x 100

x 10

305

2Ls-150

x 100

x 10

Notes to Table 9.20.5.2.A.:

(1)See Sentence 9.20.5.2.(4).

(2)Omit floor load in lintel when distance to bottom of floor construction is greater than width of opening.

(3)Interior and exterior angles in 200 mm walls and interior angles in 300 mm walls are bolted together when clear span is over 1 800 mm.

(4)When masonry lighter than brick is used over interior angles floor load may be increased by the difference in weight per square metre times the width of the opening. Not generally available.

(5)Interior angles have been designed for floor load plus brick masonry of height equal to width of opening.

(6)fs = 138 Mpa., Deflection maximum = 1/700 span.

(7)The figures in the Table indicating wall thickness and angle cross-section are in mm.

Table 9.20.5.2.B. Maximum Allowable Spans for Steel Lintels Supporting Masonry Veneer, m Forming Part of Sentence 9.20.5.2.(3)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Minimum Angle Size, mm

70 mm

90 mm

100 mm

Vertical Leg

Horizontal Leg

Thickness

Brick

Brick

Stone

90

75

6

2.55

90

90

6

2.59

2.47

2.30

100

90

6

2.79

2.66

2.48

125

90

8

3.47

3.31

3.08

125

90

10

3.64

3.48

3.24

125

90

13

3.82

3.59

3.33

150

90

10

4.06

3.82

3.54

150

90

13

4.32

4.07

3.77

150

100

13

4.37

4.12

3.82

180

100

10

4.57

4.30

3.99

180

100

13

4.87

4.59

4.25

Table 9.20.5.2.C. Maximum Allowable Spans for Steel Beams Supporting Masonry Veneer, m(1), (2) Forming Part of Sentence 9.20.5.2.(6)

Column 1

Column 2

Column 3

Column 4

Section

70 mm Brick

90 mm Brick

100 mm Stone

W 150 × 22

4.23

4.09

3.92

W 150 × 30

4.68

4.52

4.32

W 200 × 27

5.26

5.08

4.84

W 200 × 31

5.57

5.37

5.11

W 200 × 36

5.70

5.49

5.23

9.20.6. — Thickness and Height

Content not available for this version.

9.20.6.1. — Thickness of Exterior Walls

(1) Masonry exterior walls, other than cavity walls, in 1 storey buildings and the top storeys of 2- and 3-storey buildings shall be not less than 140 mm thick provided the walls are not more than 2.8 m high at the eaves and 4.6 m high at the peaks of gable ends.

(2) The exterior walls of the bottom storeys of 2 storey buildings, and exterior walls of the bottom 2 storeys of 3 storey buildings shall be not less than 190 mm thick.

(3) In exterior walls composed of more than one wythe, each wythe shall be not less than 90 mm thick.

Text · e-Laws consolidated snapshot

9.20.6.2. — Cavity Walls

(1) Cavity walls shall be made with not less than 90 mm wide units if the joints are raked and not less than 75 mm wide units if the joints are not raked.

(2) The width of a cavity in a cavity wall shall be not less than 50 mm nor greater than 150 mm.

(3) The minimum thickness of cavity walls above the supporting base shall be 230 mm for the top 7.6 m and 330 mm for the remaining portion, except that where 75 mm wide units are used, the wall height above the top of the foundation wall shall not exceed 6 m.

Text · e-Laws consolidated snapshot

9.20.6.3. — Thickness of Interior Walls

(1) The thickness of loadbearing interior walls shall be determined on the basis of the maximum lateral support spacing as provided in Sentences 9.20.10.1.(2) and (3).

(2) The thickness of interior non-loadbearing walls shall be,

(a) determined on the basis of the maximum lateral support spacing as provided in Sentences 9.20.10.1.(2) and (3), and

(b) in any case, not less than 65 mm.

Text · e-Laws consolidated snapshot

9.20.6.4. — Masonry Veneer

(1) Except for masonry veneer where each masonry unit is supported individually by the structural backing, masonry veneer shall be of solid units not less than 70 mm thick.

(2) Veneer described in Sentence (1) over wood frame walls shall have not less than a 25 mm air space behind the veneer.

(3) Masonry veneer less than 90 mm thick shall have unraked joints.

(4) Masonry veneer shall conform to Subsection 4.3.2. where the masonry units are required to be individually supported by the structural backing.

Text · e-Laws consolidated snapshot

9.20.6.5. — Parapet Walls

(1) The height of parapet walls above the adjacent roof surface shall be not more than 3 times the parapet wall thickness.

(2) Parapet walls shall be solid from the top of the parapet to not less than 300 mm below the adjacent roof level.

Text · e-Laws consolidated snapshot

9.20.6.6. — Stone or Concrete Facings

(1) Slab and panel facings of precast concrete and natural or artificial stone shall conform to Subsection 4.3.2.

Text · e-Laws consolidated snapshot

9.20.7. — Chases and Recesses

Content not available for this version.

9.20.7.1. — Maximum Dimensions

(1) Except as permitted in Sentence 9.20.7.2.(2) and Article 9.20.7.4., the depth of any chase or recess shall not exceed one third the thickness of the wall, and the width of the chase or recess shall not exceed 500 mm.

Text · e-Laws consolidated snapshot

9.20.7.2. — Minimum Wall Thickness

(1) Except as permitted in Sentence (2) and Article 9.20.7.4., no chase or recess shall be constructed in any wall 190 mm or less in thickness.

(2) Recesses may be constructed in 190 mm walls provided they do not exceed 100 mm in depth, 750 mm in height and 500 mm in width.

Text · e-Laws consolidated snapshot

9.20.7.3. — Separation of Chases and Recesses

(1) Chases and recesses shall be not less than,

(a) 4 times the wall thickness apart measured from centre to centre, and

(b) 600 mm away from any pilaster, cross wall, buttress or other vertical element providing required lateral support for the wall.

Text · e-Laws consolidated snapshot

9.20.7.4. — Non-Conforming Chases or Recesses

(1) Chases or recesses that do not conform to the limits specified in Articles 9.20.7.1. to 9.20.7.3.v1 shall be considered as openings, and any masonry supported above such a chase or recess shall be supported by a lintel or arch as provided in Article 9.20.5.2.v1

Text · e-Laws consolidated snapshot

9.20.7.5. — Chases or Recesses Cut into Walls

(1) Chases or recesses shall not be cut into walls made with hollow units after the masonry units are in place.

Text · e-Laws consolidated snapshot

9.20.8. — Support of Loads

Content not available for this version.

9.20.8.1. — Capping of Hollow Masonry Walls

(1) Except as permitted in Sentence (2), loadbearing walls of hollow masonry units supporting roof or floor framing members shall be capped with not less than 50 mm of solid masonry or have the top course filled with concrete.

(2) Capping required in Sentence (1) may be omitted where the roof framing is supported on a wood plate not less than 38 mm by 89 mm.

Text · e-Laws consolidated snapshot

9.20.8.2. — Cavity Walls Supporting Framing Members

(1) Floor joists supported on cavity walls shall be supported on solid units not less than 57 mm high.

(2) Floor joists described in Sentence (1) shall not project into the cavity.

(3) Roof and ceiling framing members bearing on cavity walls shall be supported on,

(a) not less than 57 mm of solid masonry, bridging the full thickness of the wall, or

(b) a wood plate not less than 38 mm thick, bearing not less than 50 mm on each wythe.

Text · e-Laws consolidated snapshot

9.20.8.3. — Bearing of Beams and Joists

(1) The bearing area under beams and joists shall be sufficient to carry the supported load.

(2) In no case shall the minimum length of end bearing of beams supported on masonry be less than 90 mm.

(3) The length of end bearing of floor, roof or ceiling joists supported on masonry shall be not less than 40 mm.

Text · e-Laws consolidated snapshot

9.20.8.4. — Support of Beams and Columns

(1) Beams and columns supported on masonry walls shall be supported on pilasters where the thickness of the masonry wall or wythe is less than 190 mm.

(2) Not less than 190 mm depth of solid masonry or concrete shall be provided under the beam or column referred to in Sentence (1).

(3) Pilasters required in Sentence (1) shall be bonded or tied to masonry walls.

(4) Concrete pilasters required in Sentence (1) shall be not less than 50 mm by 300 mm.

(5) Unit masonry pilasters required in Sentence (1) shall be not less than 100 mm by 290 mm.

Text · e-Laws consolidated snapshot

9.20.8.5. — Distance to Edge of Supporting Members

(1) Masonry veneer of hollow units resting on bearing support shall not project more than,

(a) 30 mm beyond the supporting base where the veneer is not less than 90 mm thick, and

(b) 12 mm beyond the supporting base where the veneer is less than 90 mm thick.

(2) Masonry veneer of solid units resting on bearing support shall not project more than one third of the width of the veneer.

(3) Where the masonry veneer described in Sentence (2) is rough stone masonry,

(a) the projection shall be measured as the average projection of the units, and

(b) the width of the veneer shall be measured as the average width of the veneer.

Text · e-Laws consolidated snapshot

9.20.9. — Bonding and Tying

Content not available for this version.

9.20.9.1. — Joints to be Offset or Reinforced

(1) Vertical joints in adjacent masonry courses shall be offset unless each wythe of masonry is reinforced with the equivalent of no fewer than 2 corrosion-resistant steel bars of 3.76 mm diam placed in the horizontal joints at vertical intervals not exceeding 460 mm.

(2) Where joints in the reinforcing referred to in Sentence (1) occur, the bars shall be lapped not less than 150 mm.

Text · e-Laws consolidated snapshot

9.20.9.2. — Bonding or Tying of Other than Masonry Veneer

(1) Except as provided in Article 9.20.9.5 for masonry veneer, masonry walls that consist of 2 or more wythes shall have the wythes bonded or tied together with masonry bonding units as described in Article 9.20.9.3. or with metal ties as described in Articles 9.20.9.4.

Text · e-Laws consolidated snapshot

9.20.9.3. — Bonding

(1) Where wythes are bonded together with masonry units, the bonding units shall comprise not less than 4 per cent of the wall surface area.

(2) Bonding units described in Sentence (1) shall be spaced not more than 600 mm vertically and horizontally in the case of brick masonry and 900 mm o.c. in the case of block or tile.

(3) Units described in Sentence (1) shall extend not less than 90 mm into adjacent wythes.

Text · e-Laws consolidated snapshot

9.20.9.4. — Tying

(1) Where 2 or more wythes are tied together with metal ties of the individual rod type, the ties shall conform to the requirements in Sentences (3) to (6).

(2) Other ties may be used where it can be shown that such ties provide walls that are at least as strong and as durable as those made with the individual rod type.

(3) Metal ties of the individual rod type shall,

(a) be corrosion-resistant,

(b) have a minimum cross-sectional area of not less than 17.8 mm², and

(c) have not less than a 50 mm portion bent at right angles at each end.

(4) Metal ties of the individual rod type shall,

(a) extend from within 25 mm of the outer face of the wall to within 25 mm of the inner face of the wall,

(b) be completely embedded in mortar except for the portion exposed in cavity walls, and

(c) be staggered from course to course.

(5) Where 2 or more wythes in walls other than cavity walls and masonry veneer/masonry back-up walls are tied together with metal ties of the individual rod type, the space between wythes shall be completely filled with mortar.

(6) Ties described in Sentence (5) shall be,

(a) located within 300 mm of openings and spaced not more than 900 mm apart around openings, and

(b) spaced not more than 900 mm apart horizontally and 460 mm apart vertically at other locations.

(7) Except as required in Sentences (8) and (9), where the inner and outer wythes of cavity walls are tied with individual wire ties, the ties shall be spaced not more than 900 mm apart horizontally and 400 mm apart vertically.

(8) Within 100 mm of the bottom of each floor or roof assembly where the cavity extends below the assemblies, the ties described in Sentence (7) shall be spaced not more than 600 mm apart horizontally.

(9) Within 300 mm of any openings, the ties described in Sentence (7) shall be spaced not more than 900 mm apart.

Text · e-Laws consolidated snapshot

9.20.9.5. — Ties for Masonry Veneer

(1) Masonry veneer 70 mm or more in thickness and resting on a bearing support shall be tied to masonry back-up or to wood framing members with straps that are,

(a) corrosion-resistant,

(b) not less than 0.76 mm thick,

(c) not less than 22 mm wide,

(d) shaped to provide a key with the mortar, and

(e) spaced in accordance with Table 9.20.9.5.

(2) The straps described in Sentence (1) that are fastened to the wood framing members shall be,

(a) bent at a right angle within 6 mm from the fastener, and

(b) fastened with corrosion resistant 3.18 mm diam. screws or spiral nails having a wood penetration of not less than 30 mm.

(3) Masonry veneer individually supported by masonry or wood-frame back-up shall be secured to the back-up in conformance with Subsection 4.3.2.

(4) The straps described in Sentence (1) may be installed against one of the sheathings listed in Table 9.23.16.2.A.v1 provided that,

(a) the tie is in contact with the exterior surface of the sheathing, and

(b) the sheathing beneath the tie is not compressed.

Text · e-Laws consolidated snapshot

Table 9.20.9.5. Veneer Tie Spacing Forming Part of Sentence 9.20.9.5.(1)

Column 1

Column 2

Maximum Vertical Spacing, mm

Maximum Horizontal Spacing, mm

400

800

500

600

600

400

9.20.9.6. — Reinforcing for Glass Block

(1) Glass block shall have horizontal joint reinforcement of 2 corrosion-resistant bars of not less than 3.76 mm or expanded metal strips not less than 75 mm wide,

(a) spaced at vertical intervals of not more than 600 mm for units 190 mm or less in height, and

(b) installed in every horizontal joint for units higher than 190 mm.

(2) Reinforcement required in Sentence (1) shall be lapped not less than 150 mm.

Text · e-Laws consolidated snapshot

9.20.10. — Lateral Support

Content not available for this version.

9.20.10.1. — Lateral Support Required

(1) Masonry walls shall be laterally supported by floor or roof construction or by intersecting masonry walls or buttresses.

(2) The spacing of supports required in Sentence (1) shall be not more than,

(a) 20 times the wall thickness for all loadbearing walls and exterior non-loadbearing walls, and

(b) 36 times the wall thickness for interior non-loadbearing walls.

(3) In applying Sentence (2), the thickness of cavity walls shall be taken as the greater of,

(a) two-thirds of the sum of the thicknesses of the wythes, or

(b) the thickness of the thicker wythe.

(4) Floor and roof constructions providing lateral support for walls as required in Sentence (1) shall be constructed to transfer lateral loads to walls or buttresses approximately at right angles to the laterally supported walls.

Text · e-Laws consolidated snapshot

9.20.11. — Anchorage of Roofs, Floors and Intersecting Walls

Content not available for this version.

9.20.11.1. — Anchorage of Floor or Roof Assemblies

(1) Where required to receive lateral support, masonry walls shall be anchored to each floor or roof assembly at maximum intervals of 2 000 mm, except that anchorage of floor joists not more than 1 000 mm above grade may be omitted.

(2) Anchors required in Sentence (1) shall be corrosion-resistant and be not less than the equivalent of 40 mm by 4.76 mm thick steel straps.

(3) Anchors required in Sentence (1) shall be shaped to provide a mechanical key with the masonry and shall be securely fastened to the horizontal support to develop the full strength of the tie.

(4) When joists are parallel to the wall, anchors required in Sentence (1) shall extend across no fewer than 3 joists.

Text · e-Laws consolidated snapshot

9.20.11.2. — Bonding and Tying of Intersecting Walls

(1) Where required to provide lateral support, intersecting walls shall be bonded or tied together.

(2) Where bonding is used to satisfy the requirements of Sentence (1), 50% of the adjacent masonry units in the intersecting wall, distributed uniformly over the height of the intersection, shall be imbedded in the laterally supported wall.

(3) Where tying is used to satisfy the requirements of Sentence (1), the ties shall be,

(a) corrosion-resistant metal,

(b) equivalent to not less than 4.76 mm by 40 mm steel strapping,

(c) spaced not more than 800 mm o.c. vertically, and

(d) shaped at both ends to provide sufficient mechanical key to develop the strength of the ties.

Text · e-Laws consolidated snapshot

9.20.11.3. — Wood Frame Walls Intersecting Masonry Walls

(1) Wood-frame walls shall be tied to intersecting masonry walls with not less than 4.76 mm diam corrosion-resistant steel rods spaced not more than 900 mm o.c. vertically.

(2) Ties required in Sentence (1) shall be anchored to the wood framing at one end and shaped to provide a mechanical key at the other end to develop the strength of the tie.

Text · e-Laws consolidated snapshot

9.20.11.4. — Wood Frame Roof Systems

(1) Except as permitted in Sentence (2), roof systems of wood-frame construction shall be tied to exterior walls by not less than 12.7 mm diam anchor bolts,

(a) spaced not more than 2 400 mm apart,

(b) embedded not less that 90 mm into the masonry, and

(c) fastened to a rafter plate of not less than 38 mm thick lumber.

(2) The roof system described in Sentence (1) is permitted to be anchored by nailing the wall furring strips to the side of the rafter plate.

Text · e-Laws consolidated snapshot

9.20.11.5. — Cornices, Sills and Trim

(1) Cornices, sills or other trim of masonry material that project beyond the wall face shall have not less than 65% of their mass, but not less than 90 mm, within the wall or shall be adequately anchored to the wall with corrosion-resistant anchors.

Text · e-Laws consolidated snapshot

9.20.11.6. — Piers

(1) Where anchor bolts are to be placed in the top of a masonry pier, the pier shall conform to the requirements of Sentence 9.15.2.3.(4) and shall be capped with concrete or reinforced masonry not less than 200 mm thick.

Text · e-Laws consolidated snapshot

9.20.12. — Corbelling

Content not available for this version.

9.20.12.1. — Corbelling

(1) All corbelling shall consist of solid units.

(2) The units referred to in Sentence (1) shall be corbelled so that the horizontal projection of any unit does not exceed 25 mm and the total projection does not exceed one-third of the total wall thickness.

Text · e-Laws consolidated snapshot

9.20.12.2. — Corbelling for Cavity Walls

(1) Cavity walls of greater thickness than the foundation wall on which they rest shall not be corbelled but may project 25 mm over the outer face of the foundation wall disregarding parging.

(2) Where the foundation wall referred to in Sentence (1) is unit masonry, it is permitted to be corbelled to meet flush with the inner face of a cavity wall provided,

(a) the projection of each course does not exceed half the height or one-third the width of the corbelled unit, and

(b) the total corbel does not exceed one-third of the foundation wall thickness.

Text · e-Laws consolidated snapshot

9.20.12.3. — Corbelling for Masonry Veneer

(1) Masonry veneer resting on a bearing support shall not project more than 25 mm beyond the supporting base where the veneer is at least 90 mm thick, and 12 mm beyond the supporting base where the veneer is less than 90 mm thick.

(2) In the case of rough stone veneer, the projection, measured as the average projection of the stone units, shall not exceed one-third the bed width beyond the supporting base.

Text · e-Laws consolidated snapshot

9.20.13. — Control of Rain Water Penetration

Content not available for this version.

9.20.13.1. — Materials for Flashing

(1) Material used for flashing shall conform to Table 9.20.13.1.

(2) Aluminum flashing in contact with masonry or concrete shall be effectively coated or separated from the masonry or concrete by an impervious membrane.

Text · e-Laws consolidated snapshot

Table 9.20.13.1. Flashing Material Forming Part of Sentence 9.20.13.1.(1)

Column 1

Column 2

Column 3

Material

Minimum Thickness, mm

Exposed Flashing

Concealed Flashing

Aluminum

0.48

Copper

0.46

0.46

Copper or aluminum laminated to felt or kraft paper

0.05

Hot dipped or galvanized steel

0. 33

0.33

Lead sheet

1.73

1.73

Polyethylene

0.50

Roll roofing, Type S

standard

Zinc

0.46

0.46

9.20.13.2. — Fastening of Flashing

(1) Fastening devices for flashing shall be corrosion-resistant and where metal flashing is used, shall be compatible with the flashing with respect to galvanic action.

Text · e-Laws consolidated snapshot

9.20.13.3. — Location of Flashing

(1) Flashing shall be installed in masonry and masonry veneer walls,

(a) beneath jointed masonry window sills,

(b) over the back and top of parapet walls,

(c) over the heads of glass block panels, beneath weep holes, and

(d) over the heads of window and door openings in exterior walls when the vertical distance between the top of a window or door frame and the bottom edge of the eave exceeds one-quarter of the horizontal eave overhang.

(2) Throughwall flashing shall be provided in a masonry veneer wall such that any moisture that accumulates in the air space will be directed to the exterior of the building.

Text · e-Laws consolidated snapshot

9.20.13.4. — Extension of Flashing

(1) A flashing may be deleted when the masonry at the sill of a wall opening or the top of a wall is protected by an impervious non-jointed masonry coping that conforms to Article 9.20.13.12.

(2) When installed beneath jointed masonry window sills and jointed masonry copings or over the heads of openings, flashing shall extend from the front edge of the masonry up behind the sill or lintel.

Text · e-Laws consolidated snapshot

9.20.13.5. — Flashing for Weep Holes in Masonry Veneer/Masonry Walls

(1) Flashing beneath weep holes in cavity walls and masonry veneer/masonry back-up walls shall,

(a) be bedded not less than 25 mm in the inside wythe,

(b) extend to not less than 5 mm beyond the outer face of the building element below the flashing, and

(c) be installed with a nominally horizontal slope toward the outside wythe.

Text · e-Laws consolidated snapshot

9.20.13.6. — Flashing for Weep Holes in Veneer

(1) Flashing beneath weep holes in masonry veneer over masonry back-up walls shall conform to the flashing requirements for cavity walls and masonry veneer/masonry back-up walls in Article 9.20.13.5.

(2) Flashing beneath weep holes in masonry veneer over wood-frame walls shall be installed so that it extends from a point not less than 5 mm beyond the outer face of the building element below the flashing to a point 150 mm up the wood frame wall.

(3) Where the frame wall is sheathed with a sheathing membrane, a non-wood-based rigid exterior insulating sheathing or a semi-rigid insulating sheathing with an integral sheathing membrane, the flashing shall be installed behind the sheathing membrane or insulating sheathing.

(4) Flashing described in Sentence (2) is permitted to conform to the requirements for concealed flashing in Table 9.20.13.1.

Text · e-Laws consolidated snapshot

9.20.13.7. — Flashing Joints

(1) Joints in flashing shall be made watertight.

Text · e-Laws consolidated snapshot

9.20.13.8. — Required Weep Holes

(1) Weep holes spaced not more than 800 mm apart shall be provided at the bottom of,

(a) cavities in cavity walls, and

(b) cavities or air spaces in masonry veneer walls.

(2) The cavities or air spaces described in Sentence (1) shall include those above lintels over window and door openings required to be flashed in conformance with Article 9.20.13.3.

(3) The weep holes required in Sentence (1) shall be in a location such that any water that collects in the cavity or space will be directed to the exterior of the building.

Text · e-Laws consolidated snapshot

9.20.13.9. — Protection of Interior Finish

(1) Except as provided in Sentence (3), where the interior finish of the exterior walls of a building is a type that may be damaged by moisture, exterior masonry walls, other than cavity walls or walls that are protected for their full height by a roof of a carport or porch, shall be,

(a) parged on the interior surface, and

(b) covered with No. 15 breather-type asphalt-saturated paper conforming to CAN/CGSB-51.32-M, “Sheathing, Membrane, Breather Type”, and shall be lapped not less than 100 mm at the joints.

(2) In situations described in Sentence (1), flashing shall be provided where water will accumulate, to lead it to the exterior.

(3) Where the insulation effectively limits the passage of water vapour and is applied by a waterproof adhesive or by mortar directly to the masonry, the requirements for sheathing paper do not apply.

Text · e-Laws consolidated snapshot

9.20.13.10. — Mortar Droppings

(1) Cavity walls shall be constructed so that mortar droppings are prevented from forming a bridge to allow the passage of rain water across the cavity.

Text · e-Laws consolidated snapshot

9.20.13.11. — Caulking at Door and Window Frames

(1) The junction of door and window frames with masonry shall be caulked in conformance with Subsection 9.27.4.

Text · e-Laws consolidated snapshot

9.20.13.12. — Drips Beneath Window Sills

(1) Except for wall openings located less than 150 mm above ground level, where a concealed flashing is not installed beneath window and door sills, such sills shall be provided with an outward slope and a drip located not less than 25 mm from the wall surface.

Text · e-Laws consolidated snapshot

9.20.14. — Protection During Work

Content not available for this version.

9.20.14.1. — Laying Temperature of Mortar and Masonry

(1) Mortar and masonry shall be maintained at a temperature not below 5°C during installation and for not less than 48 h after installation.

(2) No frozen material shall be used in the mortar mix.

Text · e-Laws consolidated snapshot

9.20.14.2. — Protection from Weather

(1) The top surface of uncompleted masonry exposed to the weather shall be completely covered with a waterproofing material when construction is not in progress.

Text · e-Laws consolidated snapshot

9.20.15. — Reinforcement for Earthquake Resistance

Content not available for this version.

9.20.15.1. — Amount of Reinforcement

(1) Where reinforcement is required in this Section, masonry walls shall be reinforced horizontally and vertically with steel having a total cross-sectional area of not less than 0.002 times the horizontal cross-sectional area of the wall, so that not less than one-third of the required steel area is installed either horizontally or vertically and the remainder in the other direction.

Text · e-Laws consolidated snapshot

9.20.15.2. — Installation Standard

(1) Where reinforcement for masonry is required in this Section, it shall be installed in conformance with the requirements for reinforced masonry as contained in CSA A371, “Masonry Construction for Buildings”.

Text · e-Laws consolidated snapshot

9.20.16. — Corrosion Resistance

Content not available for this version.

9.20.16.1. — Corrosion Resistance of Connectors

(1) Carbon steel connectors required to be corrosion-resistant shall be galvanized to at least the minimum standards in Table 9.20.16.1.

Editor's note

In the notes to Table-9.20.16.1., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.20.16.1. Minimum Requirements for Galvanizing Forming Part of Sentence 9.20.16.1.(1)

Column 1

Column 2

Column 3

Connector Material

ASTM Standard

Coating Class

Wire ties and continuous reinforcing (hot-dipped galvanizing)

A153 / A153M

Class B2 or 458 g/m²

Hardware and bolts

A153 / A153M

See A153 / A153M

Strip, plate, bars, and rolled sections (not less than 3.18 mm thick)

A123 / A123M

610 g/m²

Sheet (less than 3.18 mm thick)

A123 / A123M

305 g/m² on material 0.76 mm thick(1)

Notes to Table 9.20.16.1.:

(1)ASTM A123 / A123M does not apply to metal less than 3.18 mm thick. Galvanizing coatings may be interpolated for thicknesses between 3.18 mm and 0.76 mm.

9.20.17. — Above-Ground Flat Insulating Concrete Form Walls

Content not available for this version.

9.20.17.1. — Thickness of Flat Insulating Concrete Form Walls

(1) The thickness of concrete in flat insulating concrete form walls not in contact with the ground shall be,

(a) not less than 140 mm, and

(b) constant for the entire height of the wall.

Text · e-Laws consolidated snapshot

9.20.17.2. — Reinforcement for Flat Insulating Concrete Form Walls

(1) Horizontal reinforcement in above-grade flat insulating concrete form walls shall,

(a) consist of,

(i) one 10M bar placed not more than 300 mm from the top of the wall, and

(ii) 10M bars spaced not more than 600 mm o.c., and

(b) be placed in the middle third of the wall section.

(2) Vertical reinforcement in above-grade flat insulating concrete form walls shall,

(a) consist of 10M bars spaced not more than 400 mm o.c., and

(b) be placed in the middle third of the wall section.

(3) Vertical reinforcement required in Sentence (2) and interrupted by wall openings shall be placed not more than 600 mm from each side of the opening.

Text · e-Laws consolidated snapshot

9.20.17.3. — Openings in Flat Non-Loadbearing Insulating Concrete Form Walls

(1) No openings shall occur within 1 200 mm of interior and exterior corners of exterior non-loadbearing flat insulating concrete form walls.

(2) Portions of walls over openings in non-loadbearing flat insulating concrete form walls shall have a minimum depth of concrete of not less than 200 mm over the width of the opening.

(3) Openings more than 600 mm but not more than 3 000 mm in width in non-loadbearing flat insulating concrete form walls shall be reinforced at the top and bottom with one 10M bar.

(4) Openings more than 3 000 mm in width in non-loadbearing flat insulating concrete form walls shall be reinforced on all four sides with two 10M bar.

(5) Reinforcing bars described in Sentences (3) and (4) shall extend not less than 600 mm beyond the edges of the opening.

(6) The cumulative width of openings in non-loadbearing flat insulating concrete form walls shall be not more than 70% of the length of any wall.

Text · e-Laws consolidated snapshot

9.20.17.4. — Lintels over Openings in Loadbearing Flat Insulating Concrete Form Walls

(1) In loadbearing flat insulating concrete form walls, lintels shall be provided over all openings wider than 900 mm.

(2) Lintels described in Sentence (1) shall be constructed in accordance with Tables A-17, A-18 or A-19.

(3) Lintels described in Sentence (1) over openings wider than 1 200 mm shall be reinforced for shear with 10M stirrups at a maximum spacing of half the distance from the bottom reinforcing bar to the top of the lintel.

Editor's note

In the notes to Table-A-17, Table-A-18, Table-A-19, the footnote reference numbers differ only in presentation (superscript/inline rendering and separator spacing) from the e-Laws consolidation. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table A-17 Maximum Allowable Clear Spans for Lintels in Flat Loadbearing Insulating Concrete Form (ICF) Walls(1)(2)(3) (1-10M Bottom Bar) Forming Part of Sentence 9.20.17.4.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Minimum Lintel Thickness, mm

Minimum Lintel Depth, mm

Maximum Clear Span, m

Supporting Light-Frame Roof Only

Supporting ICF Second Storey and Light-Frame Roof

Maximum Ground Snow Load, kN/m2

1.50

3.33

1.50

3.33

140

200

1.41

1.18

1.03

0.93

300

1.78

1.50

1.30

1.18

400

2.08

1.75

1.53

1.38

500

2.33

1.97

1.72

1.56

600

2.55

2.16

1.89

1.71

150

200

1.41

1.18

1.02

0.92

300

1.78

1.50

1.29

1.17

400

2.08

1.75

1.51

1.37

500

2.33

1.97

1.70

1.54

600

2.54

2.15

1.87

1.70

160

200

1.41

1.18

1.01

0.91

300

1.78

1.50

1.28

1.16

400

2.07

1.75

1.50

1.36

500

2.32

1.96

1.68

1.53

600

2.53

2.15

1.85

1.68

190

200

1.41

1.19

0.98

0.89

300

1.78

1.50

1.24

1.13

400

2.06

1.74

1.45

1.32

500

2.30

1.95

1.63

1.49

600

2.51

2.13

1.78

1.63

200

200

1.41

1.19

0.97

0.89

300

1.77

1.49

1.23

1.12

400

2.06

1.74

1.43

1.31

500

2.30

1.95

1.61

1.48

600

2.50

2.13

1.77

1.62

240

200

1.41

1.19

0.94

0.86

300

1.76

1.49

1.18

1.09

400

2.04

1.73

1.38

1.27

500

2.27

1.93

1.55

1.43

600

2.47

2.11

1.70

1.56

Notes to Table A-17:

(1) Deflection criteria is L/240, where “L” is the clear span of the lintel.

(2) Linear interpolation is permitted between ground snow loads and between lintel depths.

(3) 10M stirrups are required at a maximum d/2 spacing for spans greater than 1 200 mm, where “d” is the distance from the top of the lintel to the level of the bottom reinforcing bar in the lintel.

Table A-18 Maximum Allowable Clear Spans for Lintels in Flat Loadbearing Insulating Concrete Form (ICF) Walls(1)(2)(3) (1-15M Bottom Bar) Forming Part of Sentence 9.20.17.4.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Minimum Lintel Thickness, mm

Minimum Lintel Depth, mm

Maximum Clear Span, m

Supporting Light-Frame Roof Only

Supporting ICF Second Storey and Light-Frame Roof

Maximum Ground Snow Load, kN/m2

1.50

3.33

1.50

3.33

140

200

1.63

1.46

1.31

1.23

300

2.43

2.08

1.81

1.64

400

2.90

2.44

2.13

1.93

500

3.26

2.75

2.41

2.18

600

3.58

3.03

2.65

2.40

150

200

1.67

1.49

1.33

1.25

300

2.48

2.08

1.79

1.62

400

2.90

2.44

2.11

1.91

500

3.26

2.75

2.38

2.16

600

3.57

3.02

2.62

2.38

160

200

1.70

1.53

1.35

1.26

300

2.48

2.08

1.78

1.61

400

2.90

2.44

2.09

1.90

500

3.25

2.75

2.36

2.14

600

3.56

3.02

2.59

2.36

190

200

1.80

1.61

1.36

1.24

300

2.48

2.09

1.73

1.58

400

2.89

2.44

2.03

1.85

500

3.23

2.74

2.29

2.09

600

3.53

3.00

2.51

2.30

200

200

1.83

1.64

1.35

1.23

300

2.48

2.09

1.71

1.57

400

2.88

2.44

2.01

1.84

500

3.22

2.74

2.26

2.07

600

3.52

2.99

2.48

2.28

240

200

1.93

1.65

1.30

1.20

300

2.47

2.08

1.66

1.52

400

2.86

2.43

2.94

1.78

500

3.19

2.72

2.18

2.01

600

3.47

2.97

2.39

2.20

Notes to Table A-18:

(1) Deflection criteria is L/240, where “L” is the clear span of the lintel.

(2) Linear interpolation is permitted between ground snow loads and between lintel depths.

(3) 10M stirrups are required at a maximum d/2 spacing for spans greater than 1 200 mm, where “d” is the distance from the top of the lintel to the level of the bottom reinforcing bar in the lintel.

Table A-19 Maximum Allowable Clear Spans for Lintels in Flat Loadbearing Insulating Concrete Form (ICF) Walls(1)(2)(3) (2-15M Bottom Bar) Forming Part of Sentence 9.20.17.4.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Minimum Lintel Thickness, mm

Minimum Lintel Depth, mm

Maximum Clear Span, m

Supporting Light-Frame Roof Only

Supporting ICF Second Storey and Light-Frame Roof

Maximum Ground Snow Load, kN/m2

1.50

3.33

1.50

3.33

140

200

1.63

1.46

1.31

1.23

300

2.43

2.18

1.96

1.84

400

3.22

2.90

2.60

2.42

500

4.00

3.60

3.25

2.70

600

4.71

4.20

3.61

2.97

150

200

1.67

1.49

1.33

1.25

300

2.48

2.23

1.99

1.87

400

3.29

2.96

2.64

2.45

500

4.80

3.68

3.29

2.74

600

4.87

4.20

3.64

3.02

160

200

1.70

1.53

1.35

1.27

300

2.53

2.28

2.02

1.90

400

3.36

3.02

2.68

2.48

500

4.16

3.76

3.27

2.78

600

4.95

4.20

3.61

3.08

190

200

1.80

1.61

1.39

1.32

300

2.67

2.40

2.09

1.97

400

3.53

3.19

2.77

2.56

500

4.38

3.81

3.18

2.90

600

4.92

4.19

3.50

3.21

200

200

1.83

1.64

1.41

1.33

300

2.87

2.44

2.11

2.00

400

3.78

3.24

2.79

2.55

500

4.46

3.81

3.15

2.89

600

4.86

4.18

3.47

3.18

240

200

2.07

1.74

1.46

1.38

300

3.07

2.59

2.18

2.07

400

3.95

3.38

2.70

2.48

500

4.40

3.80

3.04

2.80

600

4.78

4.16

3.34

3.08

Notes to Table A-19:

(1) Deflection criteria is L/240, where “L” is the clear span of the lintel.

(2) Linear interpolation is permitted between ground snow loads and between lintel depths.

(3) 10M stirrups are required at a maximum d/2 spacing for spans greater than 1 200 mm, where “d” is the distance from the top of the lintel to the level of the bottom reinforcing bar in the lintel.

9.20.17.5. — Framing Supported on Flat Insulating Concrete Form Walls

(1) Floor joists supported on the side of flat insulating concrete form walls shall be supported with joist hangers secured to wood ledger boards.

(2) The ledger boards described in Sentence (1) shall be not less than,

(a) 38 mm thick, and

(b) the depth of the floor joists.

(3) Anchor bolts shall be used to secure ledger boards to insulating concrete form walls and shall be,

(a) embedded in the wall to a depth not less than 100 mm, and

(b) spaced in accordance with Table 9.20.17.5.

(4) Floor joists and building frames supported on top of flat insulating concrete form walls shall be anchored in conformance with Article 9.23.6.1.

Text · e-Laws consolidated snapshot

Table 9.20.17.5. Maximum Anchor Bolt Spacing for the Connection of Ledger Boards to Flat Insulating Concrete Form Walls Forming Part of Sentence 9.20.17.5.(3)

Column 1

Column 2

Column 3

Maximum Clear Floor Span, m

Maximum Anchor Bolt Spacing, mm

Staggered 12.7 mm Diameter Anchor Bolts

Staggered 16 mm Diameter Anchor Bolts

2.44

450

500

3.00

400

450

4.00

300

400

5.00

275

325

9.20.17.6. — Anchoring of Roof Framing to Top of Flat Insulating Concrete Form Walls

(1) Roof framing supported on the top of flat insulating concrete form walls shall be fixed to the top plates, which shall be anchored to the wall with anchor bolts,

(a) not less than 12.7 mm in diameter, and

(b) spaced not more than 1 200 mm o.c.

(2) The anchor bolts described in Sentence (1) shall be placed in the centre of the insulating concrete form wall and shall be embedded not less than 100 mm into the concrete.

(3) Attachment of roof framing to wood top plates shall be in accordance with Table 9.23.3.4.

Text · e-Laws consolidated snapshot

9.20.17.7. — Protection from Precipitation and Damage

(1) Above ground flat insulating concrete form walls shall be protected from precipitation and damage in conformance with Section 9.27.

Text · e-Laws consolidated snapshot

9.21. — Masonry and Concrete Chimneys and Flues

Content not available for this version.

9.21.1. — General

Content not available for this version.

9.21.1.1. — Application

(1) This Section applies to,

(a) rectangular masonry or concrete chimneys not more than 12 m in height serving fireplaces or serving appliances having a combined total rated heat output of 120 kW or less, and

(b) flue pipes serving solid fuel-burning appliances.

(2) Chimneys and flue pipes other than those described in Sentence (1) shall conform to Section 6.3.

Text · e-Laws consolidated snapshot

9.21.1.2. — Factory-Built Chimneys

(1) Factory-built chimneys serving solid fuel-burning appliances, and their installation, shall conform to CAN/ULC-S629-M, “650°C Factory-Built Chimneys”.

Text · e-Laws consolidated snapshot

9.21.1.3. — Chimneys, Gas Vents or Flue Pipes

(1) Except as provided in Sentence (2), chimneys (other than those described in Sentences 9.21.1.1.(1) and 9.21.1.2.(1)), gas vents and flue pipes serving gas-, oil- or solid fuel-burning appliances and associated equipment shall conform to Section 6.3.

(2) Flue pipes serving solid fuel-burning stoves, ranges and space heaters shall conform to CAN/CSA-B365, “Installation Code for Solid-Fuel Burning Appliances and Equipment”.

Text · e-Laws consolidated snapshot

9.21.1.4. — Chimney or Flue Pipe Walls

(1) The walls of any chimney or flue pipe shall be constructed to be smoke- and flame-tight.

Text · e-Laws consolidated snapshot

9.21.2. — Chimney Flues

Content not available for this version.

9.21.2.1. — Chimney Flue Limitations

(1) A chimney flue that serves a fireplace or incinerator shall not serve any other appliance.

(2) A chimney flue that serves a solid fuel-burning appliance shall not be connected to a natural gas- or propane-fired appliance.

(3) A chimney flue that serves a solid-fuel burning appliance shall not be connected to an oil-burning appliance unless the solid-fuel burning appliance is listed for such installation and the installation of both appliances meets their respective installation requirements.

Text · e-Laws consolidated snapshot

9.21.2.2. — Connections of More Than One Appliance

(1) Except as required in Article 9.21.2.1.v1, two or more fuel-burning appliances are permitted to be connected to the same chimney flue provided adequate draft is maintained for the connected appliances and the connections are made as described in Sentences (2) and (3).

(2) Where 2 or more solid fuel-burning appliances are connected to the same chimney flue, the appliances must be located on the same storey.

(3) The connection referred to in Sentence (2) for a solid fuel-burning appliance shall be made below connections for appliances burning other fuels.

Text · e-Laws consolidated snapshot

9.21.2.3. — Inclined Chimney Flues

(1) Chimney flues shall not be inclined more than 45° to the vertical.

Text · e-Laws consolidated snapshot

9.21.2.4. — Size of Chimney Flues

(1) Except for chimneys serving fireplaces, the size of a chimney flue shall conform to the requirements of the solid fuel-burning appliance installation standard referenced in Sentence 6.2.1.4.(1) and Article 9.33.1.2.

(2) Where a chimney flue serves only one solid fuel-burning appliance, the flue area shall be at least equal to that of the flue pipe connected to it.

Text · e-Laws consolidated snapshot

9.21.2.5. — Fireplace Chimneys

(1) The size of a chimney flue serving a masonry fireplace shall be within the allowable range specified in Table 9.21.2.5.A. or Table 9.21.2.5.B.

Text · e-Laws consolidated snapshot

Table 9.21.2.5.A. Diameter of Round Flues for Fireplace Chimneys Forming Part of Sentence 9.21.2.5.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Fireplace Opening, m²

Chimney Height, m

3.0 to 4.5

> 4.5 to 5.9

> 5.9 to 8.9

> 8.9 to 12

Flue diameter, mm

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

Up to 0.150

110

170

100

160

90

150

90

150

0.151 to 0.250

150

210

130

190

130

190

120

180

0.251 to 0.350

180

240

160

220

150

210

140

200

0.351 to 0.500

220

280

200

260

190

250

170

230

0.501 to 0.650

260

320

230

290

220

280

200

260

0.651 to 0.800

290

350

260

320

240

300

220

280

0.801 to 1.00

330

390

290

350

270

330

250

310

1.01 to 1.20

360

420

320

380

300

360

270

330

1.21 to 1.40

390

450

350

410

330

390

300

360

1.41 to 1.60

420

480

380

440

350

410

320

380

1.61 to 1.80

400

460

370

430

340

400

1.81 to 2.00

400

460

360

420

2.01 to 2.20

380

440

Table 9.21.2.5.B. Rectangular Flue Sizes for Fireplace Chimneys Forming Part of Sentence 9.21.2.5.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Fireplace Opening, m²

Chimney Height, m

3.0 to 4.5

> 4.5 to 5.9

> 5.9 to 8.9

> 8.9 to 12

Flue Size, mm

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

Up to 0.150

200 × 200

200 × 200

100 × 200

100 × 200

100 × 200

100 × 200

100 × 200

100 × 200

0.151 to 0.250

200 × 200

200 × 200

200 × 200

200 × 200

200 × 200

200 × 200

200 × 200

200 × 200

0.251 to 0.350

200 × 300

200 × 300

200 × 200

200 × 300

200 × 200

200 × 200

200 × 200

200 × 200

0.351 to 0.500

300 × 300

300 × 300

200 × 300

200 × 300

200 × 300

200 × 300

200 × 200

200 × 300

0.501 to 0.650

300 × 300

300 × 400

300 × 300

300 × 300

300 × 300

300 × 300

200 × 300

200 × 300

0.651 to 0.800

300 × 400

300 × 400

300 × 300

300 × 400

300 × 300

300 × 300

300 × 300

300 × 300

0.801 to 1.00

400 × 400

400 × 400

300 × 400

300 × 400

300 × 400

300 × 400

300 × 300

300 × 300

1.01 to 1.20

400 × 400

400 × 400

400 × 400

400 × 400

300 × 400

300 × 400

300 × 400

300 × 400

1.21 to 1.40

400 × 400

400 × 400

400 × 400

400 × 400

300 × 400

300 × 400

1.41 to 1.60

400 × 400

400 × 400

400 × 400

400 × 400

1.61 to 1.80

400 × 400

400 × 400

1.81 to 2.00

400 × 400

400 × 400

9.21.2.6. — Oval Chimney Flues

(1) The width of an oval chimney flue shall be not less than two-thirds its breadth.

Text · e-Laws consolidated snapshot

9.21.3. — Chimney Lining

Content not available for this version.

9.21.3.1. — Lining Materials

(1) Every masonry or concrete chimney shall have a lining of clay, concrete, firebrick or metal.

Text · e-Laws consolidated snapshot

9.21.3.2. — Joints in Chimney Liners

(1) Joints of chimney liners shall be sealed to provide a barrier to the passage of flue gases and condensate into the cavity between the liner and the surrounding masonry.

(2) Joints of clay, concrete or firebrick chimney liners shall be struck flush to provide a straight, smooth, aligned chimney flue.

Text · e-Laws consolidated snapshot

9.21.3.3. — Clay Liners

(1) Clay liners shall conform to CAN/CSA-A324-M, “Clay Flue Liners”.

(2) Liners referred to in Sentence (1) shall be not less than 15.9 mm thick and shall be capable of resisting, without softening or cracking, a temperature of 1100°C.

Text · e-Laws consolidated snapshot

9.21.3.4. — Firebrick Liners

(1) Firebrick liners shall conform to ASTM C27, “Classification of Fireclay and High Alumina Refractory Brick”.

(2) Firebrick liners shall be laid with high temperature cement mortar conforming to CAN/CGSB-10.3, “Air Setting Refractory Mortar”.

Text · e-Laws consolidated snapshot

9.21.3.5. — Concrete Liners

(1) Concrete flue liners shall conform to Clause 4.2.6.4. of CAN/CSA-A405-M, “Design and Construction of Masonry Chimneys and Fireplaces”.

Text · e-Laws consolidated snapshot

9.21.3.6. — Metal Liners

(1) Metal liners shall be constructed of at least 0.3 mm thick stainless steel.

(2) Except as permitted in Sentence 9.22.10.2.(3), metal liners referred to in Sentence (1) shall only be used in chimneys serving gas- or oil-burning appliances.

Text · e-Laws consolidated snapshot

9.21.3.7. — Installation of Chimney Liners

(1) Chimney liners shall be installed when the surrounding masonry or concrete is placed.

Text · e-Laws consolidated snapshot

9.21.3.8. — Spaces Between Liners and Surrounding Masonry

(1) A space not less than 10 mm wide shall be left between a chimney liner and the surrounding masonry.

(2) The space required in Sentence (1) shall not be filled with mortar.

Text · e-Laws consolidated snapshot

9.21.3.9. — Mortar for Chimney Liners

(1) Chimney liners used in chimneys for solid fuel-burning appliances shall be laid in a full bed of,

(a) high temperature cement mortar conforming to CAN/CGSB-10.3, “Air Setting Refractory Mortar”, or

(b) mortar consisting of 1 part Portland cement to 3 parts sand by volume.

(2) Chimney liners used in chimneys for oil- or gas-burning appliances shall be laid in a full bed of mortar consisting of 1 part Portland cement to 3 parts sand by volume.

Text · e-Laws consolidated snapshot

9.21.3.10. — Extension of Chimney Liners

(1) Chimney liners shall extend from a point not less than 200 mm below the lowest flue pipe connection to a point not less than 50 mm or more than 100 mm above the chimney cap.

Text · e-Laws consolidated snapshot

9.21.4. — Masonry and Concrete Chimney Construction

Content not available for this version.

9.21.4.1. — Unit Masonry

(1) Unit masonry shall conform to Section 9.20.

Text · e-Laws consolidated snapshot

9.21.4.2. — Concrete

(1) Concrete shall conform to Section 9.3.

Text · e-Laws consolidated snapshot

9.21.4.3. — Footings

(1) Footings for masonry chimneys and concrete chimneys shall conform to the requirements in Section 9.15.

Text · e-Laws consolidated snapshot

9.21.4.4. — Height of Chimney Flues

(1) A chimney flue shall extend not less than,

(a) 900 mm above the highest point at which the chimney comes in contact with the roof, and

(b) 600 mm above the highest roof surface or structure within 3 m of the chimney.

Text · e-Laws consolidated snapshot

9.21.4.5. — Lateral Stability

(1) Except as provided in Sentence (2), chimneys shall be braced in accordance with Subsection 4.3.2. to provide stability under wind loads.

(2) A chimney need not be laterally braced provided,

(a) no horizontal outside dimension is less than 400 mm, and

(b) the chimney extends not more than 3.6 m above a roof or the masonry wall of which it forms a part.

Text · e-Laws consolidated snapshot

9.21.4.6. — Chimney Caps

(1) The top of a chimney shall have a waterproof cap of reinforced concrete, masonry or metal.

(2) The cap required in Sentence (1) shall slope from the lining and be provided with a drip not less than 25 mm from the chimney wall.

(3) Cast-in-place concrete caps shall be separated from the chimney liner by a bond break and be sealed at that location.

(4) Jointed precast concrete or masonry chimney caps shall have flashing installed beneath the cap extending from the liner to the drip edge.

Text · e-Laws consolidated snapshot

9.21.4.7. — Cleanout

(1) Except for a chimney flue constructed to serve a masonry fireplace, a cleanout opening with a metal frame and tight-fitting metal door shall be installed near the base of the chimney flue.

Text · e-Laws consolidated snapshot

9.21.4.8. — Wall Thickness

(1) The walls of a masonry chimney shall be built of solid units not less than 70 mm thick.

Text · e-Laws consolidated snapshot

9.21.4.9. — Separation of Flue Liners

(1) Flue liners in the same chimney shall be separated by not less than 70 mm of masonry or concrete exclusive of liners where clay liners are used, or 90 mm of firebrick where firebrick liners are used.

(2) Flue liners referred to in Sentence (1) shall be installed to prevent significant lateral movement.

Text · e-Laws consolidated snapshot

9.21.4.10. — Flashing

(1) Junctions with adjacent materials shall be adequately flashed to shed water.

Text · e-Laws consolidated snapshot

9.21.5. — Clearance from Combustible Construction

Content not available for this version.

9.21.5.1. — Clearance from Combustible Materials

(1) The clearance between masonry or concrete chimneys and combustible framing material shall be not less than,

(a) 50 mm for interior chimneys, and

(b) 12 mm for exterior chimneys.

(2) A clearance of not less than 150 mm shall be provided between a cleanout opening and combustible material.

(3) Combustible flooring, subflooring and ceiling finishes shall have not less than a 12 mm clearance from masonry or concrete chimneys.

Text · e-Laws consolidated snapshot

9.21.5.2. — Sealing of Spaces

(1) All spaces between masonry or concrete chimneys and combustible material shall be sealed top or bottom with noncombustible material.

Text · e-Laws consolidated snapshot

9.21.5.3. — Support of Joists or Beams

(1) Joists or beams may be supported on masonry walls that enclose chimney flues provided the combustible members are separated from the flue by a minimum of 290 mm of solid masonry.

Text · e-Laws consolidated snapshot

9.22. — Fireplaces

Content not available for this version.

9.22.1. — General

Content not available for this version.

9.22.1.1. — Application

(1) Except as otherwise specifically stated in this Part, this Section applies to masonry fireplaces constructed on site.

Text · e-Laws consolidated snapshot

9.22.1.2. — Masonry and Concrete

(1) Except as otherwise stated in this Section, unit masonry shall conform to Section 9.20. and concrete to Section 9.3.

(2) Masonry above openings shall be supported by steel lintels conforming to Sentence 9.20.5.2.(2)v1, reinforced concrete or a masonry arch.

Text · e-Laws consolidated snapshot

9.22.1.3. — Footings

(1) Footings for masonry and concrete fireplaces shall conform to Section 9.15.

Text · e-Laws consolidated snapshot

9.22.1.4. — Combustion Air

(1) Every solid fuel-fired fireplace, including a factory-built fireplace, shall have a supply of combustion air from outdoors in accordance with Sentences (2) to (7).

(2) The combustion air shall be supplied by a noncombustible and corrosion-resistant supply duct.

(3) The supply duct shall have,

(a) a diameter of not less than 100 mm or equivalent area, and

(b) an exterior intake for entry of air from the outdoors.

(4) The supply duct shall contain a tight-fitting damper that shall be located close to the interior outlet and be operable from the room containing the fireplace.

(5) The operating mechanism shall clearly indicate the actual position of the damper.

(6) The interior outlet shall,

(a) be located as close as possible to the opening in the face of the fireplace, and

(b) be designed to prevent embers from entering the supply duct.

(7) Where a supply of combustion air is provided directly to the fire chamber of a fireplace, including a factory-built fireplace or a steel fireplace liner, the installation shall comply with the “Outdoor Air Supply” requirements provided in CAN/CSA-A405-M, “Design and Construction of Masonry Chimneys and Fireplaces”.

Text · e-Laws consolidated snapshot

9.22.2. — Fireplace Liners

Content not available for this version.

9.22.2.1. — Brick or Steel Liners

(1) Except where a fireplace is equipped with a steel liner, every fireplace shall have a firebrick liner.

Text · e-Laws consolidated snapshot

9.22.2.2. — Firebrick Liners

(1) Fireplace liners shall be not less than,

(a) 50 mm thick for the sides and back, and

(b) 25 mm thick for the floor.

(2) Firebrick liners shall be laid with high temperature cement mortar conforming to CAN/CGSB- 10.3, “Air Setting Refractory Mortar”.

(3) Joints between a firebrick liner and the adjacent back-up masonry shall be offset.

Text · e-Laws consolidated snapshot

9.22.2.3. — Steel Liners

(1) Steel liners for fireplaces shall conform to CAN/ULC-S639M, “Steel Liner Assemblies for Solid-Fuel Burning Masonry Fireplaces”, and shall be installed in accordance with the installation instructions in that standard.

Text · e-Laws consolidated snapshot

9.22.3. — Fireplace Walls

Content not available for this version.

9.22.3.1. — Thickness of Walls

(1) Except as provided in Sentence (2), the thickness of the back and sides of a fireplace, including the thickness of any firebrick liner, shall consist of not less than 190 mm thick where a metal liner or a firebrick liner less than 51 mm is used.

(2) When a steel fireplace liner is used with an air circulating chamber surrounding the firebox, the back and sides of the fireplace shall consist of,

(a) solid masonry units not less than 90 mm thick, or

(b) hollow masonry units not less than 190 mm thick.

Text · e-Laws consolidated snapshot

9.22.4. — Fire Chamber

Content not available for this version.

9.22.4.1. — Fire Chamber Dimensions

(1) The distance from the back of the fire chamber to the plane of the fireplace opening shall be not less than 300 mm.

Text · e-Laws consolidated snapshot

9.22.5. — Hearth

Content not available for this version.

9.22.5.1. — Hearth Extension

(1) Except as required in Sentence (2), fireplaces shall have a noncombustible hearth extending not less than 400 mm in front of the fireplace opening measured from the facing, and not less than 200 mm beyond each side of the fireplace opening.

(2) Where the fire chamber floor is elevated more than 150 mm above the hearth, the dimension of the hearth measured perpendicular to the plane of the fireplace opening shall be increased by not less than,

(a) 50 mm for an elevation above 150 mm and not more than 300 mm, and

(b) an additional 25 mm for every 50 mm in elevation above 300 mm.

Text · e-Laws consolidated snapshot

9.22.5.2. — Support of Hearth

(1) Except as permitted in Sentence (2), the fire chamber floor and hearth shall be supported on a reinforced concrete slab not less than a 100 mm thick at its supports and, if cantilevered, not less than 50 mm thick at its unsupported edge.

(2) A hearth for a fireplace with an opening raised not less than 200 mm from a combustible floor is permitted to be supported on that floor provided the requirements of Clauses 5.3.6.5. to 5.3.6.7. of CAN/CSA-A405-M, “Design and Construction of Masonry Chimneys and Fireplaces”, are followed.

Text · e-Laws consolidated snapshot

9.22.6. — Damper

Content not available for this version.

9.22.6.1. — Required Damper and Size

(1) The throat of every fireplace shall be equipped with a metal damper sufficiently large to cover the full area of the throat opening.

Text · e-Laws consolidated snapshot

9.22.7. — Smoke Chamber

Content not available for this version.

9.22.7.1. — Slope of Smoke Chamber

(1) The sides of the smoke chamber connecting a fireplace throat with a flue shall not be sloped at an angle greater than 45° to the vertical.

Text · e-Laws consolidated snapshot

9.22.7.2. — Wall Thickness

(1) The thickness of masonry walls surrounding the smoke chamber shall be not less than 190 mm at the sides, front and back, except that the portions of the back exposed to the outside may be 140 mm thick.

Text · e-Laws consolidated snapshot

9.22.8. — Factory-Built Fireplaces

Content not available for this version.

9.22.8.1. — Conformance to Standard

(1) Factory-built fireplaces and their installation shall conform to CAN/ULC-S610-M, “Factory-Built Fireplaces”.

Text · e-Laws consolidated snapshot

9.22.9. — Clearance of Combustible Material

Content not available for this version.

9.22.9.1. — Clearance to the Fireplace Opening

(1) Combustible material shall not be placed on or near the face of a fireplace within 150 mm of the fireplace opening, except that where the combustible material projects more than 38 mm out from the face of the fireplace above the opening, such material shall be at least 300 mm above the top of the opening.

Text · e-Laws consolidated snapshot

9.22.9.2. — Metal Exposed to the Interior

(1) Metal exposed to the interior of a fireplace such as the damper control mechanism shall have at least a 50 mm clearance from any combustible material on the face of the fireplace where such metal penetrates through the face of the fireplace.

Text · e-Laws consolidated snapshot

9.22.9.3. — Clearance to Combustible Framing

(1) Not less than a 100 mm clearance shall be provided between the back and sides of a solid fuel burning fireplace and combustible framing, except that a 50 mm clearance is permitted where the fireplace is located in an exterior wall.

(2) Not less than a 50 mm clearance shall be provided between the back and sides of the smoke chamber of a solid fuel burning fireplace and combustible framing, except that a 25 mm clearance is permitted where the fireplace is located in an exterior wall.

Text · e-Laws consolidated snapshot

9.22.9.4. — Heat Circulating Duct Openings

(1) The clearance of combustible material above heat circulating duct openings from those openings shall be not less than,

(a) 300 mm where the combustible material projects more than 38 mm from the face, and

(b) 150 mm where the projection is less than 38 mm.

Text · e-Laws consolidated snapshot

9.22.10. — Fireplace Inserts and Hearth-Mounted Stoves

Content not available for this version.

9.22.10.1. — Installation Standard

(1) Fireplace inserts and hearth mounted stoves vented through the throat of a fireplace shall conform to ULC-S628, “Fireplace Inserts”.

Text · e-Laws consolidated snapshot

9.22.10.2. — Installation

(1) The installation of fireplace inserts and hearth mounted stoves vented through the throat of a fireplace shall conform to CAN/CSA-B365, “Installation Code for Solid-Fuel Burning Appliances and Equipment”.

(2) Fireplace inserts and hearth mounted stoves vented through the throat of a fireplace described in Sentence (1) may be installed in existing fireplaces only if a minimum thickness of 190 mm of solid masonry is provided between the smoke chamber and any existing combustible materials, unless the insert is listed for lesser clearances.

(3) A fireplace insert installed in a masonry fireplace shall have,

(a) a listed metal chimney liner installed from the insert collar to the top of the chimney, or

(b) a direct sealed connection to the chimney flue where such provision is part of an insert conforming to Sentence 9.22.10.1.(1)v1,

Text · e-Laws consolidated snapshot

9.23. — Wood-Frame Construction

Content not available for this version.

9.23.1. — Application

Content not available for this version.

9.23.1.1. — Limitations

(1) This Section applies where wall, floor and roof planes are generally comprised of lumber frames of small repetitive structural members, or engineered components, and where,

(a) roof and wall planes are clad, sheathed or braced on at least one side,

(b) the small repetitive structural members are spaced not more than 600 mm o.c.,

(c) the walls do not serve as foundations,

(d) the specified live load on supported subfloors and floor framing does not exceed 2.4 kPa, and

(e) the span of any structural member does not exceed 12.20 m.

(2) Where the conditions in Sentence (1) are exceeded for wood construction, the design of the framing and fastening shall conform to Subsection 4.3.1.

Text · e-Laws consolidated snapshot

9.23.2. — General

Content not available for this version.

9.23.2.1. — Strength and Rigidity

(1) All members shall be so framed, anchored, fastened, tied and braced to provide the necessary strength and rigidity.

Text · e-Laws consolidated snapshot

9.23.2.2. — Protection from Decay

(1) Ends of wood joists, beams and other members framing into masonry or concrete shall be treated to prevent decay where the bottom of the member is at or below ground level, or a 12 mm air space shall be provided at the end and sides of the member.

(2) Air spaces required in Sentence (1) shall not be blocked by insulation, vapour barriers or air tight materials.

Text · e-Laws consolidated snapshot

9.23.2.3. — Protection from Dampness

(1) Except as permitted in Sentence (2), wood framing members that are not pressure-treated with a wood preservative and that are supported on concrete in contact with the ground or fill shall be separated from the concrete by not less than 0.05 mm polyethylene film or Type S roll roofing.

(2) Dampproofing material referred to in Sentence (1) is not required where the wood member is at least 150 mm above the ground.

Text · e-Laws consolidated snapshot

9.23.2.4. — Lumber

(1) Lumber shall conform to the appropriate requirements in Subsection 9.3.2.

Text · e-Laws consolidated snapshot

9.23.2.5. — Termite Protection

(1) Where termites are known to exist, unless pressure-treated with a chemical that is toxic to such termites in accordance with Article 9.3.2.9.v1v2, wood steps shall rest on a non-cellulosic base or apron extending at least 150 mm above grade.

(2) Wood lattice or skirting around porches shall be separated from piers and soil by at least 50 mm.

Text · e-Laws consolidated snapshot

9.23.3. — Fasteners

Content not available for this version.

9.23.3.1. — Standards for Nails and Screws

(1) Unless otherwise indicated, nails specified in this Section shall be common steel wire nails or common spiral nails, conforming to CSA B111, “Wire Nails, Spikes and Staples”.

(2) Wood screws specified in this Section shall conform to ANSI/ASME B18.6.1., “Wood Screws (Inch Series)”.

Text · e-Laws consolidated snapshot

9.23.3.2. — Length of Nails

(1) All nails shall be long enough so that not less than half their required length penetrates into the second member.

Text · e-Laws consolidated snapshot

9.23.3.3. — Prevention of Splitting

(1) Splitting of wood members shall be minimized by staggering the nails in the direction of the grain and by keeping nails well in from the edges.

Text · e-Laws consolidated snapshot

9.23.3.4. — Nailing of Framing

(1) Except as provided in Sentence (2), nailing of framing shall conform to Table 9.23.3.4.

(2) Where the bottom wall plate or sole plate of an exterior wall is not nailed to joists or blocking in conformance with Table 9.23.3.4., the exterior wall may be fastened to the floor framing by,

(a) having plywood, OSB or waferboard sheathing extend down over floor framing and fastened to the floor framing by nails or staples conforming to Article 9.23.3.5., or

(b) tying the wall framing to the floor framing by 50 mm wide galvanized-metal strips,

(i) not less than 0.41 mm in thickness,

(ii) spaced not more than 1 200 mm apart, and

(iii) fastened at each end with at least two 63 mm nails.

Text · e-Laws consolidated snapshot

Table 9.23.3.4. Nailing for Framing Forming Part of Sentence 9.23.3.4.(1)

Column 1

Column 2

Column 3

Construction Detail

Minimum Length of Nails, mm

Minimum Number or Maximum Spacing of Nails

Floor joist to plate – toe nail

82

2

Wood or metal strapping to underside of floor joists

57

2

Cross bridging to joists

57

2 at each end

Double header or trimmer joists

76

300 mm (o.c.)

Floor joist to stud (balloon construction)

76

2

Ledger strip to wood beam

82

2 per joist

Joist to joist splice (See also Table 9.23.13.8.)

76

2 at each end

Header joist end nailed to joists along perimeter

101

3

Tail joist to adjacent header joist

82

5

(end nailed) around openings

101

3

Each header joist to adjacent trimmer joist

82

5

(end nailed) around openings

101

3

Stud to wall plate (each end) toe nail

62

4

or end nail

82

2

Doubled studs at openings, or studs at walls or wall intersections and corners

76

750 mm (o.c.)

Doubled top wall plates

76

600 mm (o.c.)

Bottom wall plate or sole plate to joists or blocking (exterior walls)(1)

82

400 mm (o.c.)

Interior walls to framing or subflooring

82

600 mm (o.c.)

Horizontal member over openings in non-loadbearing walls – each end

82

2

Lintels to studs

82

2 at each end

Ceiling joist to plate – toe nail each end

82

2

Roof rafter, roof truss or roof joist to plate – toe nail

82

3

Rafter plate to each ceiling joist

101

2

Rafter to joist (with ridge supported)

76

3

Rafter to joist (with ridge unsupported)

76

See Table 9.23.13.8.

Gusset plate to each rafter at peak

57

4

Rafter to ridge board – toe nail – end nail

82

3

Collar tie to rafter – each end

76

3

Collar tie lateral support to each collar tie

57

2

Jack rafter to hip or valley rafter

82

2

Roof strut to rafter

76

3

Roof strut to loadbearing wall – toe nail

82

2

38 mm × 140 mm or less plank decking to support

82

2

Plank decking wider than 38 mm × 140 mm to support

82

3

38 mm edge laid plank decking to support (toe nail)

76

1

38 mm edge laid plank to each other

76

450 mm (o.c.)

Notes to Table 9.23.3.4.:

(1) See Sentence 9.23.3.4.(2).

9.23.3.5. — Fastening for Sheathing or Subflooring

(1) Fastening of sheathing and subflooring shall conform to Table 9.23.3.5.

(2) Staples shall not be less than 1.6 mm in diameter or thickness, with not less than a 9.5 mm crown driven with the crown parallel to framing.

(3) Roofing nails for the attachment of fibreboard or gypsum sheathing shall not be less than 3.2 mm in diameter with a minimum head diameter of 11.1 mm.

(4) Flooring screws shall not be less than 3.2 mm in diameter.

Text · e-Laws consolidated snapshot

Table 9.23.3.5. Fasteners for Sheathing and Subflooring Forming Part of Sentence 9.23.3.5.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Element

Minimum Length of Fasteners, mm

Minimum Number or Maximum Spacing of Fasteners

Common or Spiral Nails

Ring Thread Nails or Screws

Roofing Nails

Staples

Board lumber 184 mm or less wide

51

45

N/A

51

2 per support

Board Lumber more than 184 mm wide

51

45

N/A

51

3 per support

Fibreboard sheathing up to 13 mm thick

N/A

N/A

44

28

150 mm (o.c.) along edges and 300 mm (o.c.) along intermediate supports

Gypsum sheathing up to 13 mm thick

N/A

N/A

44

N/A

Plywood, OSB or waferboard up to 10 mm thick

51

45

N/A

38

Plywood, OSB or waferboard from 10 mm to 20 mm thick

51

45

N/A

51

Plywood, OSB or waferboard over 20 mm thick

57

51

N/A

N/A

9.23.4. — Maximum Spans

Content not available for this version.

9.23.4.1. — Application

(1) Spans provided in this Subsection for joists, beams and lintels supporting floors shall apply only where,

(a) the floors serve residential areas as described in Table 4.1.5.3.v1, or

(b) the uniformly distributed live load on the floors do not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2) Spans for joists, beams and lintels supporting floors shall be determined according to Subsection 4.1.3. where the supported floors,

(a) serve other than residential areas, or

(b) support a uniform live load in excess of that specified for residential areas.

Text · e-Laws consolidated snapshot

9.23.4.2. — Spans for Joists, Rafters and Beams

(1) Except as required in Sentence (2) and Article 9.23.13.10., the spans for wood joists and rafters shall conform to the spans shown in Tables A-1 to A-7 for the uniform live loads shown in the Tables.

(2) Spans for floor joists that are not selected from Tables A-1 and A-2 and that are required to be designed for the same loading conditions, shall not exceed the design requirements for uniform loading and vibration criteria.

(3) Spans for built-up wood and glued-laminated timber floor beams shall conform to the spans in Tables A-8 to A-11.

(4) Spans for roof ridge beams shall conform to the spans in Table A-12 for the uniform snow load shown.

Editor's note

In the 'Maximum Spans for Floor Joists - Special Cases' table (Table A-2) under Article 9.23.4.2., the as-filed O. Reg. 350/06 contains several typographical anomalies that this map reproduces as filed: the Column 8 header cell is blank ('Col.'; it is Column 8 by position), one lumber-grade label reads 'No .1' with a misplaced space, and another reads 'No 3' with the period omitted. In the table notes, the '(1)' and '(2)' reference markers appear as plain text. The consolidated e-Laws version silently supplies the missing characters, superscripts the note markers, and bolds the notes heading; none of these changes was enacted by an amending regulation.

Text · e-Laws consolidated snapshot

Table A-1 Maximum Spans for Floor Joists – General Cases(1) Forming Part of Sentence 9.23.4.2.(1)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Joist Size, mm

Maximum Span, m

With Strapping(2)

With Bridging

With Strapping(2) and Bridging

Joist Spacing, mm

Joist Spacing, mm

Joist Spacing, mm

300

400

600

300

400

600

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

38 × 89

2.13

1.97

1.73

2.19

1.99

1.73

2.19

1.99

1.73

Structural

38 × 140

3.23

3.07

2.73

3.44

3.12

2.73

3.44

3.12

2.73

38 × 184

3.88

3.69

3.51

4.18

3.92

3.59

4.37

4.07

3.59

38 × 235

4.57

4.34

4.13

4.86

4.57

4.29

5.05

4.70

4.39

38 × 286

5.21

4.95

4.71

5.49

5.16

4.85

5.66

5.28

4.92

No. 1

38 × 89

2.00

1.85

1.66

2.09

1.90

1.66

2.09

1.90

1.66

and No. 2

38 × 140

3.09

2.91

2.62

3.29

2.99

2.62

3.29

2.99

2.62

38 × 184

3.71

3.53

3.36

4.00

3.76

3.44

4.19

3.90

3.44

38 × 235

4.38

4.16

3.96

4.66

4.38

4.11

4.84

4.51

4.20

38 × 286

4.99

4.75

4.52

5.26

4.94

4.65

5.43

5.06

4.72

No. 3

38 × 89

1.90

1.69

1.38

1.95

1.69

1.38

1.95

1.69

1.38

38 × 140

2.78

2.41

1.97

2.78

2.41

1.97

2.78

2.41

1.97

38 × 184

3.38

2.93

2.39

3.38

2.93

2.39

3.38

2.93

2.39

38 × 235

4.14

3.58

2.93

4.14

3.58

2.93

4.14

3.58

2.93

38 × 286

4.80

4.16

3.39

4.80

4.16

3.39

4.80

4.16

3.39

Construction

38 × 89

1.90

1.77

1.61

2.03

1.84

1.61

2.03

1.84

1.61

Standard

38 × 89

1.81

1.63

1.33

1.88

1.63

1.33

1.88

1.63

1.33

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

38 × 89

2.08

1.93

1.71

2.16

1.96

1.71

2.16

1.96

1.71

Structural

38 × 140

3.18

3.03

2.69

3.39

3.08

2.69

3.39

3.08

2.69

38 × 184

3.82

3.64

3.46

4.12

3.87

3.54

4.31

4.02

3.54

38 × 235

4.50

4.28

4.08

4.80

4.51

4.23

4.98

4.64

4.33

38 × 286

5.14

4.89

4.65

5.42

5.09

4.78

5.59

5.21

4.86

No. 1 and

38 × 89

2.00

1.85

1.66

2.09

1.90

1.66

2.09

1.90

1.66

No. 2

38 × 140

3.09

2.91

2.62

3.29

2.99

2.62

3.29

2.99

2.62

38 × 184

3.71

3.53

3.36

4.00

3.76

3.44

4.19

3.90

3.44

38 × 235

4.38

4.16

3.96

4.66

4.38

4.11

4.84

4.51

4.20

38 × 286

4.99

4.75

4.52

5.26

4.94

4.65

5.43

5.06

4.72

No. 3

38 × 89

1.90

1.77

1.61

2.03

1.84

1.61

2.03

1.84

1.61

38 × 140

2.99

2.78

2.43

3.19

2.90

2.43

3.19

2.90

2.43

38 × 184

3.60

3.42

2.95

3.88

3.61

2.95

4.06

3.61

2.95

38 × 235

4.24

4.03

3.61

4.51

4.24

3.61

4.68

4.37

3.61

38 × 286

4.84

4.60

4.19

5.10

4.79

4.19

5.26

4.90

4.19

Construction

38 × 89

1.90

1.77

1.61

2.03

1.84

1.61

2.03

1.84

1.61

Standard

38 × 89

1.81

1.68

1.39

1.96

1.71

1.39

1.96

1.71

1.39

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

1.95

1.81

1.64

2.06

1.87

1.64

2.06

1.87

1.64

Structural

38 × 140

3.05

2.85

2.57

3.24

2.95

2.57

3.24

2.95

2.57

38 × 184

3.66

3.48

3.31

3.94

3.70

3.38

4.12

3.84

3.38

38 × 235

4.31

4.10

3.90

4.59

4.31

4.05

4.76

4.44

4.14

38 × 286

4.91

4.67

4.45

5.18

4.87

4.57

5.34

4.98

4.64

No. 1 and

38 × 89

1.86

1.72

1.58

1.99

1.81

1.58

1.99

1.81

1.58

No. 2

38 × 140

2.92

2.71

2.49

3.14

2.85

2.49

3.14

2.85

2.49

38 × 184

3.54

3.36

3.20

3.81

3.58

3.27

3.99

3.72

3.27

38 × 235

4.17

3.96

3.77

4.44

4.17

3.92

4.60

4.29

4.00

38 × 286

4.75

4.52

4.30

5.01

4.71

4.42

5.17

4.82

4.49

No. 3

38 × 89

1.81

1.68

1.55

1.96

1.78

1.55

1.96

1.78

1.55

38 × 140

2.84

2.64

2.43

3.08

2.80

2.43

3.08

2.80

2.43

38 × 184

3.47

3.30

2.95

3.74

3.52

2.95

3.92

3.61

2.95

38 × 235

4.09

3.89

3.61

4.36

4.09

3.61

4.52

4.22

3.61

38 × 286

4.67

4.44

4.19

4.92

4.62

4.19

5.08

4.73

4.19

Construction

38 × 89

1.81

1.68

1.55

1.96

1.78

1.55

1.96

1.78

1.55

Standard

38 × 89

1.70

1.58

1.44

1.88

1.71

1.44

1.88

1.71

1.44

Northern Species (includes any Canadian Species covered by the NLGA Standard Grading Rules

Select

38 × 89

1.65

1.53

1.42

1.84

1.68

1.46

1.84

1.68

1.46

Structural

38 × 140

2.59

2.41

2.24

2.90

2.63

2.30

2.90

2.63

2.30

38 × 184

3.27

3.11

2.94

3.52

3.31

3.03

3.69

3.44

3.03

38 × 235

3.85

3.66

3.48

4.10

3.85

3.62

4.26

3.97

3.70

38 × 286

4.39

4.18

3.97

4.63

4.35

4.09

4.78

4.45

4.15

No. 1 and

38 × 89

1.59

1.48

1.37

1.80

1.64

1.43

1.80

1.64

1.43

No. 2

38 × 140

2.51

2.33

2.16

2.83

2.57

2.25

2.83

2.57

2.25

38 × 184

3.19

3.04

2.84

3.44

3.23

2.96

3.60

3.36

2.96

38 × 235

3.76

3.58

3.41

4.01

3.77

3.54

4.16

3.88

3.62

38 × 286

4.29

4.08

3.88

4.53

4.25

4.00

4.67

4.35

4.06

No. 3

38 × 89

1.54

1.43

1.32

1.74

1.57

1.36

1.76

1.60

1.36

38 × 140

2.42

2.24

1.94

2.74

2.38

1.94

2.75

2.38

1.94

38 × 184

3.12

2.90

2.37

3.35

2.90

2.37

3.35

2.90

2.37

38 × 235

3.67

3.49

2.89

3.91

3.54

2.89

4.06

3.54

2.89

38 × 286

4.19

3.98

3.36

4.42

4.11

3.36

4.55

4.11

3.36

Construction

38 × 89

1.54

1.43

1.32

1.74

1.57

1.40

1.76

1.60

1.40

Standard

38 × 89

1.48

1.37

1.15

1.63

1.41

1.15

1.63

1.41

1.15

Notes to Table A-1:

(1) Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floor does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2) See Sentence 9.23.9.4.(5) for alternatives to strapping.

Table A-2 Maximum Spans for Floor Joists – Special Cases(1) Forming Part of Sentence 9.23.4.2.(1) and 9.23.4.4.(2)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col.

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Joist Size, mm

Maximum Span, m

Joists with Ceilings Attached to Wood Furring

Joists with Concrete Topping

Without Bridging

With Bridging

With or Without Bridging(2)

Joist Spacing, mm

Joist Spacing, mm

Joist Spacing, mm

300

400

600

300

400

600

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

38 × 89

2.19

1.99

1.73

2.19

1.99

1.73

2.19

1.99

1.73

Structural

38 × 140

3.44

3.12

2.73

3.44

3.12

2.73

3.44

3.12

2.73

38 × 184

4.24

3.99

3.59

4.52

4.11

3.59

4.52

4.11

3.59

38 × 235

4.98

4.69

4.29

5.47

5.20

4.58

5.77

5.24

4.58

38 × 286

5.67

5.34

4.88

6.19

5.89

5.54

6.83

6.37

5.58

No. 1 and

38 × 89

2.09

1.90

1.66

2.09

1.90

1.66

2.09

1.90

1.66

No. 2

38 × 140

3.29

2.99

2.62

3.29

2.99

2.62

3.29

2.99

2.55

38 × 184

4.06

3.83

3.44

4.33

3.93

3.44

4.33

3.81

3.11

38 × 235

4.78

4.50

4.11

5.24

4.98

4.31

5.37

4.65

3.80

38 × 286

5.44

5.12

4.68

5.93

5.64

5.00

6.24

5.40

4.41

No. 3

38 × 89

1.95

1.69

1.38

1.95

1.69

1.38

1.72

1.49

1.21

38 × 140

2.78

2.41

1.97

2.78

2.41

1.97

2.45

2.12

1.73

38 × 184

3.38

2.93

2.39

3.38

2.93

2.39

2.98

2.58

2.11

38 × 235

4.14

3.58

2.93

4.14

3.58

2.93

3.65

3.16

2.58

38 × 286

4.80

4.16

3.39

4.80

4.16

3.39

4.23

3.66

2.99

Construction

38 × 89

2.03

1.84

1.61

2.03

1.84

1.61

2.03

1.84

1.61

Standard

38 × 89

1.88

1.63

1.33

1.88

1.63

1.33

1.66

1.44

1.17

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

38 × 89

2.16

1.96

1.71

2.16

1.96

1.71

2.16

1.96

1.71

Structural

38 × 140

3.39

3.08

2.69

3.39

3.08

2.69

3.39

3.08

2.69

38 × 184

4.18

3.94

3.54

4.46

4.05

3.54

4.46

4.05

3.54

38 × 235

4.92

4.63

4.23

5.39

5.13

4.52

5.69

5.17

4.52

38 × 286

5.60

5.27

4.82

6.10

5.81

5.47

6.74

6.28

5.50

No .1 and

38 × 89

2.09

1.90

1.66

2.09

1.90

1.66

2.09

1.90

1.66

No. 2

38 × 140

3.29

2.99

2.62

3.29

2.99

2.62

3.29

2.99

2.62

38 × 184

4.06

3.83

3.44

4.33

3.93

3.44

4.33

3.93

3.26

38 × 235

4.78

4.50

4.11

5.24

4.98

4.39

5.53

4.88

3.99

38 × 286

5.44

5.12

4.68

5.93

5.64

5.25

6.54

5.66

4.63

No 3

38 × 89

2.03

1.84

1.61

2.03

1.84

1.61

2.03

1.83

1.50

38 × 140

3.19

2.90

2.43

3.19

2.90

2.43

3.02

2.62

2.14

38 × 184

3.94

3.61

2.95

4.17

3.61

2.95

3.68

3.18

2.60

38 × 235

4.63

4.36

3.61

5.08

4.42

3.61

4.50

3.89

3.18

38 × 286

5.27

4.96

4.19

5.74

5.13

4.19

5.22

4.52

3.69

Construction

38 × 89

2.03

1.84

1.61

2.03

1.84

1.61

2.03

1.84

1.61

Standard

38 × 89

1.96

1.71

1.39

1.96

1.71

1.39

1.74

1.50

1.23

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

2.06

1.87

1.64

2.06

1.87

1.64

2.06

1.87

1.64

Structural

38 × 140

3.24

2.95

2.57

3.24

2.95

2.57

3.24

2.95

2.57

38 × 184

4.00

3.77

3.38

4.26

3.87

3.38

4.26

3.87

3.38

38 × 235

4 70

4.43

4.05

5.16

4.91

4.32

5.45

4.95

4.32

38 × 286

5.35

5.04

4.61

5.84

5.55

5.23

6.45

6.01

5.26

No. 1 and

38 × 89

1.99

1.81

1.58

1.99

1.81

1.58

1.99

1.81

1.58

No. 2

38 × 140

3.14

2.85

2.49

3.14

2.85

2.49

3.14

2.85

2.49

38 × 184

3.87

3.64

3.27

4.12

3.75

3.27

4.12

3.75

3.27

38 × 235

4.55

4.28

3.91

4.99

4.75

4.18

5.27

4.79

4.13

38 × 286

5.18

4.88

4.46

5.65

5.37

5.06

6.23

5.81

4.79

No. 3

38 × 89

1.96

1.78

1.55

1.96

1.78

1.55

1.96

1.78

1.50

38 × 140

3.08

2.80

2.43

3.08

2.80

2.43

3.02

2.62

2.14

38 × 184

3.80

3.58

2.95

4.05

3.61

2.95

3.68

3.18

2.60

38 × 235

4.47

4.21

3.61

4.90

4.42

3.61

4.50

3.89

3.18

38 × 286

5.09

4.79

4.19

5.55

5.13

4.19

5.22

4.52

3.69

Construction

38 × 89

1.96

1.78

1.55

1.96

1.78

1.55

1.96

1.78

1.55

Standard

38 × 89

1.88

1.71

1.44

1.88

1.71

1.44

1.80

1.56

1.27

Northern Species (includes any Canadian Species covered by the NLGA Standard Grading Rules

Select

38 × 89

1.84

1.68

1.46

1.84

1.68

1.46

1.84

1.68

1.46

Structural

38 × 140

2.90

2.63

2.30

2.90

2.63

2.30

2.90

2.63

2.30

38 × 184

3.58

3.37

3.03

3.81

3.46

3.03

3.81

3.46

3.03

38 × 235

4.20

3.96

3.62

4.61

4.39

3.86

4.87

4.42

3.86

38 × 286

4.79

4.51

4.12

5.22

4.96

4.68

5.76

5.37

4.54

No. 1 and

38 × 89

1.80

1.64

1.43

1.80

1.64

1.43

1.80

1.64

1.43

No. 2

38 × 140

2.83

2.57

2.25

2.83

2.57

2.25

2.83

2.57

2.23

38 × 184

3.50

3.29

2.96

3.72

3.38

2.96

3.72

3.32

2.71

38 × 235

4.11

3.87

3.54

4.51

4.29

3.76

4.69

4.06

3.31

38 × 286

4.68

4.40

4.03

5.10

4.85

4.36

5.44

4.71

3.84

No. 3

38 × 89

1.76

1.60

1.36

1.76

1.60

1.36

1.70

1.47

1.20

38 × 140

2.75

2.38

1.94

2.75

2.38

1.94

2.42

2.10

1.71

38 × 184

3.35

2.90

2.37

3.35

2.90

2.37

2.95

2.55

2.08

38 × 235

4.01

3.54

2.89

4.09

3.54

2.89

3.61

3.12

2.55

38 × 286

4.56

4.11

3.36

4.75

4.11

3.36

4.18

3.62

2.96

Construction

38 × 89

1.76

1.60

1.40

1.76

1.60

1.40

1.76

1.60

1.37

Standard

38 × 89

1.63

1.41

1.15

1.63

1.41

1.15

1.44

1.25

1.02

Notes to Table A-2:

(1)Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floor does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2)No bridging is assumed for spans for floor joists with concrete topping.

Table A-3 Maximum Spans for Ceiling Joists – Attic not Accessible by a Stairway Forming Part of Sentence 9.23.4.2.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Commercial Designation

Grade

Joist Size, mm

Maximum Span, m

Joist Spacing, mm

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select Structural

38 × 89

3.4

3.10

2.71

38 × 140

5.37

4.88

4.26

38 × 184

7.05

6.41

5.60

38 × 235

9.01

8.18

7.15

38 × 286

10.96

9.96

8.70

No. 1 and No. 2

38 × 89

3.27

2.97

2.59

38 × 140

5.14

4.67

4.08

38 × 184

6.76

6.14

5.36

38 × 235

8.63

7.84

6.85

38 × 286

10.50

9.54

8.34

No. 3

38 × 89

3.17

2.88

2.42

38 × 140

4.89

4.23

3.46

38 × 184

5.95

5.15

4.20

38 × 235

7.27

6.30

5.14

38 × 286

8.44

7.31

5.97

Construction

38 × 89

3.17

2.88

2.51

Standard

38 × 89

3.06

2.78

2.34

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select Structural

38 × 89

3.36

3.06

2.67

38 × 140

5.29

4.81

4.20

38 × 184

6.96

6.32

5.52

38 × 235

8.88

8.07

7.05

38 × 286

10.81

9.82

8.58

No. 1 and No. 2

38 × 89

3.27

2.97

2.59

38 × 140

5.14

4.67

4.08

38 × 184

6.76

6.14

5.36

38 × 235

8.63

7.84

6.85

38 × 286

10.50

9.54

8.34

No. 3

38 × 89

3.17

2.88

2.51

38 × 140

4.98

4.53

3.95

38 × 184

6.55

5.95

5.19

38 × 235

8.36

7.60

6.34

38 × 286

10.18

9.01

7.36

Construction

38 × 89

3.17

2.88

2.50

Standard

38 × 89

3.06

2.78

2.43

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select Structural

38 × 89

3.22

2.92

2.55

38 × 140

5.06

4.60

4.02

38 × 184

6.65

6.05

5.28

38 × 235

8.50

7.72

6.74

38 × 286

10.34

9.40

8.21

No. 1 and No. 2

38 × 89

3.11

2.83

2.47

38 × 140

4.90

4.45

3.89

38 × 184

6.44

5.85

5.11

38 × 235

8.22

7.47

6.52

38 × 286

10.00

9.09

7.94

No. 3

38 × 89

3.06

2.78

2.43

38 × 140

4.81

4.37

3.82

38 × 184

6.32

5.74

5.02

38 × 235

8.07

7.33

6.34

38 × 286

9.82

8.93

7.36

Construction

38 × 89

3.06

2.78

2.43

Standard

38 × 89

2.94

2.67

2.33

Northern Species (includes any Canadian Species covered by the NLGA Standard Grading Rules

Select Structural

38 × 89

2.88

2.61

2.28

38 × 140

4.53

4.11

3.59

38 × 184

5.95

5.40

4.72

38 × 235

7.60

6.90

6.03

38 × 286

9.25

8.40

7.34

No. 1 and No. 2

38 × 89

2.81

2.55

2.23

38 × 140

4.42

4.02

3.51

38 × 184

5.81

5.28

4.61

38 × 235

7.42

6.74

5.89

38 × 286

9.03

8.21

7.17

No. 3

38 × 89

2.74

2.49

2.18

38 × 140

4.31

3.92

3.42

38 × 184

5.67

5.09

4.16

38 × 235

7.19

6.23

5.08

38 × 286

8.34

7.23

5.90

Construction

38 × 89

2.74

2.49

2.18

Standard

38 × 89

2.67

2.43

2.03

Table A-4 Maximum Spans for Roof Joists – Specified Roof Snow Loads 1.0 to 2.0 kPa Forming Part of Sentence 9.23.4.2.(1)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Joist Size, mm

Maximum Span, m

Specified Snow Load, kPa

1.0

1.5

2.0

Joist Spacing, mm

Joist Spacing, mm

Joist Spacing, mm

300

400

600

300

400

600

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

38 × 89

2.71

2.46

2.15

2.37

2.15

1.88

2.15

1.95

1.71

Structural

38 × 140

4.26

3.87

3.38

3.72

3.38

2.95

3.38

3.07

2.68

38 × 184

5.60

5.09

4.44

4.89

4.44

3.88

4.44

4.04

3.53

38 × 235

7.15

6.49

5.67

6.24

5.67

4.96

5.67

5.15

4.50

38 × 286

8.70

7.90

6.91

7.60

6.91

6.03

6.91

6.27

5.48

No. 1 and

38 × 89

2.59

2.36

2.06

2.27

2.06

1.80

2.06

1.87

1.63

No. 2

38 × 140

4.08

3.71

3.24

3.57

3.24

2.83

3.24

2.94

2.57

38 × 184

5.36

4.87

4.26

4.69

4.26

3.72

4.26

3.87

3.38

38 × 235

6.85

6.22

5.44

5.98

5.44

4.74

5.44

4.94

4.22

38 × 286

8.34

7.57

6.40

7.28

6.62

5.50

6.62

6.00

4.90

No. 3

38 × 89

2.49

2.16

1.76

2.14

1.85

1.51

1.91

1.65

1.35

38 × 140

3.56

3.08

2.51

3.06

2.65

2.16

2.72

2.36

1.92

38 × 184

4.33

3.75

3.06

3.72

3.22

2.63

3.31

2.87

2.34

38 × 235

5.29

4.58

3.74

4.55

3.94

3.22

4.05

3.51

2.86

38 × 286

6.14

5.32

4.34

5.28

4.57

3.73

4.70

4.07

3.32

Construction

38 × 89

2.51

2.28

1.99

2.20

1.99

1.74

1.99

1.81

1.58

Standard

38 × 89

2.41

2.08

1.70

2.07

1.79

1.46

1.84

1.60

1.30

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

38 × 89

2.67

2.43

2.12

2.33

2.12

1.85

2.12

1.93

1.68

Structural

38 × 140

4.20

3.82

3.33

3.67

3.33

2.91

3.33

3.03

2.65

38 × 184

5.52

5.02

4.38

4.82

4.38

3.83

4.38

3.98

3.48

38 × 235

7.05

6.41

5.60

6.16

5.60

4.89

5.60

5.09

4.44

38 × 286

8.58

7.80

6.81

7.50

6.81

5.95

6.81

6.19

5.41

No. 1 and

38 × 89

2.59

2.36

2.06

2.27

2.06

1.80

2.06

1.87

1.63

No. 2

38 × 140

4.08

3.71

3.24

3.57

3.24

2.83

3.24

2.94

2.57

38 × 184

5.36

4.87

4.26

4.69

4.26

3.72

4.26

3.87

3.38

38 × 235

6.85

6.22

5.44

5.98

5.44

4.75

5.44

4.94

4.32

38 × 286

8.34

7.57

6.62

7.28

6.62

5.77

6.62

6.01

5.25

No. 3

38 × 89

2.51

2.28

1.99

2.20

1.99

1.74

1.99

1.81

1.58

38 × 140

3.95

3.59

3.10

3.45

3.14

2.67

3.14

2.85

2.37

38 × 184

5.20

4.62

3.77

4.54

3.97

3.24

4.09

3.54

2.89

38 × 235

6.53

5.65

4.61

5.61

4.86

3.97

5.00

4.33

3.53

38 × 286

7.57

6.56

5.35

6.51

5.64

4.60

5.80

5.02

4.10

Construction

38 × 89

2.51

2.28

1.99

2.20

1.99

1.74

1.99

1.81

1.58

Standard

38 × 89

2.43

2.18

1.78

2.12

1.88

1.53

1.93

1.67

1.36

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

2.55

2.32

2.03

2.23

2.03

1.77

2.03

1.84

1.61

Structural

38 × 140

4.02

3.65

3.19

3.51

3.19

2.79

3.19

2.90

2.53

38 × 184

5.28

4.80

4.19

4.61

4.19

3.66

4.19

3.81

3.33

38 × 235

6.74

6.13

5.35

5.89

5.35

4.68

5.35

4.86

4.25

38 × 286

8.21

7.46

6.52

7.17

6.52

5.69

6.52

5.92

5.17

No. 1 and

38 × 89

2.47

2.24

1.96

2.16

1.96

1.71

1.96

1.78

1.56

No. 2

38 × 140

3.89

3.53

3.08

3.40

3.08

2.69

3.08

2.80

2.45

38 × 184

5.11

4.64

4.05

4.46

4.05

3.54

4.05

3.68

3.22

38 × 235

6.52

5.93

5.18

5.70

5.18

4.52

5.18

4.70

4.11

38 × 286

7.94

7.21

6.30

6.94

6.30

5.50

6.30

5.73

5.00

No. 3

38 × 89

2.43

2.20

1.93

2.12

1.93

1.68

1.93

1.75

1.53

38 × 140

3.82

3.47

3.03

3.33

3.03

2.65

3.03

2.75

2.37

38 × 184

5.02

4.56

3.77

4.38

3.97

3.24

3.98

3.54

2.89

38 × 235

6.41

5.65

4.61

5.60

4.86

3.97

5.00

4.33

3.53

38 × 286

7.57

6.56

5.35

6.51

5.64

4.60

5.80

5.02

4.10

Construction

38 × 89

2.43

2.20

1.93

2.12

1.93

1.68

1.93

1.75

1.53

Standard

38 × 89

2.33

2.12

1.85

2.04

1.85

1.59

1.85

1.68

1.41

Northern Species (includes any Canadian Species covered by the NLGA Standard Grading Rules

Select

38 × 89

2.28

2.07

1.81

1.99

1.81

1.58

1.81

1.65

1.44

Structural

38 × 140

3.59

3.26

2.85

3.14

2.85

2.49

2.85

2.59

2.26

38 × 184

4.72

4.29

3.75

4.12

3.75

3.27

3.75

3.40

2.97

38 × 235

6.03

5.48

4.79

5.27

4.79

4.18

4.79

4.35

3.80

38 × 286

7.34

6.67

5.82

6.41

5.82

5.09

5.82

5.29

4.62

No. 1 and

38 × 89

2.23

2.03

1.77

1.95

1.77

1.55

1.77

1.61

1.41

No. 2

38 × 140

3.51

3.19

2.79

3.07

2.79

2.43

2.79

2.53

2.21

38 × 184

4.61

4.19

3.66

4.03

3.66

3.20

3.66

3.33

2.91

38 × 235

5.89

5.35

4.68

5.15

4.68

4.09

4.68

4.25

3.68

38 × 286

7.17

6.52

5.58

6.26

5.69

4.80

5.69

5.17

4.27

No. 3

38 × 89

2.18

1.98

1.73

1.90

1.73

1.50

1.73

1.57

1.33

38 × 140

3.42

3.05

2.49

2.99

2.62

2.14

2.69

2.33

1.90

38 × 184

4.28

3.71

3.03

3.68

3.19

2.60

3.28

2.84

2.32

38 × 235

5.23

4.53

3.70

4.50

3.90

3.18

4.01

3.47

2.83

38 × 286

6.07

5.26

4.29

5.22

4.52

3.69

4.65

4.03

3.29

Construction

38 × 89

2.18

1.98

1.73

1.90

1.73

1.51

1.73

1.57

1.37

Standard

38 × 89

2.09

1.81

1.48

1.80

1.56

1.27

1.60

1.38

1.13

Table A-5 Maximum Spans for Roof Joists – Specified Roof Snow Loads 2.5 and 3.0 kPa Forming Part of Sentence 9.23.4.2.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Commercial Designation

Grade

Joist Size, mm

Maximum Span, m

Specified Snow Load, kPa

2.5

3.0

Joist Spacing, mm

Joist Spacing, mm

300

400

600

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

38 × 89

1.99

1.81

1.58

1.88

1.71

1.49

Structural

38 × 140

3.14

2.85

2.49

2.95

2.68

2.34

38 × 184

4.12

3.75

3.27

3.88

3.53

3.08

38 × 235

5.27

4.79

4.18

4.96

4.50

3.93

38 × 286

6.41

5.82

5.09

6.03

5.48

4.79

No. 1 and

38 × 89

1.91

1.74

1.52

1.80

1.63

1.43

No. 2

38 × 140

3.01

2.73

2.39

2.83

2.57

2.25

38 × 184

3.95

3.59

3.14

3.72

3.38

2.90

38 × 235

5.05

4.59

3.84

4.75

4.32

3.55

38 × 286

6.14

5.46

4.46

5.78

5.05

4.12

No. 3

38 × 89

1.74

1.50

1.23

1.60

1.39

1.13

38 × 140

2.48

2.15

1.75

2.29

1.98

1.62

38 × 184

3.01

2.61

2.13

2.79

2.41

1.97

38 × 235

3.69

3.19

2.61

3.41

2.95

2.41

38 × 286

4.28

3.70

3.03

3.95

3.42

2.79

Construction

38 × 89

1.85

1.68

1.47

1.74

1.58

1.38

Standard

38 × 89

1.68

1.45

1.19

1.55

1.34

1.10

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

38 × 89

1.97

1.79

1.56

1.85

1.68

1.47

Structural

38 × 140

3.10

2.81

2.46

2.91

2.65

2.31

38 × 184

4.07

3.70

3.23

3.83

3.48

3.04

38 × 235

5.20

4.72

4.12

4.89

4.44

3.88

38 × 286

6.32

5.75

5.02

5.95

5.41

4.72

No. 1 and

38 × 89

1.91

1.74

1.52

1.80

1.63

1.43

No. 2

38 × 140

3.01

2.73

2.39

2.83

2.57

2.25

38 × 184

3.95

3.59

3.14

3.72

3.38

2.95

38 × 235

5.05

4.59

4.01

4.75

4.32

3.72

38 × 286

6.14

5.58

4.68

5.78

5.25

4.32

No. 3

38 × 89

1.85

1.68

1.47

1.74

1.58

1.38

38 × 140

2.91

2.65

2.16

2.74

2.45

2.00

38 × 184

3.72

3.22

2.63

3.44

2.98

2.43

38 × 235

4.55

3.94

3.22

4.20

3.64

2.97

38 × 286

5.28

4.57

3.73

4.88

4.22

3.45

Construction

38 × 89

1.85

1.68

1.47

1.74

1.58

1.38

Standard

38 × 89

1.76

1.52

1.24

1.62

1.40

1.15

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

1.88

1.71

1.49

1.77

1.61

1.41

Structural

38 × 140

2.96

2.69

2.35

2.79

2.53

2.21

38 × 184

3.89

3.54

3.09

3.66

3.33

2.91

38 × 235

4.97

4.52

3.94

4.68

4.25

3.71

38 × 286

6.05

5.50

4.80

5.69

5.17

4.52

No. 1 and

38 × 89

1.82

1.65

1.44

1.71

1.56

1.36

No. 2

38 × 140

2.86

2.60

2.27

2.69

2.45

2.14

38 × 184

3.76

3.42

2.99

3.54

3.22

2.81

38 × 235

4.81

4.37

3.82

4.52

4.11

3.59

38 × 286

5.85

5.31

4.64

5.50

5.00

4.37

No. 3

38 × 89

1.79

1.62

1.42

1.68

1.53

1.34

38 × 140

2.81

2.56

2.16

2.65

2.40

2.005

38 × 184

3.70

3.22

2.63

3.44

2.98

2.43

38 × 235

4.55

3.94

3.22

4.20

3.64

2.97

38 × 286

5.28

4.57

3.73

4.88

4.22

3.45

Construction

38 × 89

1.79

1.62

1.42

1.68

1.53

1.34

Standard

38 × 89

1.72

1.56

1.29

1.62

1.46

1.19

Northern Species (includes any Canadian Species covered by the NLGA Standard Grading Rules

Select

38 × 89

1.68

1.53

1.34

1.58

1.44

1.26

Structural

38 × 140

2.65

2.40

2.10

2.49

2.26

1.98

38 × 184

3.48

3.16

2.76

3.27

2.97

2.60

38 × 235

4.44

4.04

3.53

4.18

3.80

3.32

38 × 286

5.41

4.91

4.29

5.09

4.62

4.04

No. 1 and

38 × 89

1.64

1.49

1.31

1.55

1.41

1.23

No. 2

38 × 140

2.59

2.35

2.05

2.43

2.21

1.93

38 × 184

3.40

3.09

2.70

3.20

2.91

2.53

38 × 235

4.34

3.94

3.35

4.09

3.71

3.10

38 × 286

5.28

4.76

3.89

4.97

4.40

3.59

No. 3

38 × 89

1.60

1.46

1.21

1.51

1.37

1.12

38 × 140

2.45

2.12

1.73

2.26

1.96

1.60

38 × 184

2.98

2.58

2.11

2.76

2.39

1.95

38 × 235

3.65

3.16

2.58

3.37

2.92

2.38

38 × 286

4.23

3.66

2.99

3.91

3.39

2.76

Construction

38 × 89

1.60

1.46

1.27

1.51

1.37

1.20

Standard

38 × 89

1.46

1.26

1.03

1.34

1.16

0.95

Table A-6 Maximum Spans for Roof Rafters – Specified Roof Snow Loads 1.0 to 2.0 kPa Forming Part of Sentence 9.23.4.2.(1)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Rafter Size, mm

Maximum Span, m

Specified Snow Load, kPa

1.0

1.5

2.0

Rafter Spacing, mm

Rafter Spacing, mm

Rafter Spacing, mm

300

400

600

300

400

600

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

38 × 89

3.41

3.10

2.71

2.98

2.71

2.37

2.71

2.46

2.15

Structural

38 × 140

5.37

4.88

4.26

4.69

4.26

3.72

4.26

3.87

3.38

38 × 184

7.05

6.41

5.60

6.16

5.60

4.89

5.60

5.09

4.44

38 × 235

9.01

8.18

7.15

7.87

7.15

6.24

7.15

6.49

5.62

38 × 286

10.96

9.96

8.70

9.58

8.70

7.40

8.70

7.90

6.52

No. 1 and

38 × 89

3.27

2.97

2.59

2.86

2.59

2.27

2.59

2.36

2.06

No. 2

38 × 140

5.14

4.67

3.95

4.49

4.08

3.34

4.08

3.60

2.94

38 × 184

6.76

5.88

4.80

5.74

4.97

4.06

5.06

4.38

3.58

38 × 235

8.30

7.19

5.87

7.02

6.08

4.96

6.19

5.36

4.38

38 × 286

9.63

8.34

6.81

8.14

7.05

5.76

7.18

6.22

5.08

No. 3

38 × 89

2.65

2.30

1.87

2.24

1.94

1.58

1.98

1.71

1.40

38 × 140

3.78

3.28

2.68

3.20

2.77

2.26

2.82

2.44

1.99

38 × 184

4.61

3.99

3.26

3.89

3.37

2.75

3.43

2.97

2.43

38 × 235

5.63

4.88

3.98

4.76

4.12

3.37

4.20

3.64

2.97

38 × 286

6.53

5.66

4.62

5.52

4.78

3.91

4.87

4.22

3.44

Construction

38 × 89

3.17

2.88

2.42

2.77

2.50

2.04

2.51

2.21

1.80

Standard

38 × 89

2.56

2.22

1.81

2.17

1.88

1.53

1.91

1.65

1.35

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

38 × 89

3.36

3.06

2.67

2.94

2.67

2.33

2.67

2.43

2.12

Structural

38 × 140

5.29

4.81

4.20

4.62

4.20

3.67

4.20

3.82

3.33

38 × 184

6.96

6.32

5.52

6.08

5.52

4.82

5.52

5.02

4.38

38 × 235

8.88

8.07

7.05

7.76

7.05

6.16

7.05

6.41

5.54

38 × 286

10.81

9.82

8.58

9.45

8.58

7.28

8.58

7.80

6.42

No. 1 and

38 × 89

3.27

2.97

2.59

2.86

2.59

2.27

2.59

2.36

2.06

No. 2

38 × 140

5.14

4.67

4.08

4.49

4.08

3.50

4.08

3.71

3.08

38 × 184

6.76

6.14

5.04

5.90

5.21

4.26

5.31

4.60

3.75

38 × 235

8.63

7.54

6.16

7.36

6.37

5.20

6.49

5.62

4.59

38 × 286

10.11

8.75

7.15

8.54

7.40

6.04

7.53

6.52

5.33

No. 3

38 × 89

3.17

2.83

2.31

2.76

2.39

1.95

2.44

2.11

1.72

38 × 140

4.67

4.04

3.30

3.95

3.42

2.79

3.48

3.01

2.46

38 × 184

5.68

4.92

4.02

4.80

4.16

3.40

4.23

3.67

2.99

38 × 235

6.95

6.02

4.91

5.87

5.08

4.15

5.18

4.48

3.66

38 × 286

8.06

6.98

5.70

6.81

5.90

4.82

6.01

5.20

4.25

Construction

38 × 89

3.17

2.88

2.51

2.77

2.51

2.14

2.51

2.28

1.89

Standard

38 × 89

2.68

2.32

1.90

2.27

1.96

1.60

2.00

1.73

1.41

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

3.22

2.92

2.55

2.81

2.55

2.23

2.55

2.32

2.03

Structural

38 × 140

5.06

4.60

4.02

4.42

4.02

3.51

4.02

3.65

3.19

38 × 184

6.65

6.05

5.28

5.81

5.28

4.61

5.28

4.80

4.19

38 × 235

8.50

7.72

6.74

7.42

6.74

5.89

6.74

6.13

5.35

38 × 286

10.34

9.40

8.21

9.03

8.21

7.17

8.21

7.46

6.52

No. 1 and

38 × 89

3.11

2.83

2.47

2.72

2.47

2.16

2.47

2.24

1.96

No. 2

38 × 140

4.90

4.45

3.89

4.28

3.89

3.40

3.89

3.53

3.08

38 × 184

6.44

5.85

5.11

5.62

5.11

4.41

5.11

4.64

3.89

38 × 235

8.22

7.47

6.38

7.18

6.52

5.39

6.52

5.82

4.75

38 × 286

10.00

9.06

7.40

8.74

7.66

6.25

7.80

6.76

5.52

No. 3

38 × 89

3.06

2.78

2.31

2.67

2.39

1.95

2.43

2.11

1.72

38 × 140

4.67

4.04

3.30

3.95

3.42

2.79

3.48

3.01

2.46

38 × 184

5.68

4.92

4.02

4.80

4.16

3.40

4.23

3.67

2.99

38 × 235

6.95

6.02

4.91

5.87

5.08

4.15

5.18

4.48

3.66

38 × 286

8.06

6.98

5.70

6.81

5.90

4.82

6.01

5.20

4.25

Construction

38 × 89

3.06

2.78

2.43

2.67

2.43

2.12

2.43

2.20

1.93

Standard

38 × 89

2.78

2.41

1.97

2.35

2.04

1.66

2.07

1.79

1.47

Northern Species (includes any Canadian species covered by the NLGA Standard Grading Rules)

Select

38 × 89

2.88

2.61

2.28

2.51

2.28

1.99

2.28

2.07

1.81

Structural

38 × 140

4.53

4.11

3.59

3.95

3.59

3.14

3.59

3.26

2.85

38 × 184

5.95

5.40

4.72

5.20

4.72

4.12

4.72

4.29

3.68

38 × 235

7.60

6.90

6.03

6.64

6.03

5.11

6.03

5.48

4.51

38 × 286

9.25

8.40

7.01

8.08

7.26

5.93

7.34

6.40

5.23

No. 1 and

38 × 89

2.81

2.55

2.23

2.46

2.23

1.95

2.23

2.03

1.77

No. 2

38 × 140

4.42

4.02

3.44

3.86

3.51

2.91

3.51

3.14

2.56

38 × 184

5.81

5.13

4.19

5.00

4.33

3.54

4.41

3.82

3.12

38 × 235

7.24

6.27

5.12

6.12

5.30

4.33

5.40

4.67

3.82

38 × 286

8.40

7.27

5.94

7.10

6.15

5.02

6.26

5.42

4.43

No. 3

38 × 89

2.62

2.27

1.85

2.22

1.92

1.57

1.95

1.69

1.38

38 × 140

3.74

3.24

2.65

3.16

2.74

2.24

2.79

2.42

1.97

38 × 184

4.56

3.94

3.22

3.85

3.33

2.72

3.40

2.94

2.40

38 × 235

5.57

4.82

3.94

4.71

4.08

3.33

4.15

3.60

2.94

38 × 286

6.46

5.60

4.57

5.46

4.73

3.86

4.82

4.17

3.41

Construction

38 × 89

2.74

2.49

2.11

2.40

2.18

1.90

2.18

1.93

1.57

Standard

38 × 89

2.22

1.93

1.57

1.88

1.63

1.33

1.66

1.44

1.17

Table A-7 Maximum Spans for Roof Rafters – Specified Roof Snow Loads 2.5 and 3.0 kPa Forming Part of Sentence 9.23.4.2.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Commercial Designation

Grade

Rafter Size, mm

Maximum Span, m

Specified Snow Load, kPa

2.5

3.0

Rafter Spacing, mm

Rafter Spacing, mm

300

400

600

300

400

600

Douglas Fir – Larch

(includes Douglas Fir and Western Larch)

Select

38 × 89

2.51

2.28

1.99

2.37

2.15

1.88

Structural

38 × 140

3.95

3.59

3.14

3.72

3.38

2.95

38 × 184

5.20

4.72

4.12

4.89

4.44

3.83

38 × 235

6.64

6.03

5.08

6.24

5.67

4.68

38 × 286

8.08

7.23

5.90

7.60

6.65

5.43

No. 1 and

38 × 89

2.41

2.19

1.86

2.27

2.06

1.71

No. 2

38 × 140

3.76

3.26

2.66

3.46

3.00

2.45

38 × 184

4.58

3.96

3.24

4.21

3.65

2.98

38 × 235

5.60

4.85

3.96

5.15

4.46

3.64

38 × 286

6.50

5.63

4.59

5.98

5.17

4.23

No. 3

38 × 89

1.79

1.55

1.26

1.64

1.42

1.16

38 × 140

2.55

2.21

1.80

2.35

2.03

1.66

38 × 184

3.10

2.69

2.20

2.86

2.47

2.02

38 × 235

3.80

3.29

2.68

3.49

3.02

2.47

38 × 286

4.41

3.82

3.12

4.05

3.51

2.87

Construction

38 × 89

2.30

2.00

1.63

2.12

1.84

1.50

Standard

38 × 89

1.73

1.50

1.22

1.59

1.38

1.12

Hem – Fir (includes

Western Hemlock and Amabilis Fir)

Select

38 × 89

2.48

2.25

1.97

2.33

2.12

1.85

Structural

38 × 140

3.90

3.54

3.10

3.67

3.33

2.91

38 × 184

5.13

4.66

4.07

4.82

4.38

3.77

38 × 235

6.55

5.95

5.01

6.16

5.60

4.61

38 × 286

7.97

7.12

5.81

7.50

6.55

5.34

No. 1 and

38 × 89

2.41

2.19

1.91

2.27

2.06

1.80

No. 2

38 × 140

3.79

3.42

2.79

3.57

3.14

2.57

38 × 184

4.80

4.16

3.40

4.42

3.83

3.12

38 × 235

5.87

5.08

4.15

5.40

4.68

3.82

38 × 286

6.81

5.90

4.82

6.27

5.43

4.43

No. 3

38 × 89

2.21

1.91

1.56

2.03

1.76

1.43

38 × 140

3.15

2.73

2.23

2.90

2.51

2.05

38 × 184

3.83

3.32

2.71

3.52

3.05

2.49

38 × 235

4.68

4.06

3.31

4.31

3.73

3.05

38 × 286

5.53

4.71

3.84

5.00

4.33

3.54

Commercial

38 × 89

2.33

2.09

1.71

2.20

1.93

1.57

Standard

38 × 89

1.81

1.57

1.28

1.66

1.44

1.18

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

2.37

2.15

1.88

2.23

2.03

1.77

Structural

38 × 140

3.73

3.39

2.96

3.51

3.19

2.79

38 × 184

4.90

4.45

3.89

4.61

4.19

3.66

38 × 235

6.26

5.69

4.97

5.89

5.35

4.68

38 × 286

7.62

6.92

5.90

7.17

6.52

5.43

No. 1 and

38 × 89

2.29

2.08

1.82

2.16

1.96

1.71

No. 2

38 × 140

3.61

3.28

2.86

3.40

3.08

2.66

38 × 184

4.74

4.31

3.52

4.46

3.96

3.23

38 × 235

6.06

5.27

4.30

5.59

4.84

3.96

38 × 286

7.06

6.11

4.99

6.49

5.62

4.59

No. 3

38 × 89

2.21

1.91

1.56

2.03

1.76

1.43

38 × 140

3.15

2.73

2.23

2.90

2.51

2.05

38 × 184

3.83

3.32

2.71

3.52

3.05

2.49

38 × 235

4.68

4.06

3.31

4.31

3.73

3.05

38 × 286

5.43

4.71

3.84

5.00

4.33

3.54

Construction

38 × 89

2.25

2.05

1.77

2.12

1.93

1.63

Standard

38 × 89

1.87

1.62

1.33

1.72

1.49

1.22

Northern Species (includes any Canadian species covered by the NLGA Standard Grading Rules)

Select

38 × 89

2.12

1.93

1.68

1.99

1.81

1.58

Structural

38 × 140

3.33

3.03

2.65

3.14

2.85

2.49

38 × 184

4.38

3.98

3.33

4.12

3.75

3.07

38 × 235

5.60

4.99

4.08

5.27

4.59

3.75

38 × 286

6.69

5.79

4.73

6.15

5.33

4.35

No. 1 and

38 × 89

2.07

1.88

1.62

1.95

1.77

1.49

No. 2

38 × 140

3.26

2.84

2.32

3.02

2.61

2.13

38 × 184

3.99

3.46

2.82

3.67

3.18

2.60

38 × 235

4.88

4.23

3.45

4.49

3.89

3.17

38 × 286

5.66

4.90

4.00

5.21

4.51

3.68

No. 3

38 × 89

1.77

1.53

1.25

1.63

1.41

1.15

38 × 140

2.52

2.19

1.78

2.32

2.01

1.64

38 × 184

3.07

2.66

2.17

2.82

2.45

2.00

38 × 235

3.76

3.25

2.66

3.45

2.99

2.44

38 × 286

4.36

3.77

3.08

4.01

3.47

2.83

Construction

38 × 89

2.01

1.74

1.42

1.85

1.60

1.31

Standard

38 × 89

1.50

1.30

1.06

1.38

1.19

0.98

Table A-8 Maximum Spans for Built-up Floor Beams Supporting not more than One Floor(1)(2) Forming Part of Sentence 9.23.4.2.(3)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Supported Length, mm(3)(4)

Maximum Span, m(5)(6)

Size of Built-up Beam, mm

3 – 38 ×184

4 – 38 × 184

5 – 38 × 184

3 – 38 × 235

4 – 38 × 235

5 – 38 × 235

3 – 38 × 286

4 – 38 × 286

5 – 38 × 286

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

2.4

3.36

3.70

3.99

4.30

4.73

5.09

5.23

5.66

5.99

Structural

3.0

3.12

3.44

3.70

3.99

4.39

4.73

4.84

5.34

5.66

3.6

2.94

3.23

3.48

3.75

4.13

4.45

4.41

5.03

5.41

4.2

2.79

3.07

3.31

3.52

3.92

4.23

4.09

4.72

5.14

4.8

2.67

2.94

3.17

3.29

3.75

4.04

3.82

4.41

4.92

5.4

2.54

2.83

3.04

3.11

3.59

3.89

3.60

4.16

4.65

6.0

2.41

2.73

2.94

2.95

3.40

3.75

3.42

3.95

4.41

No. 1 and

2.4

2.97

3.42

3.82

3.63

4.19

4.68

4.21

4.86

5.43

No. 2

3.0

2.65

3.06

3.42

3.24

3.75

4.19

3.76

4.35

4.86

3.6

2.42

2.80

3.13

2.96

3.42

3.82

3.44

3.97

4.44

4.2

2.24

2.59

2.89

2.74

3.17

3.54

3.18

3.67

4.11

4.8

2.10

2.42

2.71

2.56

2.96

3.31

2.98

3.44

3.84

5.4

1.98

2.28

2.55

2.42

2.79

3.12

2.81

3.24

3.62

6.0

1.88

2.17

2.42

2.29

2.65

2.96

2.66

3.07

3.44

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

2.4

3.32

3.65

3.93

4.24

4.66

5.03

5.16

5.61

5.93

Structural

3.0

3.08

3.39

3.65

3.93

4.33

4.66

4.76

5.27

5.61

3.6

2.90

3.19

3.44

3.70

4.08

4.39

4.35

4.96

5.34

4.2

2.75

3.03

3.27

3.47

3.87

4.17

4.02

4.65

5.07

4.8

2.63

2.90

3.12

3.24

3.70

3.99

3.66

4.35

4.85

5.4

2.49

2.79

3.00

2.95

3.53

3.83

3.32

4.10

4.58

6.0

2.28

2.69

2.90

2.70

3.35

3.70

3.04

3.87

4.35

No. 1 and

2.4

3.11

3.55

3.82

3.80

4.39

4.88

4.41

5.10

5.70

No. 2

3.0

2.78

3.21

3.55

3.40

3.93

4.39

3.95

4.56

5.10

3.6

2.54

2.93

3.28

3.11

3.59

4.01

3.60

4.16

4.65

4.2

2.35

2.72

3.04

2.88

3.32

3.71

3.34

3.85

4.31

4.8

2.20

2.54

2.84

2.69

3.11

3.47

3.12

3.60

4.03

5.4

2.07

2.39

2.68

2.54

2.93

3.27

2.94

3.40

3.80

6.0

1.97

2.27

2.54

2.41

2.78

3.11

2.79

3.22

3.60

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

2.4

3.17

3.49

3.76

4.05

4.46

4.81

4.93

5.42

5.73

Structural

3.0

2.95

3.24

3.49

3.76

4.14

4.46

4.58

5.04

5.42

3.6

2.77

3.05

3.29

3.54

3.90

4.20

4.31

4.74

5.11

4.2

2.63

2.90

3.12

3.36

3.70

3.99

4.09

4.51

4.85

4.8

2.52

2.77

2.99

3.22

3.54

3.81

3.82

4.31

4.64

5.4

2.42

2.67

2.87

3.09

3.41

3.67

3.60

4.14

4.46

6.0

2.34

2.57

2.77

2.95

3.29

3.54

3.32

3.95

4.31

No. 1 and

2.4

3.07

3.38

3.64

3.92

4.32

4.65

4.57

5.25

5.59

No. 2

3.0

2.85

3.14

3.38

3.52

4.01

4.32

4.09

4.72

5.25

3.6

2.63

2.95

3.18

3.22

3.71

4.06

3.73

4.31

4.82

4.2

2.44

2.80

3.02

2.98

3.44

3.84

3.46

3.99

4.46

4.8

2.28

2.63

2.89

2.79

3.22

3.60

3.23

3.73

4.17

5.4

2.15

2.48

2.77

2.63

3.03

3.39

3.05

3.52

3.93

6.0

2.04

2.35

2.63

2.49

2.88

3.22

2.89

3.34

3.73

Northern Species (includes any Canadian species covered by the NLGA Standard GradingRules)

Select

2.4

2.84

3.12

3.36

3.62

3.99

4.30

4.33

4.85

5.23

Structural

3.0

2.63

2.90

3.12

3.34

3.70

3.99

3.88

4.47

4.85

3.6

2.48

2.73

2.94

3.05

3.48

3.75

3.54

4.08

4.57

4.2

2.31

2.59

2.79

2.82

3.26

3.57

3.28

3.78

4.23

4.8

2.16

2.48

2.67

2.64

3.05

3.41

3.06

3.54

3.96

5.4

2.04

2.35

2.57

2.49

2.87

3.21

2.89

3.34

3.73

6.0

1.93

2.23

2.48

2.36

2.73

3.05

2.74

3.16

3.54

No. 1 and

2.4

2.59

2.99

3.29

3.16

3.65

4.08

3.67

4.24

4.74

No. 2

3.0

2.31

2.67

2.99

2.83

3.27

3.65

3.28

3.79

4.24

3.6

2.11

2.44

2.73

2.58

2.98

3.33

3.00

3.46

3.87

4.2

1.95

2.26

2.52

2.39

2.76

3.09

2.77

3.20

3.58

4.8

1.83

2.11

2.36

2.24

2.58

2.89

2.59

3.00

3.35

5.4

1.72

1.99

2.23

2.11

2.43

2.72

2.45

2.82

3.16

6.0

1.64

1.89

2.11

2.00

2.31

2.58

2.32

2.68

3.00

Notes to Table A-8:

(1) Beam spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floors does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2) When the floors have a concrete topping of not more than 51 mm, the spans must be multiplied by 0.8

(3) Supported length means half the sum of the joists spans on both sides of the beam.

(4) Straight interpolation may be used for other supported lengths.

(5) Spans are clear spans between supports.  For total span, add two bearing lengths.

(6) 3-ply beams with supported lengths greater than 4.2 m require minimum bearing length of 114 mm.  All other beams require minimum bearing length of 76 mm.

Table A-9 Maximum Spans for Built-up Floor Beams Supporting not more than Two Floors(1)(2) Forming Part of Sentence 9.23.4.2.(3)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Supported Length, mm(3)(4)

Maximum Span, m(5)(6)

Size of Built-up Beam, mm

3 – 38 × 184

4 – 38 × 184

5 – 38 × 184

3 – 38 × 235

4 – 38 × 235

5 – 38 × 235

3 – 38 × 286

4 – 38 × 286

5 – 38 × 286

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

2.4

2.80

3.08

3.32

3.49

3.93

4.24

4.05

4.67

5.16

Structural

3.0

2.55

2.86

3.08

3.12

3.60

3.93

3.62

4.18

4.67

3.6

2.33

2.69

2.90

2.85

3.29

3.68

3.30

3.82

4.27

4.2

2.16

2.49

2.75

2.64

3.04

3.40

2.99

3.53

3.95

4.8

2.00

2.33

2.60

2.38

2.85

3.18

2.69

3.30

3.69

5.4

1.82

2.20

2.45

2.17

2.68

3.00

2.45

3.08

3.48

6.0

1.67

2.08

2.33

2.00

2.51

2.85

2.26

2.83

3.30

No. 1 and

2.4

2.22

2.56

2.87

2.72

3.14

3.51

3.15

3.64

4.07

No.2

3.0

1.99

2.29

2.56

2.43

2.80

3.14

2.82

3.25

3.64

3.6

1.81

2.09

2.34

2.22

2.56

2.86

2.57

2.97

3.32

4.2

1.68

1.94

2.17

2.05

2.37

2.65

2.38

2.75

3.07

4.8

1.57

1.81

2.03

1.92

2.22

2.48

2.23

2.57

2.88

5.4

1.48

1.71

1.91

1.81

2.09

2.34

2.10

2.43

2.71

6.0

1.40

1.62

1.81

1.72

1.98

2.22

1.99

2.30

2.57

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

2.4

2.76

3.04

3.27

3.43

3.88

4.18

3.99

4.60

5.09

Structural

3.0

2.51

2.82

3.04

2.97

3.55

3.88

3.34

4.12

4.60

3.6

2.15

2.65

2.86

2.56

3.24

3.62

2.88

3.65

4.20

4.2

1.90

2.40

2.72

2.26

2.85

3.35

2.55

3.21

3.87

4.8

1.70

2.15

2.56

2.03

2.56

3.08

2.30

2.88

3.46

5.4

1.56

1.95

2.35

1.86

2.32

2.79

2.11

2.62

3.14

6.0

1.44

1.79

2.15

1.72

2.14

2.56

1.96

2.42

2.88

No. 1 and

2.4

2.33

2.69

3.01

2.85

3.29

3.68

3.30

3.82

4.27

No.2

3.0

2.08

2.41

2.69

2.55

2.94

3.29

2.96

3.41

3.82

3.6

1.90

2.20

2.45

2.33

2.68

3.00

2.70

3.12

3.48

4.2

1.76

2.03

2.27

2.15

2.49

2.78

2.50

2.88

3.22

4.8

1.65

1.90

2.13

2.01

2.33

2.60

2.30

2.70

3.02

5.4

1.55

1.79

2.00

1.86

2.19

2.45

2.11

2.54

2.84

6.0

1.44

1.70

1.90

1.72

2.08

2.33

1.96

2.41

2.70

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

2.4

2.64

2.91

3.13

3.37

3.71

4.00

4.05

4.52

4.87

Structural

3.0

2.45

2.70

2.91

3.12

3.45

4.71

3.62

4.18

4.52

3.6

2.31

2.54

2.73

2.79

3.24

3.49

3.14

3.82

4.25

4.2

2.07

2.41

2.60

2.46

3.04

3.32

2.77

3.50

3.95

4.8

1.85

2.31

2.48

2.21

2.79

3.17

2.50

3.14

3.69

5.4

1.69

2.13

2.39

2.02

2.53

3.00

2.28

2.85

3.42

6.0

1.56

1.95

2.31

1.86

2.32

2.79

2.11

2.62

3.14

No. 1 and

2.4

2.41

2.79

3.03

2.95

3.41

3.81

3.42

3.95

4.42

No.2

3.0

2.16

2.49

2.79

2.64

3.05

3.41

3.06

3.53

3.95

3.6

1.97

2.27

2.54

2.41

2.78

3.11

2.79

3.23

3.61

4.2

1.82

2.11

2.35

2.23

2.57

2.88

2.59

2.99

3.34

4.8

1.71

1.97

2.20

2.09

2.41

2.69

2.42

2.79

3.12

5.4

1.61

1.86

2.08

1.97

2.27

2.54

2.28

2.63

2.95

6.0

1.53

1.76

1.97

1.86

2.15

2.41

2.11

2.50

2.79

Northern Species (includes any Canadian species covered by the NLGA Standard Grading Rules)

Select

2.4

2.29

2.60

2.80

2.80

3.23

3.57

3.24

3.75

4.19

Structural

3.0

2.04

2.36

2.60

2.50

2.89

3.23

2.90

3.35

3.75

3.6

1.87

2.16

2.41

2.28

2.64

2.95

2.65

3.06

3.42

4.2

1.73

2.00

2.23

2.11

2.44

2.73

2.45

2.83

3.17

4.8

1.62

1.87

2.09

1.98

2.28

2.55

2.29

2.65

2.96

5.4

1.52

1.76

1.97

1.86

2.15

2.41

2.11

2.50

2.79

6.0

1.44

1.67

1.87

1.72

2.04

2.28

1.96

2.37

2.65

No. 1 and

2.4

1.94

2.24

2.50

2.37

2.73

3.06

2.75

3.17

3.55

No.2

3.0

1.73

2.00

2.24

2.12

2.44

2.73

2.46

2.84

3.17

3.6

1.58

1.83

2.04

1.93

2.23

2.50

2.24

2.59

2.90

4.2

1.46

1.69

1.89

1.79

2.07

2.31

2.08

2.40

2.68

4.8

1.37

1.58

1.77

1.67

1.93

2.16

1.94

2.24

2.51

5.4

1.29

1.49

1.67

1.58

1.82

2.04

1.83

2.11

2.36

6.0

1.22

1.41

1.58

1.50

1.73

1.93

1.74

2.01

2.24

Notes to Table A-9:

(1) Beam spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floors does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2) When the floors have a concrete topping of not more than 51 mm, the spans must be multiplied by 0.8

(3) Supported length means half the sum of the joists spans on both sides of the beam.

(4) Straight interpolation may be used for other supported lengths.

(5) Spans are clear spans between supports.  For total span, add two bearing lengths.

(6) 3-ply beams require minimum bearing length of 114 mm.  4-ply and 5-ply beams with supported lengths greater than 3 m require minimum bearing length of 114 mm.  All other beams require minimum bearing length of 76 mm.

Table A-10 Maximum Spans for Built-up Floor Beams Supporting not more than Three Floors(1)(2) Forming Part of Sentence 9.23.4.2.(3)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Supported Length, mm(3)(4)

Maximum Span, m(5)(6)

Size of Built-up Beam, mm

3 – 38 × 184

4 – 38 × 184

5 – 38 × 184

3 – 38 × 235

4 – 38 × 235

5 – 38 × 235

3 – 38 × 286

4 – 38 × 286

5 – 38 × 286

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

2.4

2.38

2.74

2.95

2.91

3.36

3.75

3.37

3.89

4.35

Structural

3.0

2.13

2.46

2.74

2.60

3.00

3.36

2.92

3.48

3.89

3.6

1.88

2.24

2.51

2.24

2.74

3.06

2.53

3.18

3.56

4.2

1.66

2.08

2.32

1.99

2.49

2.84

2.25

2.81

3.29

4.8

1.50

1.88

2.17

1.80

2.24

2.65

2.04

2.53

3.02

5.4

1.38

1.71

2.05

1.65

2.04

2.44

1.88

2.31

2.75

6.0

1.28

1.58

1.88

1.53

1.89

2.24

1.75

2.14

2.53

No. 1 and

2.4

1.85

2.14

2.39

2.26

2.61

2.92

2.63

3.03

3.39

No.2

3.0

1.66

1.91

2.14

2.02

2.34

2.61

2.35

2.71

3.03

3.6

1.51

1.74

1.95

1.85

2.13

2.39

2.14

2.48

2.77

4.2

1.40

1.62

1.81

1.71

1.98

2.21

1.99

2.29

2.56

4.8

1.31

1.51

1.69

1.60

1.85

2.07

1.86

2.14

2.40

5.4

1.23

1.42

1.59

1.51

1.74

1.95

1.75

2.02

2.26

6.0

1.17

1.35

1.51

1.43

1.65

1.85

1.66

1.92

2.14

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

2.4

2.22

2.70

2.91

2.64

3.31

3.70

2.98

3.78

4.29

Structural

3.0

1.85

2.35

2.70

2.21

2.79

3.31

2.50

3.14

3.78

3.6

1.61

2.02

2.43

1.92

2.40

2.89

2.18

2.71

3.24

4.2

1.43

1.78

2.14

1.71

2.13

2.54

1.95

2.40

2.86

4.8

1.30

1.61

1.92

1.56

1.92

2.28

1.77

2.18

2.58

5.4

1.19

1.47

1.74

1.44

1.76

2.08

1.64

2.00

2.35

6.0

1.11

1.36

1.61

1.34

1.63

1.92

1.53

1.85

2.18

No. 1 and

2.4

1.94

2.24

2.51

2.37

2.74

3.06

2.75

3.18

3.56

No.2

3.0

1.74

2.00

2.24

2.12

2.45

2.74

2.46

2.84

3.18

3.6

1.58

1.83

2.05

1.92

2.24

2.50

2.18

2.60

2.90

4.2

1.43

1.69

1.89

1.71

2.07

2.32

1.95

2.40

2.69

4.8

1.30

1.58

1.77

1.56

1.92

2.17

1.77

2.18

2.51

5.4

1.19

1.47

1.67

1.44

1.76

2.04

1.64

2.00

2.35

6.0

1.11

1.36

1.58

1.34

1.63

1.92

1.53

1.85

2.18

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

2.4

2.35

2.58

2.78

2.89

3.30

3.55

3.24

3.89

4.33

Structural

3.0

2.02

2.40

2.58

2.40

3.00

3.30

2.71

3.42

3.89

3.6

1.74

2.20

2.43

2.08

2.62

3.06

2.35

2.95

3.54

4.2

1.55

1.94

2.31

1.85

2.31

2.77

2.10

2.61

3.12

4.8

1.40

1.74

2.09

1.68

2.08

2.48

1.91

2.35

2.80

5.4

1.28

1.59

1.90

1.54

1.90

2.26

1.76

2.16

2.55

6.0

1.19

1.47

1.74

1.44

1.76

2.08

1.64

2.00

2.35

No. 1 and

2.4

2.01

2.32

2.60

2.46

2.84

3.17

2.85

3.29

3.68

No.2

3.0

1.80

2.08

2.32

2.20

2.54

2.84

2.55

2.95

3.29

3.6

1.64

1.90

2.12

2.01

2.32

2.59

2.33

2.69

3.01

4.2

1.52

1.75

2.96

1.85

2.15

2.40

2.10

2.49

2.78

4.8

1.40

1.64

1.84

1.68

2.01

2.24

1.91

2.33

2.60

5.4

1.28

1.55

1.73

1.54

1.89

2.12

1.76

2.16

2.46

6.0

1.19

1.47

1.64

1.44

1.76

2.01

1.64

2.00

2.33

Northern Species (includes any Canadian species covered by the NLGA Standard Grading Rules)

Select

2.4

1.91

2.20

2.46

2.33

2.69

3.01

2.70

3.12

3.49

Structural

3.0

1.70

1.97

2.20

2.08

2.41

2.69

2.42

2.79

3.12

3.6

1.56

1.80

2.01

1.90

2.20

2.46

2.18

2.55

2.85

4.2

1.43

1.66

1.86

1.71

2.03

2.27

1.95

2.36

2.64

4.8

1.30

1.56

1.74

1.56

1.90

2.13

1.77

2.18

2.47

5.4

1.19

1.47

1.64

1.44

1.76

2.01

1.64

2.00

2.33

6.0

1.11

1.36

1.56

1.34

1.63

1.90

1.53

1.85

2.18

No. 1 and

2.4

1.61

1.86

2.08

1.97

2.28

2.55

2.29

2.64

2.96

No.2

3.0

1.44

1.67

1.86

1.76

2.04

2.28

2.05

2.36

2.64

3.6

1.32

1.52

1.70

1.61

1.86

2.08

1.87

2.16

2.41

4.2

1.22

1.41

1.57

1.49

1.72

1.93

1.73

2.00

2.23

4.8

1.14

1.32

1.47

1.40

1.61

1.80

1.62

1.87

2.09

5.4

1.08

1.24

1.39

1.32

1.52

1.70

1.53

1.76

1.97

6.0

1.02

1.18

1.32

1.25

1.44

1.61

1.45

1.67

1.87

Notes to Table A-10:

(1) Beam spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floors does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2) When the floors have a concrete topping of not more than 51 mm, the spans must be multiplied by 0.8

(3) Supported length means half the sum of the joists spans on both sides of the beam.

(4) Straight interpolation may be used for other supported lengths.

(5) Spans are clear spans between supports.  For total span, add two bearing lengths.

(6) 3-ply beams with supported lengths greater than 4.2 m require minimum bearing length of 152 mm.  All other beams require minimum bearing length of 114 mm.

Table A-11 Maximum Spans for Glue-Laminated Floor Beams – 20f-E Grade(1) Forming Part of Sentence 9.23.4.2.(3)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Number of Storeys Supported

Beam Width, mm

Supported Length, m(2)(3)

Maximum Span, m(4)(5)(6)(7)

Beam Depth, mm

228

266

304

342

380

418

456

1

80

2.4

4.32

5.04

5.76

6.48

7.20

7.92

8.64

3.0

3.87

4.51

5.15

5.80

6.44

7.09

7.73

3.6

3.53

4.12

4.70

5.29

5.88

6.47

7.06

4.2

3.27

3.81

4.36

4.90

5.44

5.99

6.53

4.8

3.06

3.57

4.07

4.58

5.09

5.60

6.11

5.4

2.88

3.36

3.84

4.32

4.80

5.28

5.76

6.0

2.73

3.19

3.64

4.10

4.56

5.01

5.47

130

2.4

5.51

6.43

7.35

8.26

9.18

10.10

11.02

3.0

4.93

5.75

6.57

7.39

8.21

9.03

9.86

3.6

4.50

5.25

6.00

6.75

7.50

8.25

9.00

4.2

4.16

4.86

5.55

6.25

6.94

7.64

8.33

4.8

3.90

4.54

5.19

5.84

6.49

7.14

7.79

5.4

3.67

4.28

4.90

5.51

6.12

6.73

7.35

6.0

3.48

4.07

4.65

5.23

5.81

6.39

6.97

2

80

2.4

3.28

3.83

4.37

4.92

5.47

6.01

6.56

3.0

2.93

3.42

3.91

4.40

4.89

5.38

5.87

3.6

2.68

3.12

3.57

4.02

4.46

4.91

5.36

4.2

2.48

2.89

3.31

3.72

4.13

4.54

4.96

4.8

2.32

2.71

3.09

3.48

3.86

4.25

4.64

5.4

2.19

2.55

2.91

3.28

3.64

4.01

4.37

6.0

2.07

2.42

2.77

3.11

3.46

3.80

4.15

130

2.4

4.18

4.88

5.57

6.27

6.97

7.66

8.36

3.0

3.74

4.36

4.99

5.61

6.23

6.85

7.48

3.6

3.41

3.98

4.55

5.12

5.69

6.26

6.83

4.2

3.16

3.69

4.21

4.74

5.27

5.79

6.32

4.8

2.96

3.45

3.94

4.43

4.93

5.42

5.91

5.4

2.79

3.25

3.72

4.18

4.64

5.11

5.57

6.0

2.64

3.08

3.53

3.97

4.41

4.85

5.29

3

80

2.4

2.75

3.21

3.66

4.12

4.58

5.04

5.50

3.0

2.46

2.87

3.28

3.69

4.10

4.51

4.92

3.6

2.24

2.62

2.99

3.37

3.74

4.11

4.49

4.2

2.08

2.42

2.77

3.12

3.46

3.81

4.15

4.8

1.94

2.27

2.59

2.91

3.24

3.56

3.89

5.4

1.83

2.14

2.44

2.75

3.05

3.36

3.66

6.0

1.74

2.03

2.32

2.61

2.90

3.19

3.48

130

2.4

3.50

4.09

4.67

5.25

5.84

6.42

7.01

3.0

3.13

3.66

4.18

4.70

5.22

5.74

6.27

3.6

2.86

3.34

3.81

4.29

4.77

5.24

5.72

4.2

2.65

3.09

3.53

3.97

4.41

4.85

5.30

4.8

2.48

2.89

3.30

3.72

4.13

4.54

4.95

5.4

2.34

2.72

3.11

3.50

3.89

4.28

4.67

6.0

2.22

2.58

2.95

3.32

3.69

4.06

4.43

Notes to Table A-11:

(1)Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floor does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2)Supported length means half the sum of the joist spans on both sides of the beam.

(3)Straight interpolation may be used for other supported lengths.

(4)Spans are valid for glued-laminated timber conforming to CAN/CSA-O122-M and CAN/CSA-O177-M.

(5)Spans are clear spans between supports. For total span, add two bearing lengths.

(6)Provide a minimum bearing length of 89 mm. (Alternatively, the bearing length may be designed in accordance with Part 4.)

(7)Top edge of beam assumed to be fully laterally supported by joists.

Table A-12 Maximum Spans for Built-up Ridge Beams and Lintels Supporting the Roof and Ceiling Only – No. 1 or No. 2 Grade Forming Part of Sentence 9.23.4.2.(4)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Commercial Designation

Beam or Lintel Size, mm

Maximum Span, m(1)(2)(3)

Specified Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

3 – 38 × 184

2.65

2.28

2.03

1.85

1.71

4 – 38 × 184

3.06

2.64

2.35

2.14

1.97

5 – 38 × 184

3.43

2.95

2.62

2.39

2.21

3 – 38 × 235

3.25

2.79

2.49

2.26

2.09

4 – 38 × 235

3.75

3.22

2.87

2.61

2.41

5 – 38 × 235

4.19

3.60

3.21

2.92

2.70

3 – 38 × 286

3.77

3.24

2.88

2.62

2.43

4 – 38 × 286

4.35

3.74

3.33

3.03

2.80

5 – 38 × 286

4.86

4.18

3.72

3.39

3.13

Hem – Fir (includes Western Hemlock and Amabilis Fir)

3 – 38 × 184

2.78

2.39

2.13

1.94

1.79

4 – 38 × 184

3.21

2.76

2.46

2.24

2.07

5 – 38 × 184

3.59

3.09

2.75

2.50

2.31

3 – 38 × 235

3.40

2.93

2.61

2.37

2.19

4 – 38 × 235

3.93

3.38

3.01

2.74

2.53

5 – 38 × 235

4.39

3.78

3.36

3.06

2.83

3 – 38 × 286

3.95

3.40

3.02

2.75

2.54

4 – 38 × 286

4.56

3.92

3.49

3.18

2.94

5 – 38 × 286

5.10

4.38

3.90

3.55

3.28

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

3 – 38 × 184

2.88

2.48

2.21

2.01

1.86

4 – 38 × 184

3.30

2.86

2.55

2.32

2.14

5 – 38 × 184

3.55

3.10

2.82

2.59

2.40

3 – 38 × 235

3.53

3.03

2.70

2.46

2.27

4 – 38 × 235

4.07

3.50

3.12

2.84

2.62

5 – 38 × 235

4.54

3.91

3.49

3.17

2.93

3 – 38 × 286

4.09

3.52

3.13

2.85

2.63

4 – 38 × 286

4.72

4.06

3.62

3.29

3.04

5 – 38 × 286

5.28

4.54

4.04

3.68

3.40

Notes to Table A-12:

(1)Beam and lintel spans are calculated based on a maximum supported length of 4.9 m. Spans may be increased by 5% for supported lengths of not more than 4.3 m, by 10% for supported lengths of not more than 3.7 m, and by 25% for supported lengths of not more than 2.4 m.

(2)For ridge beams, supported length means half the sum of the rafter, joist or truss spans on both sides of the beam. For lintels, supported length means half the sum of truss, roof joist or rafter spans supported by the lintel plus the length of the overhang beyond the lintel.

(3)Provide a minimum bearing length of 76 mm.

9.23.4.3. — Steel Beams

(1) The spans for steel beams with laterally supported top flanges shall conform to Table 9.23.4.3. for floors and Tables A-20 to A-29 for roofs and floors.

(2) Beams described in Sentence (1) shall at least meet the requirements for Grade 350 W steel in CAN/CSA-G40.21, “Structural Quality Steel”.

(3) A beam may be considered to be laterally supported if,

(a) the wood joists bear on its top flange at intervals of 600 mm or less over its entire length,

(b) the load being applied to this beam is transmitted through the joists, and

(c) 19 mm by 38 mm wood strips in contact with the top flange are nailed on both sides of the beam to the bottom of the joist supported.

Text · e-Laws consolidated snapshot

Table 9.23.4.3. Maximum Spans for Steel Beams Supporting Floors in Dwelling Units Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Supported Joist Length, m (Half the sum of joist spans on both sides of the beam)

2.4

3.0

3.6

4.2

4.8

5.4

6.0

Section

One Storey Supported

W150 × 22

5.5

5.2

4.9

4.8

4.6

4.5

4.3

W200 × 21

6.5

6.2

5.9

5.7

5.4

5.1

4.9

W200 × 27

7.3

6.9

6.6

6.3

6.1

5.9

5.8

W200 × 31

7.8

7.4

7.1

6.8

6.6

6.4

6.2

W250 × 24

8.1

7.6

7.3

7.0

6.6

6.2

5.9

W250 × 33

9.2

8.7

8.3

8.0

7.7

7.5

7.3

W250 × 39

10.0

9.4

9.0

8.6

8.4

8.1

7.9

W310 × 31

10.4

9.8

9.4

8.9

8.4

8.0

7.6

W310 × 39

11.4

10.7

10.2

9.8

9.5

9.2

9.0

Section

Two Storeys Supported

W150 × 22

4.9

4.4

4.1

3.8

3.5

3.4

3.2

W200 × 21

5.6

5.1

4.6

4.3

4.1

3.8

3.7

W200 × 27

6.4

6.1

5.6

5.3

4.9

4.7

4.4

W200 × 31

6.9

6.5

6.2

5.8

5.4

5.1

4.9

W250 × 24

6.8

6.1

5.6

5.2

4.9

4.6

4.4

W250 × 33

8.2

7.7

7.0

6.5

6.1

5.8

5.5

W250 × 39

8.8

8.3

7.8

7.2

6.8

6.4

6.1

W310 × 31

8.7

7.8

7.2

6.7

6.2

5.9

5.6

W310 × 39

10.0

9.3

8.5

7.9

7.4

7.0

6.7

Table A-20 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Exterior Stud Walls with Brick Veneer – 1.0 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

1.0

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

2.96

2.79

2.86

2.71

2.78

2.65

2.71

2.59

W 150 × 30

3.32

3.14

3.22

3.05

3.13

2.98

3.04

2.91

W 150 × 37

3.62

3.41

3.50

3.32

3.40

3.24

3.32

3.17

W 200 × 27

3.80

3.59

3.68

3.49

3.58

3.41

3.49

3.33

W 200 × 31

4.06

3.83

3.93

3.73

3.82

3.64

3.72

3.56

W 200 × 36

4.17

3.94

4.04

3.83

3.93

3.74

3.82

3.65

W 200 × 42

4.42

4.18

4.29

4.06

4.16

3.96

4.05

3.87

W 250 × 33

4.71

4.44

4.56

4.32

4.43

4.22

4.31

4.12

W 250 × 39

5.04

4.76

4.88

4.63

4.75

4.52

4.62

4.41

W 250 × 49

5.32

5.02

5.15

4.89

5.01

4.77

4.87

4.66

W 310 × 39

5.66

5.34

5.49

5.20

5.33

5.07

5.19

4.96

W 310 × 45

5.96

5.62

5.77

5.47

5.61

5.34

5.46

5.22

W 310 × 52

6.33

5.98

6.13

5.82

5.96

5.67

5.8

5.54

W 310 × 60

6.50

6.14

6.30

5.98

6.12

5.83

5.96

5.69

W 360 × 33

5.61

5.29

5.43

5.15

5.28

5.03

5.14

4.91

W 360 × 39

6.01

5.68

5.83

5.53

5.66

5.39

5.51

5.27

W 360 × 45

6.38

6.03

6.19

5.87

6.01

5.72

5.85

5.59

W 360 × 51

6.70

6.32

6.49

6.16

6.31

6.00

6.14

5.87

W 360 × 57

7.00

6.61

6.78

6.43

6.59

6.28

6.42

6.13

Table A-21 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Interior Stud Walls or Exterior Stud Walls with Siding – 1.0 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

1.0

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

4.20

3.82

3.98

3.67

3.81

3.51

3.66

3.35

W 150 × 30

4.72

4.30

4.48

4.13

4.28

3.98

4.11

3.85

W 150 × 37

5.14

4.68

4.88

4.49

4.66

4.33

4.48

4.19

W 200 × 27

5.41

4.92

5.13

4.72

4.90

4.56

4.71

4.41

W 200 × 31

5.77

5.25

5.48

5.04

5.23

4.86

5.02

4.71

W 200 × 36

5.93

5.40

5.63

5.18

5.38

5.00

5.16

4.84

W 200 × 42

6.29

5.72

5.97

5.50

5.70

5.30

5.47

5.13

W 250 × 33

6.69

6.09

6.35

5.85

6.06

5.64

5.82

5.45

W 250 × 39

7.17

6.52

6.80

6.26

6.49

6.04

6.24

5.85

W 250 × 49

7.56

6.88

7.17

6.61

6.85

6.37

6.58

6.17

W 310 × 39

8.05

7.32

7.63

7.03

7.29

6.78

7.01

6.56

W 310 × 45

8.47

7.71

8.03

7.40

7.68

7.14

7.37

6.91

Table A-22 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Exterior Stud Walls with Brick Veneer – 1.5 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

1.5

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

2.86

2.71

2.74

2.62

2.64

2.53

2.55

2.46

W 150 × 30

3.22

3.05

3.08

2.94

2.97

2.85

2.87

2.76

W 150 × 37

3.50

3.32

3.36

3.20

3.23

3.10

3.13

3.01

W 200 × 27

3.68

3.49

3.53

3.37

3.40

3.26

3.29

3.16

W 200 × 31

3.93

3.73

3.77

3.60

3.63

3.48

3.51

3.38

W 200 × 36

4.04

3.83

3.88

3.70

3.73

3.58

3.61

3.47

W 200 × 42

4.29

4.06

4.11

3.92

3.96

3.79

3.82

3.68

W 250 × 33

4.56

4.32

4.37

4.17

4.21

4.03

4.07

3.91

W 250 × 39

4.88

4.63

4.68

4.47

4.51

4.32

4.36

4.19

W 250 × 49

5.15

4.89

4.94

4.71

4.76

4.56

4.60

4.42

W 310 × 39

5.49

5.20

5.26

5.01

5.06

4.85

4.89

4.71

W 310 × 45

5.77

5.47

5.53

5.28

5.33

5.11

5.15

4.95

W 310 × 52

6.13

5.82

5.88

5.61

5.66

5.43

5.47

5.26

W 310 × 60

6.30

5.98

6.04

5.76

5.81

5.57

5.62

5.41

W 360 × 33

5.43

5.15

5.21

4.97

5.01

4.81

4.85

4.66

W 360 × 39

5.83

5.53

5.58

5.33

5.38

5.15

5.20

5.00

W 360 × 45

6.19

5.87

5.93

5.65

5.71

5.47

5.52

5.31

W 360 × 51

6.49

6.16

6.22

5.93

5.99

5.74

5.79

5.57

W 360 × 57

6.78

6.43

6.50

6.20

6.26

6.00

6.05

5.82

Table A-23 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Interior Stud Walls or Exterior Stud Walls with Siding – 1.5 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

1.5

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

3.98

3.67

3.73

3.48

3.53

3.30

3.36

3.12

W 150 × 30

4.48

4.13

4.19

3.91

3.97

3.74

3.78

3.59

W 150 × 37

4.88

4.49

4.56

4.26

4.32

4.07

4.12

3.91

W 200 × 27

5.13

4.72

4.80

4.48

4.54

4.28

4.33

4.11

W 200 × 31

5.48

5.04

5.12

4.78

4.85

4.57

4.62

4.39

W 200 × 36

5.63

5.18

5.27

4.92

4.98

4.70

4.75

4.51

W 200 × 42

5.97

5.50

5.58

5.21

5.28

4.98

5.04

4.78

W 250 × 33

6.35

5.85

5.94

5.54

5.62

5.30

5.36

5.09

W 250 × 39

6.80

6.26

6.36

5.94

6.02

5.67

5.74

5.45

W 250 × 49

7.17

6.61

6.71

6.27

6.35

5.99

6.06

5.75

W 310 × 39

7.63

7.03

7.14

6.67

6.76

6.37

6.45

6.12

W 310 × 45

8.03

7.40

7.52

7.02

7.11

6.71

6.78

6.44

Table A-24 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Exterior Stud Walls with Brick Veneer – 2.0 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

2

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

2.78

2.65

2.64

2.53

2.53

2.43

2.43

2.35

W 150 × 30

3.13

2.98

2.97

2.85

2.84

2.74

2.73

2.64

W 150 × 37

3.40

3.24

3.23

3.10

3.09

2.98

2.97

2.88

W 200 × 27

3.58

3.41

3.40

3.26

3.25

3.13

3.13

3.02

W 200 × 31

3.82

3.64

3.63

3.48

3.47

3.34

3.34

3.23

W 200 × 36

3.93

3.74

3.73

3.58

3.57

3.44

3.43

3.32

W 200 × 42

4.16

3.96

3.96

3.79

3.78

3.64

3.64

3.52

W 250 × 33

4.43

4.22

4.21

4.03

4.02

3.88

3.87

3.74

W 250 × 39

4.75

4.52

4.51

4.32

4.31

4.15

4.15

4.01

W 250 × 49

5.01

4.77

4.76

4.56

4.55

4.38

4.37

4.23

W 310 × 39

5.33

5.07

5.06

4.85

4.84

4.66

4.65

4.50

W 310 × 45

5.61

5.34

5.33

5.11

5.10

4.91

4.90

4.74

W 310 × 52

5.96

5.67

5.66

5.43

5.41

5.21

5.21

5.03

W 310 × 60

6.12

5.83

5.81

5.57

5.56

5.36

5.35

5.17

W 360 × 33

5.28

5.03

5.01

4.81

4.80

4.62

4.61

4.46

W 360 × 39

5.66

5.39

5.38

5.15

5.14

4.95

4.94

4.78

W 360 × 45

6.01

5.72

5.71

5.47

5.46

5.26

5.25

5.08

W 360 × 51

6.31

6.00

5.99

5.74

5.73

5.52

5.51

5.33

W 360 × 57

6.59

6.28

6.26

6.00

5.99

5.77

5.76

5.57

Table A-25 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Interior Stud Walls or Exterior Stud Walls with Siding – 2.0 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

2.0

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

3.81

3.54

3.53

3.33

3.32

3.13

3.15

2.94

W 150 × 30

4.28

3.98

3.97

3.74

3.73

3.55

3.54

3.39

W 150 × 37

4.66

4.33

4.32

4.70

4.06

3.86

3.85

3.69

W 200 × 27

4.90

4.56

4.54

4.28

4.27

4.06

4.05

3.88

W 200 × 31

5.23

4.86

4.85

4.57

4.56

4.34

4.32

4.14

W 200 × 36

5.38

5.00

4.98

4.07

4.68

4.46

4.45

4.26

W 200 × 42

5.70

5.30

5.28

4.98

4.96

4.72

4.71

4.51

W 250 × 33

6.06

5.64

5.62

5.30

5.28

5.03

5.01

4.80

W 250 × 39

6.49

6.04

6.02

5.67

5.66

5.38

5.37

5.14

W 250 × 49

6.85

6.37

6.35

5.99

5.97

5.68

5.67

5.43

W 310 × 39

7.29

6.78

6.76

6.37

6.35

6.04

6.03

5.77

W 310 × 45

7.68

7.14

7.11

6.71

6.69

6.36

6.35

6.08

Table A-26 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Exterior Stud Walls with Brick Veneer – 2.5 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

2.5

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

2.71

2.59

2.55

2.46

2.43

2.35

2.33

2.26

W 150 × 30

3.04

2.91

2.87

2.76

2.73

2.64

2.62

2.54

W 150 × 37

3.32

3.17

3.13

3.01

2.97

2.88

2.85

2.77

W 200 × 27

3.49

3.33

3.29

3.16

3.13

3.02

2.99

2.91

W 200 × 31

3.72

3.56

3.51

3.38

3.34

3.23

3.20

3.10

W 200 × 36

3.82

3.65

3.61

3.47

3.43

3.32

3.29

3.19

W 200 × 42

4.05

3.87

3.82

3.68

3.64

3.52

3.48

3.38

W 250 × 33

4.31

4.12

4.07

3.91

3.87

3.74

3.71

3.60

W 250 × 39

4.62

4.41

4.36

4.19

4.15

4.01

3.97

3.85

W 250 × 49

4.87

4.66

4.60

4.42

4.37

4.23

4.19

4.07

W 310 × 39

5.19

4.96

4.89

4.71

4.65

4.50

4.46

4.33

W 310 × 45

5.46

5.22

5.15

4.95

4.90

4.74

4.69

4.55

W 310 × 52

5.80

5.54

5.47

5.26

5.21

5.03

4.98

4.84

W 310 × 60

5.96

5.69

5.62

5.41

5.35

5.17

5.12

4.97

W 360 × 33

5.14

4.91

4.85

4.66

4.61

4.46

4.42

4.29

W 360 × 39

5.51

5.27

5.20

5.00

4.94

4.78

4.73

4.60

W 360 × 45

5.85

5.59

5.52

5.31

5.25

5.08

5.03

4.88

W 360 × 51

6.14

5.87

5.79

5.57

5.51

5.33

5.27

5.12

W 360 × 57

6.42

6.13

6.05

5.82

5.76

5.57

5.51

5.35

Table A-27 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Interior Stud Walls or Exterior Stud Walls with Siding – 2.5 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

2.5

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

3.66

3.43

3.36

3.19

3.15

2.98

2.98

2.79

W 150 × 30

4.11

3.85

3.78

3.59

3.54

3.39

3.35

3.23

W 150 × 37

4.48

4.19

4.12

3.91

3.85

3.69

3.64

3.51

W 200 × 27

4.71

4.41

4.33

4.11

4.05

3.88

3.83

3.69

W 200 × 31

5.02

4.71

4.62

4.39

4.32

4.14

4.09

3.94

W 200 × 36

5.16

4.84

4.75

4.51

4.45

4.26

4.21

4.05

W 200 × 42

5.47

5.13

5.04

4.78

4.71

4.51

4.46

4.30

W 250 × 33

5.82

5.46

5.36

5.09

5.01

4.80

4.74

4.54

W 250 × 39

6.24

5.85

5.74

5.45

5.37

5.14

5.08

4.90

W 250 × 49

6.58

6.17

6.06

5.75

5.67

5.43

5.36

5.17

W 310 × 39

7.01

6.56

6.45

6.12

6.03

5.78

5.70

5.47

W 310 × 45

7.37

6.91

6.78

6.44

6.35

6.08

6.00

5.79

Table A-28 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Exterior Stud Walls with Brick Veneer – 3.0 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

3.0

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

2.64

2.53

2.48

2.39

2.35

2.28

2.24

2.18

W 150 × 30

2.97

2.85

2.78

2.69

2.64

2.56

2.52

2.45

W 150 × 37

3.23

3.10

3.03

2.93

2.87

2.79

2.74

2.67

W 200 × 27

3.40

3.26

3.19

3.08

3.02

2.93

2.88

2.81

W 200 × 31

3.63

3.48

3.40

3.28

3.22

3.13

3.08

3.00

W 200 × 36

3.73

3.58

3.50

3.38

3.31

3.21

3.16

3.08

W 200 × 42

3.96

3.79

3.71

3.58

3.51

3.41

3.35

3.26

W 250 × 33

4.21

4.03

3.94

3.81

3.74

3.62

3.57

3.47

W 250 × 39

4.51

4.32

4.23

4.08

4.00

3.88

3.82

3.72

W 250 × 49

4.76

4.56

4.46

4.30

4.22

4.10

4.03

3.93

W 310 × 39

5.06

4.85

4.74

4.58

4.49

4.36

4.29

4.18

W 310 × 45

5.33

5.11

4.99

4.82

4.73

4.59

4.51

4.40

W 310 × 52

5.66

5.43

5.31

5.12

5.03

4.88

4.80

4.67

W 310 × 60

5.81

5.57

5.45

5.26

5.16

5.01

4.93

4.80

W 360 × 33

5.01

4.81

4.70

4.54

4.45

4.32

4.25

4.14

W 360 × 39

5.38

5.15

5.04

4.86

4.77

4.63

4.56

4.44

W 360 × 45

5.71

5.47

5.35

5.16

5.07

4.92

4.84

4.71

W 360 × 51

5.99

5.74

5.61

5.42

5.32

5.16

5.08

4.94

W 360 × 57

6.26

6.00

5.87

5.66

5.56

5.39

5.31

5.17

Table A-29 Maximum Spans for Steel Beams Supporting a Roof and one Floor in Dwelling Units Where Beams Support Interior Stud Walls or Exterior Stud Walls with Siding – 3.0 kPa Specified Roof Design Snow Load Forming Part of Sentence 9.23.4.3 (1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Column 9

Maximum Span, m

Roof Live Load, kPa

3.0

Supported Roof Length, m

2.4

3.6

4.8

6.0

Supported Floor Length, m

2.4

3.6

2.4

3.6

2.4

3.6

2.4

3.6

Steel Beam Section

W 150 × 22

3.53

3.33

3.23

3.08

3.01

2.85

2.83

2.66

W 150 × 30

3.97

3.74

3.63

3.47

3.38

3.26

3.19

3.09

W 150 × 37

4.32

4.07

3.95

3.77

3.68

3.55

3.48

3.37

W 200 × 27

4.54

4.28

4.15

3.97

3.87

3.73

3.65

3.52

W 200 × 31

4.85

4.57

4.43

4.23

4.13

3.98

3.90

3.78

W 200 × 36

4.98

4.70

4.56

4.35

4.25

4.09

4.01

3.88

W 200 × 42

5.28

4.98

4.83

4.61

4.50

4.34

4.25

4.12

W 250 × 33

5.62

5.30

5.14

4.91

4.79

4.61

4.52

4.33

W 250 × 39

6.02

5.67

5.51

5.26

5.13

4.94

4.84

4.69

W 250 × 49

6.35

5.99

5.81

5.55

5.42

5.21

5.11

4.95

W 310 × 39

6.76

6.37

6.18

5.90

5.76

5.55

5.44

5.21

W 310 × 45

7.11

6.71

6.51

6.21

6.07

5.84

5.72

5.54

9.23.4.4. — Concrete Topping

(1) Except as permitted in Sentence (2), where a floor is required to support a concrete topping, the joist spans shown in Table A-1 or the spacing of the members shall be reduced to allow for the loads due to the topping.

(2) Where a floor is required to support a concrete topping, joist spans are permitted to be selected from Table A-2 provided the concrete,

(a) is 38 to 51 mm thick,

(b) is normal weight,

(c) is placed directly on the subflooring, and

(d) has not less than 20 MPa compressive strength after 28 days.

(3) Where a floor is required to support a concrete topping not more than 51 mm thick, the beam spans shown in Tables A-8 to A-11 shall be multiplied by 0.8 or the supported length of the floor joists shall be reduced to allow for the loads due to the topping.

Editor's note

In the 'Maximum Spans for Floor Joists - Special Cases' table (Table A-2) under Article 9.23.4.4., the as-filed O. Reg. 350/06 contains several typographical anomalies that this map reproduces as filed: the Column 8 header cell is blank ('Col.'; it is Column 8 by position), one lumber-grade label reads 'No .1' with a misplaced space, and another reads 'No 3' with the period omitted. In the table notes, the '(1)' and '(2)' reference markers appear as plain text. The consolidated e-Laws version silently supplies the missing characters, superscripts the note markers, and bolds the notes heading; none of these changes was enacted by an amending regulation.

Text · e-Laws consolidated snapshot

Table A-2 Maximum Spans for Floor Joists – Special Cases(1) Forming Part of Sentence 9.23.4.2.(1) and 9.23.4.4.(2)

Column 1

Column 2

Column 3

Col. 4

Col. 5

Col. 6

Col. 7

Col.

Col. 9

Col. 10

Col. 11

Col. 12

Commercial Designation

Grade

Joist Size, mm

Maximum Span, m

Joists with Ceilings Attached to Wood Furring

Joists with Concrete Topping

Without Bridging

With Bridging

With or Without Bridging(2)

Joist Spacing, mm

Joist Spacing, mm

Joist Spacing, mm

300

400

600

300

400

600

300

400

600

Douglas Fir – Larch (includes Douglas Fir and Western Larch)

Select

38 × 89

2.19

1.99

1.73

2.19

1.99

1.73

2.19

1.99

1.73

Structural

38 × 140

3.44

3.12

2.73

3.44

3.12

2.73

3.44

3.12

2.73

38 × 184

4.24

3.99

3.59

4.52

4.11

3.59

4.52

4.11

3.59

38 × 235

4.98

4.69

4.29

5.47

5.20

4.58

5.77

5.24

4.58

38 × 286

5.67

5.34

4.88

6.19

5.89

5.54

6.83

6.37

5.58

No. 1 and

38 × 89

2.09

1.90

1.66

2.09

1.90

1.66

2.09

1.90

1.66

No. 2

38 × 140

3.29

2.99

2.62

3.29

2.99

2.62

3.29

2.99

2.55

38 × 184

4.06

3.83

3.44

4.33

3.93

3.44

4.33

3.81

3.11

38 × 235

4.78

4.50

4.11

5.24

4.98

4.31

5.37

4.65

3.80

38 × 286

5.44

5.12

4.68

5.93

5.64

5.00

6.24

5.40

4.41

No. 3

38 × 89

1.95

1.69

1.38

1.95

1.69

1.38

1.72

1.49

1.21

38 × 140

2.78

2.41

1.97

2.78

2.41

1.97

2.45

2.12

1.73

38 × 184

3.38

2.93

2.39

3.38

2.93

2.39

2.98

2.58

2.11

38 × 235

4.14

3.58

2.93

4.14

3.58

2.93

3.65

3.16

2.58

38 × 286

4.80

4.16

3.39

4.80

4.16

3.39

4.23

3.66

2.99

Construction

38 × 89

2.03

1.84

1.61

2.03

1.84

1.61

2.03

1.84

1.61

Standard

38 × 89

1.88

1.63

1.33

1.88

1.63

1.33

1.66

1.44

1.17

Hem – Fir (includes Western Hemlock and Amabilis Fir)

Select

38 × 89

2.16

1.96

1.71

2.16

1.96

1.71

2.16

1.96

1.71

Structural

38 × 140

3.39

3.08

2.69

3.39

3.08

2.69

3.39

3.08

2.69

38 × 184

4.18

3.94

3.54

4.46

4.05

3.54

4.46

4.05

3.54

38 × 235

4.92

4.63

4.23

5.39

5.13

4.52

5.69

5.17

4.52

38 × 286

5.60

5.27

4.82

6.10

5.81

5.47

6.74

6.28

5.50

No .1 and

38 × 89

2.09

1.90

1.66

2.09

1.90

1.66

2.09

1.90

1.66

No. 2

38 × 140

3.29

2.99

2.62

3.29

2.99

2.62

3.29

2.99

2.62

38 × 184

4.06

3.83

3.44

4.33

3.93

3.44

4.33

3.93

3.26

38 × 235

4.78

4.50

4.11

5.24

4.98

4.39

5.53

4.88

3.99

38 × 286

5.44

5.12

4.68

5.93

5.64

5.25

6.54

5.66

4.63

No 3

38 × 89

2.03

1.84

1.61

2.03

1.84

1.61

2.03

1.83

1.50

38 × 140

3.19

2.90

2.43

3.19

2.90

2.43

3.02

2.62

2.14

38 × 184

3.94

3.61

2.95

4.17

3.61

2.95

3.68

3.18

2.60

38 × 235

4.63

4.36

3.61

5.08

4.42

3.61

4.50

3.89

3.18

38 × 286

5.27

4.96

4.19

5.74

5.13

4.19

5.22

4.52

3.69

Construction

38 × 89

2.03

1.84

1.61

2.03

1.84

1.61

2.03

1.84

1.61

Standard

38 × 89

1.96

1.71

1.39

1.96

1.71

1.39

1.74

1.50

1.23

Spruce – Pine – Fir (includes Spruce (all species except Coast Sitka Spruce) Jack Pine, Lodgepole Pine, Balsam Fir and Alpine Fir)

Select

38 × 89

2.06

1.87

1.64

2.06

1.87

1.64

2.06

1.87

1.64

Structural

38 × 140

3.24

2.95

2.57

3.24

2.95

2.57

3.24

2.95

2.57

38 × 184

4.00

3.77

3.38

4.26

3.87

3.38

4.26

3.87

3.38

38 × 235

4 70

4.43

4.05

5.16

4.91

4.32

5.45

4.95

4.32

38 × 286

5.35

5.04

4.61

5.84

5.55

5.23

6.45

6.01

5.26

No. 1 and

38 × 89

1.99

1.81

1.58

1.99

1.81

1.58

1.99

1.81

1.58

No. 2

38 × 140

3.14

2.85

2.49

3.14

2.85

2.49

3.14

2.85

2.49

38 × 184

3.87

3.64

3.27

4.12

3.75

3.27

4.12

3.75

3.27

38 × 235

4.55

4.28

3.91

4.99

4.75

4.18

5.27

4.79

4.13

38 × 286

5.18

4.88

4.46

5.65

5.37

5.06

6.23

5.81

4.79

No. 3

38 × 89

1.96

1.78

1.55

1.96

1.78

1.55

1.96

1.78

1.50

38 × 140

3.08

2.80

2.43

3.08

2.80

2.43

3.02

2.62

2.14

38 × 184

3.80

3.58

2.95

4.05

3.61

2.95

3.68

3.18

2.60

38 × 235

4.47

4.21

3.61

4.90

4.42

3.61

4.50

3.89

3.18

38 × 286

5.09

4.79

4.19

5.55

5.13

4.19

5.22

4.52

3.69

Construction

38 × 89

1.96

1.78

1.55

1.96

1.78

1.55

1.96

1.78

1.55

Standard

38 × 89

1.88

1.71

1.44

1.88

1.71

1.44

1.80

1.56

1.27

Northern Species (includes any Canadian Species covered by the NLGA Standard Grading Rules

Select

38 × 89

1.84

1.68

1.46

1.84

1.68

1.46

1.84

1.68

1.46

Structural

38 × 140

2.90

2.63

2.30

2.90

2.63

2.30

2.90

2.63

2.30

38 × 184

3.58

3.37

3.03

3.81

3.46

3.03

3.81

3.46

3.03

38 × 235

4.20

3.96

3.62

4.61

4.39

3.86

4.87

4.42

3.86

38 × 286

4.79

4.51

4.12

5.22

4.96

4.68

5.76

5.37

4.54

No. 1 and

38 × 89

1.80

1.64

1.43

1.80

1.64

1.43

1.80

1.64

1.43

No. 2

38 × 140

2.83

2.57

2.25

2.83

2.57

2.25

2.83

2.57

2.23

38 × 184

3.50

3.29

2.96

3.72

3.38

2.96

3.72

3.32

2.71

38 × 235

4.11

3.87

3.54

4.51

4.29

3.76

4.69

4.06

3.31

38 × 286

4.68

4.40

4.03

5.10

4.85

4.36

5.44

4.71

3.84

No. 3

38 × 89

1.76

1.60

1.36

1.76

1.60

1.36

1.70

1.47

1.20

38 × 140

2.75

2.38

1.94

2.75

2.38

1.94

2.42

2.10

1.71

38 × 184

3.35

2.90

2.37

3.35

2.90

2.37

2.95

2.55

2.08

38 × 235

4.01

3.54

2.89

4.09

3.54

2.89

3.61

3.12

2.55

38 × 286

4.56

4.11

3.36

4.75

4.11

3.36

4.18

3.62

2.96

Construction

38 × 89

1.76

1.60

1.40

1.76

1.60

1.40

1.76

1.60

1.37

Standard

38 × 89

1.63

1.41

1.15

1.63

1.41

1.15

1.44

1.25

1.02

Notes to Table A-2:

(1)Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load on the floor does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

(2)No bridging is assumed for spans for floor joists with concrete topping.

9.23.4.5. — Heavy Roofing Materials

(1) Where a roof is required to support an additional uniform dead load from roofing materials such as concrete roofing tile, or materials other than as specified in Section 9.26., such as clay roofing tiles, the additional load shall be allowed for by reducing,

(a) the spans for roof joists and rafters in Tables A-4 to A-7, or the spacing of the members, and

(b) the spans for ridge beams and lintels in Tables A-12 to A-16.

Text · e-Laws consolidated snapshot

9.23.5. — Notching and Drilling

Content not available for this version.

9.23.5.1. — Holes Drilled in Framing Members

(1) Holes drilled in roof, floor or ceiling framing members shall be not larger than one-quarter the depth of the member and shall be located not less than 50 mm from the edges, unless the depth of the member is increased by the size of the hole.

Text · e-Laws consolidated snapshot

9.23.5.2. — Notching of Framing Members

(1) Floor, roof and ceiling framing members are permitted to be notched provided the notch is located on the top of the member within half the joist depth from the edge of bearing and is not deeper than one-third the joist depth, unless the depth of the member is increased by the size of the notch.

Text · e-Laws consolidated snapshot

9.23.5.3. — Wall Studs

(1) Wall studs shall not be notched, drilled or otherwise damaged so that the undamaged portion of the stud is less than two-thirds the depth of the stud if the stud is loadbearing or 40 mm if the stud is non-loadbearing, unless the weakened studs are suitably reinforced.

Text · e-Laws consolidated snapshot

9.23.5.4. — Top Plates

(1) Top plates in walls shall not be notched, drilled or otherwise weakened to reduce the undamaged width to less than 50 mm unless the weakened plates are suitably reinforced.

Text · e-Laws consolidated snapshot

9.23.5.5. — Roof Trusses

(1) Roof truss members shall not be notched, drilled or otherwise weakened unless such notching or drilling is allowed for in the design of the truss.

Text · e-Laws consolidated snapshot

9.23.6. — Anchorage

Content not available for this version.

9.23.6.1. — Anchorage of Building Frames

(1) Building frames shall be anchored to the foundation unless a structural analysis of wind and earth pressures shows anchorage is not required.

(2) Except as provided in Article 9.23.6.3., anchorage shall be provided by embedding the ends of the first floor joists in concrete, or fastening the sill plate to the foundation with not less than 12.7 mm diam anchor bolts spaced not more than 2 400 mm o.c.

(3) Anchor bolts referred to in Sentence (2) shall be fastened to the sill plate with nuts and washers and shall be embedded not less than 100 mm in the foundation and so designed that they may be tightened without withdrawing them from the foundation.

Text · e-Laws consolidated snapshot

9.23.6.2. — Anchorage of Columns and Posts

(1) Except as provided in Sentences (2) and (3), exterior columns and posts shall be anchored to resist uplift and lateral movement.

(2) Except as provided in Sentence (3), where columns or posts support balconies, decks, verandas and other exterior platforms, and the columns or posts extend not more than 600 mm above finished ground level, the supported joists or beams shall be,

(a) anchored to a foundation to resist uplift and lateral movement, or

(b) directly anchored to the ground to resist uplift.

(3) Anchorage is not required for platforms described in Sentence (2) that,

(a) are not more than 1 storey,

(b) are not more than 55 m² in area,

(c) do not support a roof, and

(d) are not attached to another structure, unless it can be demonstrated that differential movement will not adversely affect the performance of that structure.

Text · e-Laws consolidated snapshot

9.23.6.3. — Anchorage of Smaller Buildings

(1) Buildings not more than 4.3 m wide and not more than 1 storey in building height are permitted to be anchored in conformance with the requirements of CAN/CSA-Z240.10.1, “Site Preparation, Foundation and Anchorage of Mobile Homes”.

Text · e-Laws consolidated snapshot

9.23.7. — Sill Plates

Content not available for this version.

9.23.7.1. — Size of Sill Plates

(1) Where sill plates provide bearing for the floor system they shall be not less than 38 mm by 89 mm material.

Text · e-Laws consolidated snapshot

9.23.7.2. — Levelling of Sill Plates

(1) Sill plates shall be,

(a) levelled by setting them on a full bed of mortar, or

(b) laid directly on the foundation where the top of the foundation is level.

(2) The joint between the sill plate for exterior walls and the foundation shall be sealed in accordance with Subsection 9.25.3.v1

Text · e-Laws consolidated snapshot

9.23.8. — Beams to Support Floors

Content not available for this version.

9.23.8.1. — Bearing for Beams

(1) Beams shall have even and level bearing and shall have not less than 89 mm length of bearing at end supports, except as required in notes to Tables A-8 to A-11.

Text · e-Laws consolidated snapshot

9.23.8.2. — Priming of Steel Beams

(1) Exterior steel beams susceptible to corrosion shall be shop primed with rust-inhibitive paint.

Text · e-Laws consolidated snapshot

9.23.8.3. — Built-up Wood Beams

(1) Where a beam is made up of individual pieces of lumber that are nailed together, the individual members shall be 38 mm or greater in thickness and installed on edge.

(2) Except as permitted in Sentence (3), where individual members of a built-up beam are butted together to form a joint, the joint shall occur over a support.

(3) Where a beam is continuous over more than 1 span, individual members are permitted to be butted together to form a joint at or within 150 mm of the end quarter points of the clear spans, provided the quarter points are not those closest to the ends of the beam.

(4) Members joined at quarter points shall be continuous over adjacent supports.

(5) Joints in individual members of a beam that are located at or near the end quarter points shall not occur in adjacent members at the same quarter point and shall not reduce the effective beam width by more than half.

(6) Not more than 1 butt joint shall occur in any individual member of a built-up beam within any one span.

(7) Except as provided in Sentence (8), where 38 mm members are laid on edge to form a built-up beam, individual members shall be nailed together with a double row of nails not less than 89 mm in length, spaced not more than 450 mm apart in each row with the end nails located 100 mm to 150 mm from the end of each piece.

(8) Where 38 mm members in built-up wood beams are not nailed together as provided in Sentence (7), they shall be bolted together with not less than 12.7 mm diam bolts equipped with washers and spaced not more than 1 200 mm o.c., with the end bolts located not more than 600 mm from the ends of the members.

Text · e-Laws consolidated snapshot

9.23.9. — Floor Joists

Content not available for this version.

9.23.9.1. — End Bearing for Joists

(1) Except when supported on ribbon boards, floor joists shall have not less than 38 mm length of end bearing.

(2) Ribbon boards referred to in Sentence (1) shall be not less than 19 mm by 89 mm lumber let into the studs.

Text · e-Laws consolidated snapshot

9.23.9.2. — Joists Supported by Beams

(1) Floor joists may be supported on the tops of beams or may be framed into the sides of beams.

(2) When framed into the side of a wood beam, joists referred to in Sentence (1) shall be supported on,

(a) joist hangers or other acceptable mechanical connectors, or

(b) not less than 38 mm by 64 mm ledger strips nailed to the side of the beam, except that 38 mm by 38 mm ledger strips may be used provided each joist is nailed to the beam by at least four 89 mm nails, in addition to the nailing for the ledger strip required in Table 9.23.3.4.

(3) When framed into the side of a steel beam, joists referred to in Sentence (1) shall be supported on the bottom flange of the beam or on not less than 38 mm by 38 mm lumber bolted to the web with not less than 6.3 mm diam bolts spaced not more than 600 mm apart.

(4) Joists referred to in Sentence (3) shall be spliced above the beam with not less than 38 mm by 38 mm lumber at least 600 mm long to support the flooring.

(5) Not less than a 12 mm space shall be provided between the splice required in Sentence (4) and the beam to allow for shrinkage of the wood joists.

Text · e-Laws consolidated snapshot

9.23.9.3. — Restraint of Joist Bottoms

(1) Except as provided in Sentence 9.23.9.4.(1), bottoms of floor joists shall be restrained from twisting at each end by toe-nailing to the supports, end-nailing to the header joists or by providing continuous strapping, blocking between the joists or cross-bridging near the supports.

Text · e-Laws consolidated snapshot

9.23.9.4. — Strapping and Bridging in Tables A-1 and A-2

(1) Except as permitted by Sentence (5), where strapping is specified in Table A-1, it shall be,

(a) not less than 19 mm by 64 mm, nailed to the underside of floor joists,

(b) located not more than 2 100 mm from each support or other rows of strapping, and

(c) fastened at each end to a sill or header.

(2) Where bridging is specified in Table A-1, it shall consist of not less than 19 mm by 64 mm or 38 mm by 38 mm cross bridging located not more than 2 100 mm from each support or other rows of bridging.

(3) Where bridging and strapping are specified in Tables A-1,

(a) bridging shall,

(i) comply with Sentence (2), or

(ii) consist of 38 mm solid blocking located not more than 2 100 mm from each support or other rows of bridging and securely fastened between the joists, and

(b) except as provided in Sentence (5), strapping shall comply with Sentence (1) and be installed under the bridging.

(4) Bridging specified in Table A-2 shall consist of,

(a) bridging as described in Sentence (2), or

(b) 38 mm solid blocking located not more than 2 100 mm from each support or other rows of bridging and securely fastened between the joists.

(5) Strapping described in Sentence (1) and Clause (3)(b) is not required where,

(a) furring strips complying with Table 9.29.3.1. are fastened directly to the joists, or

(b) a panel-type ceiling finish complying with Subsection 9.29.5., 9.29.6., 9.29.7., 9.29.8., or 9.29.9. is attached directly to the joists.

(6) Where a ceiling attached to wood furring is specified in Table A-2,

(a) the ceiling finish shall consist of gypsum board, plywood or OSB not less than 12.7 mm thick, and

(b) the furring shall be,

(i) 19 mm by 89 mm wood furring spaced at not more than 600 mm o.c., or

(ii) 19 mm by 64 mm wood furring spaced at not more than 400 mm o.c.

Text · e-Laws consolidated snapshot

9.23.9.5. — Header Joists

(1) Header joists around floor openings shall be doubled when they exceed 1 200 mm in length.

(2) The size of header joists exceeding 3.2 m in length shall be determined by calculations.

Text · e-Laws consolidated snapshot

9.23.9.6. — Trimmer Joists

(1) Trimmer joists around floor openings shall be doubled when the length of the header joist exceeds 800 mm.

(2) When the header joist exceeds 2 000 mm in length the size of the trimmer joists shall be determined by calculations.

Text · e-Laws consolidated snapshot

9.23.9.7. — Support of Tail and Header Joists

(1) When tail joists and header joists are supported by the floor framing, they shall be supported by suitable joist hangers or nailing in accordance with Table 9.23.3.4.

Text · e-Laws consolidated snapshot

9.23.9.8. — Support of Walls

(1) Non-loadbearing walls parallel to the floor joists shall be supported by joists beneath the wall or on blocking between the joists.

(2) Blocking referred to in Sentence (1) for the support of non-loadbearing walls shall be not less than 38 mm by 89 mm lumber, spaced not more than 1 200 mm apart.

(3) Non-loadbearing interior walls at right angles to the floor joists are not restricted as to location.

(4) Loadbearing interior walls parallel to floor joists shall be supported by beams or walls of sufficient strength to transfer safely the design loads to vertical supports.

(5) Loadbearing interior walls at right angles to floor joists shall be located not more than 900 mm from the joist support when the wall does not support a floor, and not more than 600 mm from the joist support when the wall supports one or more floors, unless the joist size is designed to support such loads.

Text · e-Laws consolidated snapshot

9.23.9.9. — Cantilevered Floor Joists

(1) Floor joists supporting roof loads shall not be cantilevered more than 400 mm beyond their supports where 38 mm by 184 mm joists are used and not more than 600 mm beyond their supports where 38 mm by 235 mm or larger joists are used.

(2) The cantilevered portions referred to in Sentence (1) shall not support floor loads from other storeys unless calculations are provided to show that the design resistances of the cantilevered joists are not exceeded.

(3) Where cantilevered floor joists described in Sentences (1) and (2) are at right angles to the main floor joists, the tail joists in the cantilevered portion shall,

(a) extend inward away from the cantilever support a distance equal to not less than 6 times the length of the cantilever, and

(b) shall be end nailed to an interior doubled header joist in conformance with Table 9.23.3.4.

Text · e-Laws consolidated snapshot

9.23.10. — Wall Studs

Content not available for this version.

9.23.10.1. — Stud Size and Spacing

(1) Except as provided in Sentence (2), the size and spacing of studs shall conform to Table 9.23.10.1.

(2) Studs for walls not listed in Table 9.23.10.1. and supporting roof loads shall conform to Table A-30 to A-33, provided,

(a) the studs are clad with not less than 9.5 mm thick plywood, OSB or waferboard sheathing on the exterior face, and not less than 12.5 mm gypsum board on the interior face,

(b) solid bridging is provided at not more than 1 200 mm on centre,

(c) the studs are fastened to the top and bottom plates with no fewer than three 82 mm toe-nails,

(d) the double top plates are fastened together with not less than 76 mm nails spaced not more than 200 mm on centre,

(e) roof framing members spaced not more than 600 mm are fastened to the top plates with no fewer than four 82 mm toe-nails, and

(f) the bottom plate is fastened to the floor joists, blocking or rim joist with not less than 82 mm nails spaced not more than 200 mm on centre.

Editor's note

In the appendix tables for Article 9.23.10.1. (Table A-30 through Table A-33, Maximum Spans for Roof Joists and Rafters), the note markers '(1)' to '(4)' are superscripts each followed by a space and the headnotes are in plain weight, as filed in O. Reg. 350/06; the e-Laws consolidation removes the space after each marker, sets the headnotes in bold, and renders the markers of Tables A-30 to A-32 as plain text (those of Table A-33 remain superscript). The Table A-30 column heading also reads 'DesignSnow' run together as filed (a missing space), which this map reproduces; the e-Laws consolidation supplies the space ('Design Snow'). The table content is otherwise identical and none of these changes was enacted by an amending regulation.

Text · e-Laws consolidated snapshot

Table 9.23.10.1. Size and Spacing of Studs Forming Part of Sentence 9.23.10.1.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Type of Wall

Supported Loads (including dead loads)

Minimum Stud Size, mm

Maximum Stud Spacing, mm

Maximum Unsupported Height, m

Interior

No load

38 × 38

400

2.4

38 × 89 flat(1)

400

3.6

Attic not accessible by a stairway

38 × 64

600

3.0

38 × 64 flat(1)

400

2.4

38 × 89

600

3.6

38 × 89 flat(1)

400

2.4

Attic accessible by a stairway plus one floor Roof load plus one floor Attic not accessible by stairway plus 2 floors

38 × 89

400

3.6

Roof load,

Attic accessible by a stairway

38 × 64

400

2.4

Attic not accessible by a stairway plus one floor

38 × 89

600

3.6

Attic accessible by a stairway plus 2 floors Roof load plus 2 floors

38 × 89

300

3.6

64 × 89

400

3.6

38 × 140

400

4.2

Attic accessible by a stairway plus 3 floors Roof load plus 3 floors

38 × 140

300

4.2

Exterior

Roof with or without attic storage

38 × 64

400

2.4

38 × 89

600

3.0

Roof with or without attic storage plus one floor

38 × 89

400

3.0

38 × 140

600

3.0

Roof with or without attic storage plus 2 floors

38 × 89

300

3.0

64 × 89

400

3.0

38 × 140

400

3.6

Roof with or without attic storage plus 3 floors

38 × 140

300

1.8

Notes to Table 9.23.10.1.:

(1)See Article 9.23.10.3.

Table A-30 Sizes for Spruce-Pine-Fir No. 2 Grade Exterior Wall Studs with Brick Veneer Forming Part of Sentence 9.23.10.1.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Stud Size and Spacing

Wind Pressure, kPa

q30

0.4

0.5

0.55

q10

0.3

0.4

0.46

Specified Roof DesignSnow Load, kPa

Stud Length, m

Supported Roof Length, m

Supported Roof Length, m

Supported Roof Length, m

3.0

6.0

3.0

6.0

3.0

6.0

1.0

3.8

A

A

A

A

A

A

4.2

A

A

B

B

B

B

4.6

B

B

C

C

C

C

5.0

C

C

C

C

D

D

5.3

C

C

D

D

D

D

5.6

C

C

D

D

1.5

3.8

A

A

A

A

A

A

4.2

A

A

B

B

B

B

4.6

B

B

C

C

C

C

5.0

C

C

C

C

D

D

5.3

C

C

D

D

D

D

5.6

C

C

D

D

2.0

3.8

A

A

A

A

A

A

4.2

A

A

B

B

B

B

4.6

B

B

C

C

C

C

5.0

C

C

C

C

D

D

5.3

C

C

D

D

D

D

5.6

C

C

D

D

2.5

3.8

A

A

A

A

A

A

4.2

A

A

B

B

B

B

4.6

B

B

C

C

C

C

5.0

C

C

C

C

D

D

5.3

C

C

D

D

D

D

5.6

C

C

D

D

3.0

3.8

A

A

A

A

A

A

4.2

A

A

B

B

B

B

4.6

B

B

C

C

C

C

5.0

C

C

C

C

D

D

5.3

C

C

D

D

D

D

5.6

C

C

D

D

Legend – Stud Size and Spacing

A = 38 × 140 mm at 400 mm on centre C = two 38 × 140 mm studs at 400 mm centre

B = 38 × 140 mm at 300 mm on centre D = two 38 × 140 mm studs at 300 mm centre

Notes to Table A‑30:

(1) A roof dead load of 0.62 kPa has been assumed.

(2) It is assumed that the double top plate is rigid enough to distribute the roof load equally to the studs regardless of spacing.

(3) Solid bridging shall be provided at 1 200 mm on centre.

(4) The studs shall have a minimum of 9.5 mm plywood, waferboard or OSB sheathing on the exterior face and 12.5 mm gypsum board on the interior face.

Table A-31 Sizes for Spruce-Pine-Fir No. 2 Grade Exterior Wall Studs with Siding Forming Part of Sentence 9.23.10.1.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Stud Size and Spacing

Wind Pressure, kPa

q30

0.4

0.5

0.55

q10

0.3

0.4

0.46

Specified Roof Design Snow Load, kPa

Stud Length, m

Supported Roof Length, m

Supported Roof Length, m

Supported Roof Length, m

3.0

6.0

3.0

6.0

3.0

6.0

1.0

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

A

A

5.0

A

A

A

A

B

B

5.3

A

A

B

B

B

B

5.6

A

A

B

B

C

C

1.5

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

A

A

5.0

A

A

A

A

B

B

5.3

A

A

B

B

B

B

5.6

A

A

B

B

C

C

2.0

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

A

A

5.0

A

A

A

A

B

B

5.3

A

A

B

B

B

B

5.6

A

B

B

B

C

C

2.5

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

A

A

5.0

A

A

A

A

B

B

5.3

A

B

B

B

B

B

5.6

A

B

B

B

C

C

3.0

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

A

A

5.0

A

A

A

B

B

B

5.3

A

B

B

B

B

B

5.6

A

B

B

C

C

C

Legend – Stud Size and Spacing

A = 38 × 140 mm at 400 mm on centre C = two 38 × 140 mm studs at 400 mm centre

B = 38 × 140 mm at 300 mm on centre D = two 38 × 140 mm studs at 300 mm centre

Notes to Table A-31:

(1) A roof dead load of 0.62 kPa has been assumed.

(2) It is assumed that the double top plate is rigid enough to distribute the roof load equally to the studs regardless of spacing.

(3) Solid bridging shall be provided at 1 200 mm on centre.

(4) The studs shall have a minimum of 9.5 mm plywood, waferboard or OSB sheathing on the exterior face and 12.5 mm gypsum board on the interior face.

Table A-32 Sizes for Northern Species No. 2 Grade Exterior Wall Studs with Brick Veneer Forming Part of Sentence 9.23.10.1.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Stud Size and Spacing

Wind Pressure, kPa

q30

0.4

0.5

0.55

q10

0.3

0.4

0.46

Specified Roof Design Snow Load, kPa

Stud Length, m

Supported Roof Length, m

Supported Roof Length, m

Supported Roof Length, m

3.0

6.0

3.0

6.0

3.0

6.0

1.0

3.8

A

A

B

B

B

B

4.2

B

B

C

C

C

C

4.6

C

C

C

C

D

D

5.0

C

C

D

D

5.3

D

D

5.6

1.5

3.8

A

A

B

B

B

B

4.2

B

B

C

C

C

C

4.6

C

C

C

C

D

D

5.0

C

C

D

D

5.3

D

D

5.6

2.0

3.8

A

A

B

B

B

B

4.2

B

B

C

C

C

C

4.6

C

C

C

C

D

D

5.0

C

C

D

D

5.3

D

D

5.6

2.5

3.8

A

A

B

B

B

B

4.2

B

B

C

C

C

C

4.6

C

C

C

C

D

D

5.0

C

C

D

D

5.3

D

D

5.6

3.0

3.8

A

A

B

B

B

B

4.2

B

B

C

C

C

C

4.6

C

C

C

C

D

D

5.0

C

C

D

D

5.3

D

D

5.6

Legend – Stud Size and Spacing

A = 38 × 140 mm at 400 mm on centre C = two 38 × 140 mm studs at 400 mm on centre

B = 38 × 140 mm at 300 mm on centre D = two 38 × 140 mm studs at 300 mm on centre

Notes to Table A-32:

(1) A roof dead load of 0.62 kPa has been assumed.

(2) It is assumed that the double top plate is rigid enough to distribute the roof load equally to the studs regardless of spacing.

(3) Solid bridging shall be provided at 1 200 mm on centre.

(4) The studs shall have a minimum of 9.5 mm plywood, waferboard or OSB sheathing on the exterior face and 12.5 mm gypsum board on the interior side.

Table A-33 Sizes for Northern Species No. 2 Grade Exterior Wall Studs with Siding Forming Part of Sentence 9.23.10.1.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Stud Size and Spacing

Wind Pressure, kPa

q30

0.4

0.5

0.55

q10

0.3

0.4

0.46

Specified Roof Design Snow Load, kPa

Stud Length, m

Supported Roof Length, m

Supported Roof Length, m

Supported Roof Length, m

3.0

6.0

3.0

6.0

3.0

6.0

1.0

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

B

B

5.0

A

A

B

B

C

C

5.3

B

B

C

C

C

C

5.6

C

C

C

C

D

D

1.5

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

A

B

B

5.0

A

B

B

B

C

C

5.3

B

B

C

C

C

C

5.6

C

C

C

C

D

D

2.0

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

A

4.6

A

A

A

B

B

B

5.0

A

B

B

B

C

C

5.3

B

B

C

C

C

C

5.6

C

C

C

C

D

D

2.5

3.8

A

A

A

A

A

A

4.2

A

A

A

A

A

B

4.6

A

B

A

B

B

B

5.0

A

B

B

C

C

C

5.3

B

C

C

C

C

C

5.6

C

C

C

C

D

D

3.0

3.8

A

A

A

A

A

A

4.2

A

A

A

B

A

B

4.6

A

B

A

B

B

B

5.0

A

C

B

C

C

C

5.3

B

C

C

C

C

C

5.6

C

C

C

C

D

D

Legend – Stud Size and Spacing

A = 38 × 140 mm at 400 mm on centre C = two 38 × 140 mm studs at 400 mm on centre

B = 38 × 140 mm at 300 mm on centre D = two 38 × 140 mm studs at 300 mm on centre

Notes to Table A-33:

(1)A roof dead load of 0.62 kPa has been assumed.

(2) It is assumed that the double top plate is rigid enough to distribute the roof load equally to the studs regardless of spacing.

(3)Solid bridging shall be provided at 1.2 m on centre.

(4)The studs shall have a minimum of 9.5 mm plywood, waferboard or OSB sheathing on the exterior face and 12.5 mm gypsum board on the interior face.

9.23.10.2. — Bracing and Lateral Support

(1) Except as provided in Sentence (2), each exterior wall in each storey shall be braced with at least one diagonal brace conforming to Sentence (3).

(2) Bracing is not required where the walls,

(a) have an interior finish conforming to the requirements of Section 9.29., or

(b) where the walls are,

(i) clad with panel-type siding,

(ii) diagonally sheathed with lumber, or

(iii) sheathed with plywood, OSB, waferboard, gypsum or fibreboard sheathing.

(3) Where bracing is required, it shall,

(a) consist of not less than 19 mm by 89 mm wood members,

(b) be applied to the studs at an angle of approximately 45° to the horizontal, and

(c) extend the full height of the wall on each storey.

(4) Bracing described in Sentence (3) shall be nailed to each stud and wall plate by at least two 63 mm nails.

(5) Where loadbearing interior walls are not finished in accordance with Sentence (2), blocking or strapping shall be fastened to the studs at mid-height to prevent sideways buckling.

Text · e-Laws consolidated snapshot

9.23.10.3. — Orientation of Studs

(1) Except as permitted in Sentences (2) and (3), all studs shall be placed at right angles to the wall face.

(2) Studs on the flat are permitted to be used in gable ends of roofs that contain only unfinished space or in non-loadbearing interior walls within the limits described in Article 9.23.10.1.v1

(3) Wall studs that support only a load from an attic not accessible by a stairway are permitted to be placed on the flat within the limits permitted in Article 9.23.10.1.v1 provided,

(a) the studs are clad on at least 1 side with plywood, OSB or waferboard sheathing fastened to the face of the studs with a structural adhesive, and

(b) the portion of the roof supported by the studs does not exceed 2 100 mm in width.

Text · e-Laws consolidated snapshot

9.23.10.4. — Continuity of Studs

(1) Wall studs shall be continuous for the full storey height except at openings and shall not be spliced except by finger-jointing with a structural adhesive.

Text · e-Laws consolidated snapshot

9.23.10.5. — Support for Cladding Materials

(1) Corners and intersections shall be designed to provide adequate support for the vertical edges of interior finishes, sheathing and cladding materials, and in no instance shall exterior corners be framed with less than the equivalent of 2 studs.

(2) Where the vertical edges of interior finishes at wall intersections are supported at vertical intervals by blocking or furring, the vertical distance between such supports shall not exceed the maximum distance between supports specified in Section 9.29.

Text · e-Laws consolidated snapshot

9.23.10.6. — Studs at Sides of Openings

(1) Except as provided in Sentence (2), studs shall be doubled on each side of openings so that the inner studs extend from the lintel to the bottom wall plate and the outer studs extend from the top wall plates to the bottom wall plate.

(2) Single studs are permitted to be used on either side of openings,

(a) in non-loadbearing interior walls not required to have fire-resistance ratings provided the studs extend from the top wall plate to the bottom wall plate, or

(b) in loadbearing or non-loadbearing interior or exterior walls, provided,

(i) the opening is less than and within the required stud spacing, and

(ii) no two such openings of full stud space width are located in adjacent stud spaces.

Text · e-Laws consolidated snapshot

9.23.10.7. — Stud Posts Built into Walls

(1) Except as provided in Sentences (2) and (3), stud posts shall be designed in accordance with Part 4.

(2) The number of studs in a wall directly below a girder truss or roof beam shall conform to Tables A-34 to A-37, provided,

(a) the studs are fastened together to form a post in accordance with Sentence 9.17.4.2.(2),

(b) the wall is not less than 1 200 mm long and sheathed on at least one side with plywood, OSB, waferboard or gypsum sheathing, and

(c) the wall sheathing is fastened to the stud post with at least one row of fasteners conforming to Article 9.23.3.5. and spaced not less than 150 mm on centre.

(3) The width of the stud post shall be not less than the width of the girder or beam that it supports.

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 9.23.10.7. of Division B, which no regulation amends. The notes to its tables (Tables A-34 to A-37) differ from the e-Laws consolidation: the as-filed notes show the note numbers in superscript and the 'Notes to Table ...:' headnotes in plain text, whereas the e-Laws consolidation bolds the headnotes and, at its April 2, 2007 re-render, drops the superscript from the Table A-36 note numbers. The e-Laws consolidation also adds a source-credit line to the notes area of Table A-37 recording the regulations affecting Part 9 ('O. Reg. 350/06, Division B, Part 9', extended on April 2, 2007 to add 'O. Reg. 137/07, ss. 42-66'); this is an e-Laws amendment-history annotation rather than regulation text, and O. Reg. 137/07 does not amend this Article or its tables. In the caption of each of these tables, the as-filed text reads 'Forming Part of Sentence 9.23.10.7 (2)', with a space before the sentence number and no dot after the article number, where the e-Laws consolidation renders it '9.23.10.7.(2)'; this map preserves the as-filed spacing.

Text · e-Laws consolidated snapshot

Table A-34 Minimum Number of 38 × 89 mm Spruce-Pine-Fir Stud Posts in Exterior Stud Walls Supporting Girder Trusses and Roof Beams Forming Part of Sentence 9.23.10.7 (2)

Col. 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Minimum Number of Studs

Stud Height, m

Span of Beam or Girder, m

Specified Roof Design Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

2.4

1

1

2

2

1

2

2

2

1

2

2

3

2

2

3

3

2

2

3

3

3.6

1

2

2

2

2

2

3

3

2

2

3

4

2

3

4

4

2

3

4

5

4.8

2

2

3

3

2

3

3

4

2

3

4

5

3

4

5

3

4

5

6.0

2

2

3

4

2

3

4

5

3

4

5

3

4

3

5

7.2

2

3

4

4

3

4

5

3

4

4

5

4

8.4

2

3

4

5

3

4

5

3

5

4

5

9.6

3

4

5

3

5

4

5

5

10.8

3

4

5

4

5

4

5

12.0

3

4

4

5

3.0

2.4

1

2

2

2

2

2

3

3

2

2

3

4

2

3

4

4

2

3

4

5

3.6

2

2

3

3

2

3

4

4

2

3

4

5

3

4

5

3

4

4.8

2

3

4

4

3

4

5

3

4

4

5

4

6.0

2

3

4

5

3

4

4

5

4

5

7.2

3

4

5

4

5

4

5

8.4

3

4

4

5

9.6

4

5

5

10.8

4

5

12.0

4

Notes to Table A-34:

(1) A roof dead load of 0.62 kPa has been assumed.

(2) Roof beams require a minimum bearing length of 89 mm.

(3) Girder trusses require a minimum bearing length of 89 mm unless otherwise specified by the truss manufacturer.

Table A-35 Minimum Number of 38 × 140 mm Spruce-Pine-Fir Stud Posts in Exterior Stud Walls Supporting Girder Trusses and Roof Beams Forming Part of Sentence 9.23.10.7 (2)

Col. 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Minimum Number of Studs

Stud Height, m

Span of Beam or

Girder, m

Specified Roof Design Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

3.0

2.4

1

1

1

1

1

1

1

1

1

1

1

2

1

1

2

2

1

1

2

2

3.6

1

1

1

1

1

1

2

2

1

1

2

2

1

2

2

2

1

2

2

3

4.8

1

1

2

2

1

2

2

2

1

2

2

3

2

2

3

3

2

2

3

4

6.0

1

1

2

2

1

2

2

3

2

2

3

3

2

2

3

4

2

3

4

4

7.2

1

2

2

2

2

2

3

3

2

2

3

4

2

3

4

4

2

3

4

5

8.4

1

2

2

3

2

2

3

4

2

3

4

4

2

3

4

5

3

4

5

9.6

2

2

3

3

2

3

3

4

2

3

4

5

3

4

5

3

4

5

10.8

2

2

3

3

2

3

4

4

2

3

4

5

3

4

5

3

5

12.0

2

2

3

4

2

3

4

5

3

4

5

3

4

4

5

3.6

2.4

1

1

1

1

1

1

1

2

1

1

2

2

1

1

2

2

1

2

2

2

3.6

1

1

1

2

1

1

2

2

1

2

2

3

1

2

2

3

2

2

3

3

4.8

1

1

2

2

1

2

2

3

2

2

3

3

2

2

3

4

2

3

4

4

6.0

1

2

2

3

2

2

3

3

2

3

3

4

2

3

4

5

2

3

4

5

7.2

1

2

2

3

2

2

3

4

2

3

4

5

2

3

4

5

3

4

5

8.4

2

2

3

3

2

3

4

4

2

3

4

5

3

4

5

3

4

9.6

2

2

3

4

2

3

4

5

3

4

5

3

4

4

5

10.8

2

3

3

4

2

3

4

5

3

4

5

3

5

4

12.0

2

3

4

5

3

4

5

3

5

4

5

4

Notes to Table A-35:

(1) A roof dead load of 0.62 kPa has been assumed.

(2) Roof beams require a minimum bearing length of 140 mm.

(3) Girder trusses require a minimum bearing length of 140 mm unless otherwise specified by the truss manufacturer.

Table A-36 Minimum Number of 38 × 89 mm Northern Species Stud Posts in Exterior Stud Walls Supporting Girder Trusses and Roof Beams Forming Part of Sentence 9.23.10.7 (2)

Col. 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Minimum Number of Studs

Stud Height, m

Span of Beam or Girder, m

Specified Roof Design Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

2.4

1

2

2

2

2

2

3

3

2

2

3

4

2

3

4

4

2

3

4

5

3.6

2

2

3

3

2

3

4

4

2

3

4

5

3

4

5

3

4

4.8

2

3

4

4

3

4

5

3

4

4

5

4

6.0

2

3

4

5

3

4

4

5

4

5

7.2

3

4

5

4

5

4

5

8.4

3

4

4

5

9.6

4

5

5

10.8

4

5

12.0

4

3.0

2.4

2

2

3

3

2

3

3

4

2

3

4

5

3

4

5

3

4

3.6

2

3

4

5

3

4

5

3

5

4

5

4

4.8

3

4

5

3

5

4

5

6.0

3

5

4

5

7.2

4

5

5

8.4

4

9.6

5

10.8

5

12.0

Notes to Table A-36:

(1)A roof dead load of 0.62 kPa has been assumed.

(2)Roof beams require a minimum bearing length of 89 mm.

(3)Girder trusses require a minimum bearing length of 89 mm unless otherwise specified by the truss manufacturer.

Table A-37 Minimum Number of 38 × 140 mm Northern Species Stud Posts in Exterior Stud Walls Supporting Girder Trusses and Roof Beams Forming Part of Sentence 9.23.10.7 (2)

Col. 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Minimum Number of Studs

Stud Height, m

Span of Beam or Girder, m

Specified Roof Design Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

Supported Length, m

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

2.4

3.6

4.8

6.0

3.0

2.4

1

1

1

1

1

1

2

2

1

1

2

2

1

2

2

2

1

2

2

3

3.6

1

1

2

2

1

2

2

2

1

2

2

3

2

2

3

3

2

3

3

4

4.8

1

2

2

2

2

2

3

3

2

2

3

4

2

3

4

4

2

3

4

5

6.0

1

2

2

3

2

2

3

4

2

3

4

5

2

3

4

5

3

4

5

7.2

2

2

3

3

2

3

4

4

2

3

4

5

3

4

5

3

5

8.4

2

3

3

4

2

3

4

5

3

4

5

3

5

4

5

9.6

2

3

4

4

3

4

5

3

4

4

5

4

10.8

2

3

4

5

3

4

5

3

5

4

5

12.0

2

3

4

5

3

4

4

5

4

5

3.6

2.4

1

1

1

2

1

1

2

2

1

2

2

3

1

2

2

3

2

2

3

3

3.6

1

2

2

2

1

2

2

3

2

2

3

4

2

3

3

4

2

3

4

5

4.8

1

2

2

3

2

2

3

4

2

3

4

5

2

3

4

5

3

4

5

6.0

2

2

3

4

2

3

4

5

3

4

5

3

4

5

3

5

7.2

2

3

3

4

2

3

4

5

3

4

5

3

5

4

8.4

2

3

4

5

3

4

5

3

5

4

4

9.6

2

3

4

5

3

4

4

5

4

5

10.8

3

4

5

3

5

4

5

12.0

3

4

5

4

5

5

5

Notes to Table A-37:

(1)  A roof dead load of 0.62 kPa has been assumed.

(2)  Roof beams require a minimum bearing length of 140 mm.

(3)  Girder trusses require a minimum bearing length of 140 mm unless otherwise specified by the truss manufacturer.

9.23.11. — Wall Plates

Content not available for this version.

9.23.11.1. — Size of Wall Plates

(1) Except as provided in Sentence (2), wall plates shall be,

(a) not less than 38 mm thick, and

(b) not less than the required width of the wall studs.

(2) In non-loadbearing walls and in loadbearing walls where the studs are located directly over framing members, the bottom wall plate may be 19 mm thick.

Text · e-Laws consolidated snapshot

9.23.11.2. — Bottom Wall Plates

(1) A bottom wall plate shall be provided in all cases.

(2) The bottom plate in exterior walls shall not project more than one third the plate width over the support.

Text · e-Laws consolidated snapshot

9.23.11.3. — Top Plates

(1) Except as permitted in Sentences (2) to (4), no fewer than 2 top plates shall be provided in loadbearing walls.

(2) A single top plate is permitted to be used in a section of a loadbearing wall containing a lintel provided the top plate forms a tie across the lintel.

(3) A single top plate is permitted to be used in loadbearing walls where the concentrated loads from ceilings, floors and roofs are not more than 50 mm to one side of the supporting studs and in all non-loadbearing walls.

(4) The top plates need not be provided in a section of loadbearing wall containing a lintel provided the lintel is tied to the adjacent wall section with,

(a) not less than 75 mm by 150 mm by 0.91 mm thick galvanized steel, or

(b) 19 mm by 89 mm by 300 mm wood splice nailed to each wall section with at least three 63 mm nails.

Text · e-Laws consolidated snapshot

9.23.11.4. — Joints in Top Plates

(1) Joints in the top plates of loadbearing walls shall be staggered not less than one stud spacing.

(2) The top plates in loadbearing walls shall be lapped or otherwise suitably tied at corners and intersecting walls in accordance with Sentence (4).

(3) Joints in single top plates used with loadbearing walls shall be tied in accordance with Sentence (4).

(4) Ties referred to in Sentences (2) and (3) shall be the equivalent of not less than 75 mm by 150 mm by 0.91 mm thick galvanized steel nailed to each wall with at least three 63 mm nails.

Text · e-Laws consolidated snapshot

9.23.12. — Framing Over Openings

Content not available for this version.

9.23.12.1. — Openings in Non-Loadbearing Walls

(1) Except as provided in Sentence (2), openings in non-loadbearing walls shall be framed with not less than 38 mm material the same width as the studs securely nailed to adjacent studs.

(2) Openings for doors in non-loadbearing walls required to be fire separations with a fire-resistance rating shall be framed with the equivalent of at least two 38 mm thick members that are the same width as the wall plates.

Text · e-Laws consolidated snapshot

9.23.12.2. — Openings in Loadbearing Walls

(1) Openings in loadbearing walls greater than the required stud spacing shall be framed with lintels designed to carry the superimposed loads to adjacent studs.

(2) Except as provided in Sentence 9.23.12.3.(2)v1, where 2 or more members are used in lintels, they shall be fastened together with not less than 82 mm nails in a double row, with nails not more than 450 mm apart in each row.

(3) Lintel members may be separated by filler pieces.

Text · e-Laws consolidated snapshot

9.23.12.3. — Lintel Spans and Sizes

(1) Spans and sizes of wood lintels shall conform to the spans shown in Tables A-12 to A-16,

(a) for buildings of residential occupancy,

(b) where the wall studs exceed 38 mm by 64 mm in size,

(c) where the spans of supported joists do not exceed 4.9 m, and

(d) where the spans of trusses do not exceed 9.8 m.

(2) In loadbearing exterior and interior walls of 38 by 64 mm framing members, lintels shall consist of,

(a) solid 64 mm thick members on edge, or

(b) 38 mm thick and 19 mm thick members fastened together with a double row of nails not less than 63 mm long and spaced not more than 450 mm apart.

(3) Lintels referred to in Sentence (2),

(a) shall be not less than 50 mm greater in depth than those shown in Tables A-12 to A-16 for the maximum spans shown, and

(b) shall not exceed 2 240 mm in length.

Editor's note

This map follows the as-filed column-header text of O. Reg. 350/06 for the tables under Article 9.23.12.3. The e-Laws consolidation editorially abbreviates the column headers (e.g. 'Column' to 'col.'); no amending regulation makes this change.

Text · e-Laws consolidated snapshot

Table A-13 Maximum Spans for Douglas Fir – Larch Lintels – No. 1 or No. 2 Grade -Non-Structural Sheathing(1) Forming Part of Sentences 9.23.12.3.(1) and (3)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Lintel Supporting

Lintel Size, mm(2)

Maximum Span, m(3)(4)

Exterior Walls

Interior Walls

Specified Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Limited attic storage and ceiling

2 – 38 × 89

This Area Intentionally Left Blank

1.25

2 – 38 × 140

1.78

2 – 38 × 184

2.17

2 – 38 × 235

2.65

2 – 38 × 286

3.08

Roof and ceiling only (tributary width of 0.6 m maximum)(5)

2 – 38 × 89

2.68

2.34

2.13

1.97

1.86

1.97

2 – 38 × 140

4.21

3.68

3.34

3.10

2.92

3.10

2 – 38 × 184

5.50

4.84

4.39

4.08

3.84

4.08

2 – 38 × 235

6.61

5.97

5.56

5.21

4.88

5.21

2 – 38 × 286

7.66

6.92

6.44

6.09

5.66

6.09

Roof and ceiling only (tributary width of 4.9 m maximum)(6)

2 – 38 × 89

1.25

1.07

0.96

0.87

0.80

0.87

2 – 38 × 140

1.78

1.53

1.36

1.24

1.15

1.24

2 – 38 × 184

2.17

1.86

1.66

1.51

1.40

1.51

2 – 38 × 235

2.65

2.28

2.03

1.85

1.71

1.85

2 – 38 × 286

3.08

2.64

2.35

2.14

1.98

2.14

Roof, ceiling and 1 storey(3)(6)(7)

2 – 38 × 89

0.96

0.88

0.82

0.77

0.73

0.68

2 – 38 × 140

1.37

1.26

1.17

1.10

1.04

0.97

2 – 38 × 184

1.67

1.53

1.42

1.34

1.26

1.18

2 – 38 × 235

2.04

1.88

1.74

1.63

1.54

1.44

2 – 38 × 286

2.37

2.18

2.02

1.90

1.79

1.67

Roof, ceiling and 2 storeys(3)(6)(7)

2 – 38 × 89

0.86

0.81

0.77

0.73

0.70

0.61

2 – 38 × 140

1.23

1.16

1.09

1.04

0.99

0.87

2 – 38 × 184

1.50

1.41

1.33

1.27

1.21

1.06

2 – 38 × 235

1.84

1.72

1.63

1.55

1.48

1.30

2 – 38 × 286

2.13

2.00

1.89

1.80

1.72

1.51

Roof, ceiling and 3 storeys(3)(6)(7)

2 – 38 × 89

0.81

0.77

0.73

0.71

0.68

0.57

2 – 38 × 140

1.15

1.10

1.05

1.01

0.97

0.82

2 – 38 × 184

1.40

1.33

1.28

1.22

1.18

1.00

2 – 38 × 235

1.71

1.63

1.56

1.50

1.44

1.22

2 – 38 × 286

1.99

1.89

1.81

1.74

1.67

1.41

Notes to Table A-13:

(1)Where structural sheathing is used, lintel spans may be increased by 15%. Structural sheathing consists of a minimum 9.5 mm thick structural panel conforming to CSA O121-M, CSA O151, CAN/CSA-O325.0 or CSA O437.0 fastened with at least two rows of fasteners to the exterior face of the lintel, and a single row to the top plates and studs. Fasteners shall conform to Table 9.23.3.5.

(2)A single piece of 89 mm thick lumber may be used in lieu of 2 pieces of 38 mm thick lumber on edge.

(3)If floor joists span the full width of the building without support, lintel spans shall be reduced by 15% for “Roof, ceiling and 1 storey”, by 20% for “Roof, ceiling and 2 storeys”, and by 25% for “Roof, ceiling and 3 storeys”.

(4)For ends of lintels fully supported by walls, provide minimum bearing length of 38 mm for lintel spans up to 3 m, or minimum bearing length of 76 mm for lintel spans greater than 3 m.

(5)Spans for 0.6 m tributary width are calculated for lintels in end walls that support only a 0.6 m width of roof and ceiling, but do not support roof joists, roof rafters or roof trusses.

(6)Lintel spans are calculated based on a maximum floor joist, roof joist or rafter span of 4.9 m and a maximum roof truss span of 9.8 m. Lintel spans may be increased by 5% if rafter and joist spans are not more than 4.3 m and roof truss spans are not more than 8.6 m. Spans may be increased by 10% if rafter and joist spans are not more than 3.7 m and roof trusses are not more than 7.4 m.

(7)Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

Table A-14 Maximum Spans for Hem – Fir Lintels – No. 1 or No. 2 Grade – Non-Structural Sheathing(1) Forming Part of Sentences 9.23.12.3.(1) and (3)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Lintel Supporting

Lintel Size, mm(2)

Maximum Span, m(3)(4)

Exterior Walls

Interior Walls

Specified Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Limited attic storage and ceiling

2 – 38 × 89

This Area Intentionally Left Blank

1.31

2 – 38 × 140

1.87

2 – 38 × 184

2.27

2 – 38 × 235

2.78

2 – 38 × 286

3.23

Roof and ceiling only (tributary width of 0.6 m maximum)(5)

2 – 38 × 89

2.68

2.34

2.13

1.97

1.86

1.97

2 – 38 × 140

4.21

3.68

3.34

3.10

2.92

3.10

2 – 38 × 184

5.50

4.84

4.39

4.08

3.84

4.08

2 – 38 × 235

6.61

5.97

5.56

5.21

4.90

5.21

2 – 38 × 286

7.66

6.92

6.44

6.09

5.82

6.09

Roof and ceiling only (tributary width of 4.9 m maximum)(6)

2 – 38 × 89

1.31

1.13

1.00

0.91

0.84

0.91

2 – 38 × 140

1.87

1.61

1.43

1.30

1.20

1.30

2 – 38 × 184

2.27

1.95

1.74

1.58

1.42

1.58

2 – 38 × 235

2.78

2.39

2.13

1.92

1.71

1.92

2 – 38 × 286

3.23

2.77

2.47

2.17

1.94

2.17

Roof, ceiling and 1 storey(3)(6)(7)

2 – 38 × 89

1.01

0.93

0.86

0.81

0.76

0.69

2 – 38 × 140

1.44

1.32

1.23

1.14

1.05

0.95

2 – 38 × 184

1.75

1.61

1.47

1.34

1.23

1.12

2 – 38 × 235

2.14

1.96

1.76

1.60

1.48

1.35

2 – 38 × 286

2.49

2.22

2.00

1.82

1.69

1.55

Roof, ceiling and 2 storeys(3)(6)(7)

2 – 38 × 89

0.91

0.85

0.80

0.76

0.72

0.60

2 – 38 × 140

1.29

1.21

1.13

1.05

0.98

0.82

2 – 38 × 184

1.57

1.44

1.33

1.24

1.16

0.98

2 – 38 × 235

1.90

1.73

1.60

1.49

1.40

1.19

2 – 38 × 286

2.15

1.97

1.82

1.70

1.60

1.37

Roof, ceiling and 3 storeys(3)(6)(7)

2 – 38 × 89

0.85

0.81

0.77

0.74

0.69

0.55

2 – 38 × 140

1.21

1.14

1.06

1.00

0.95

0.76

2 – 38 × 184

1.43

1.33

1.25

1.18

1.12

0.91

2 – 38 × 235

1.72

1.60

1.50

1.42

1.35

1.10

2 – 38 × 286

1.95

1.82

1.72

1.63

1.55

1.27

Notes to Table A-14:

(1)Where structural sheathing is used, lintel spans may be increased by 15%. Structural sheathing consists of a minimum 9.5 mm thick structural panel conforming to CSA O121-M, CSA O151, CAN/CSA-O325.0 or CSA O437.0 fastened with at least two rows of fasteners to the exterior face of the lintel, and a single row to the top plates and studs. Fasteners shall conform to Table 9.23.3.5.

(2)A single piece of 89 mm thick lumber may be used in lieu of 2 pieces of 38 mm thick lumber on edge.

(3)If floor joists span the full width of the building without support, lintel spans shall be reduced by 15% for “Roof, ceiling and 1 storey”, by 20% for “Roof, ceiling and 2 storeys”, and by 25% for “Roof, ceiling and 3 storeys”.

(4) For ends of lintels fully supported by walls, provide minimum bearing length of 38 mm for lintel spans up to 3 m, or minimum bearing length of 76 mm for lintel spans greater than 3 m.

(5)Spans for 0.6 m tributary width are calculated for lintels in end walls that support only a 0.6 m width of roof and ceiling, but do not support roof joists, roof rafters or roof trusses.

(6) Lintel spans are calculated based on a maximum floor joist, roof joist or rafter span of 4.9 m and a maximum roof truss span of 9.8 m. Lintel spans may be increased by 5% if rafter and joist spans are not more than 4.3 m and roof truss spans are not more than 8.6 m. Spans may be increased by 10% if rafter and joist spans are not more than 3.7 m and roof trusses are not more than 7.4 m.

(7)Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

Table A-15 Maximum Spans for Spruce – Pine – Fir Lintels – No. 1 or No. 2 Grade – Non-Structural Sheathing(1) Forming Part of Sentences 9.23.12.3.(1) and (3)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Lintel Supporting

Lintel Size, mm(2)

Maximum Span, m(3)(4)

Exterior Walls

Interior Walls

Specified Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Limited attic storage and ceiling

2 – 38 × 89

This Area Intentionally Left Blank

1.27

2 – 38 × 140

1.93

2 – 38 × 184

2.35

2 – 38 × 235

2.88

2 – 38 × 286

3.34

Roof and ceiling only (tributary width of 0.6 m maximum)(5)

2 – 38 × 89

2.55

2.23

2.02

1.88

1.77

1.88

2 – 38 × 140

4.01

3.50

3.18

2.96

2.78

2.96

2 – 38 × 184

5.27

4.61

4.18

3.88

3.66

3.88

2 – 38 × 235

6.37

5.76

5.34

4.96

4.67

4.96

2 – 38 × 286

7.38

6.67

6.21

5.87

5.61

5.87

Roof and ceiling only (tributary width of 4.9 m maximum)(6)

2 – 38 × 89

1.27

1.11

1.01

0.93

0.87

0.93

2 – 38 × 140

1.93

1.66

1.48

1.35

1.25

1.35

2 – 38 × 184

2.35

2.02

1.80

1.64

1.52

1.64

2 – 38 × 235

2.88

2.47

2.20

2.01

1.84

2.01

2 – 38 × 286

3.34

2.87

2.56

2.33

2.09

2.33

Roof, ceiling and 1 storey(3)(6)(7)

2 – 38 × 89

1.05

0.96

0.89

0.84

0.79

0.74

2 – 38 × 140

1.49

1.37

1.27

1.19

1.13

1.02

2 – 38 × 184

1.82

1.67

1.55

1.44

1.33

1.20

2 – 38 × 235

2.22

2.04

1.89

1.73

1.59

1.45

2 – 38 × 286

2.58

2.36

2.15

1.96

1.81

1.66

Roof, ceiling and 2 storeys(3)(6)(7)

2 – 38 × 89

0.94

0.88

0.83

0.79

0.76

0.64

2 – 38 × 140

1.34

1.26

1.19

1.13

1.06

0.88

2 – 38 × 184

1.63

1.53

1.44

1.33

1.25

1.05

2 – 38 × 235

1.99

1.87

1.72

1.60

1.50

1.27

2 – 38 × 286

2.31

2.12

1.96

1.82

1.71

1.45

Roof, ceiling and 3 storeys(3)(6)(7)

2 – 38 × 89

0.88

0.83

0.80

0.77

0.74

0.59

2 – 38 × 140

1.25

1.19

1.14

1.08

1.02

0.81

2 – 38 × 184

1.52

1.44

1.35

1.27

1.21

0.97

2 – 38 × 235

1.86

1.73

1.62

1.53

1.45

1.17

2 – 38 × 286

2.11

1.96

1.84

1.74

1.66

1.35

Notes to Table A-15:

(1)Where structural sheathing is used, lintel spans may be increased by 15%. Structural sheathing consists of a minimum 9.5 mm thick structural panel conforming to CSA O121-M, CSA O151, CAN/CSA-O325.0 or CSA O437.0 fastened with at least two rows of fasteners to the exterior face of the lintel, and a single row to the top plates and studs. Fasteners shall conform to Table 9.23.3.5.

(2)A single piece of 89 mm thick lumber may be used in lieu of 2 pieces of 38 mm thick lumber on edge.

(3)If floor joists span the full width of the building without support, lintel spans shall be reduced by 15% for “Roof, ceiling and 1 storey”, by 20% for “Roof, ceiling and 2 storeys”, and by 25% for “Roof, ceiling and 3 storeys”.

(4)For ends of lintels fully supported by walls, provide minimum bearing length of 38 mm for lintel spans up to 3 m, or minimum bearing length of 76 mm for lintel spans greater than 3 m.

(5)Spans for 0.6 m tributary width are calculated for lintels in end walls that support only a 0.6 m width of roof and ceiling, but do not support roof joists, roof rafters or roof trusses.

(6)Lintel spans are calculated based on a maximum floor joist, roof joist or rafter span of 4.9 m and a maximum roof truss span of 9.8 m. Lintel spans may be increased by 5% if rafter and joist spans are not more than 4.3 m and roof truss spans are not more than 8.6 m. Spans may be increased by 10% if rafter and joist spans are not more than 3.7 m and roof trusses are not more than 7.4 m.

(7)Spans apply only where the floors serve residential areas as described in Table 4.1.5.3.v1, or the uniformly distributed live load does not exceed that specified for residential areas as described in Table 4.1.5.3.v1

Table A-16 Maximum Spans for Glued-Laminated Timber Lintels – 20f-E Stress Grade – Exterior Walls – Roof and Ceiling Load Only Forming Part of Sentences 9.23.12.3.(1) and (3)

Column 1

C. 2

C. 3

C. 4

C. 5

C. 6

C. 7

C. 8

C. 9

C. 10

C. 11

C. 12

C. 13

C. 14

C. 15

C. 16

Lintel Size, mm

Maximum Span, m(1)(2)(3)

Specified Snow Load, kPa

1.0

1.5

2.0

2.5

3.0

Supported length, m(4)(5)

Supported length, m(4)(5)

Supported length, m(4)(5)

Supported length, m(4)(5)

Supported length, m(4)(5)

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

2.4

3.6

4.8

130 × 304

6.23

5.63

5.24

5.63

5.09

4.73

5.24

4.73

4.40

4.95

4.48

4.17

4.73

4.28

3.87

80 × 380

6.52

5.89

5.48

5.89

5.32

4.96

5.48

4.96

4.52

5.19

4.69

4.11

4.96

4.39

3.80

130 × 342

6.80

6.15

5.72

6.15

5.56

5.17

5.72

5.17

4.81

5.41

4.89

4.55

5.17

4.67

4.35

80 × 418

7.00

6.33

5.89

6.33

5.72

5.32

5.89

5.32

4.96

5.57

5.03

4.52

5.32

4.81

4.18

130 × 380

7.36

6.65

6.19

6.65

6.01

5.59

6.19

5.59

5.21

5.86

5.29

4.92

5.59

5.06

4.70

80 × 456

7.48

6.76

6.29

6.76

6.10

5.68

6.29

5.68

5.29

5.95

5.37

4.93

5.68

5.13

4.56

130 × 418

7.91

7.15

6.65

7.15

6.46

6.01

6.65

6.01

5.59

6.29

5.68

5.29

6.01

5.43

5.05

80 × 494

7.94

7.17

6.68

7.17

6.48

6.03

6.68

6.03

5.61

6.31

5.71

5.31

6.03

5.45

4.94

80 × 532

8.39

7.58

7.06

7.58

6.85

6.38

7.06

6.38

5.93

6.67

6.03

5.61

6.38

5.76

5.32

130 × 456

8.44

7.63

7.10

7.63

6.89

6.41

7.10

6.41

5.97

6.71

6.07

5.65

6.41

5.80

5.39

Notes to Table A-16:

(1)Spans are valid for glued-laminated timber conforming to CAN/CSA-O122-M and CAN/CSA-O177-M.

(2)Provide a minimum bearing length of 89 mm. (Alternatively, the bearing length may be calculated in accordance with Part 4.)

(3)Top edge of lintel assumed to be fully laterally supported.

(4)Supported length means half the length of trusses or rafters, plus the length of overhang beyond the wall.

(5)For intermediate supported lengths, straight interpolation may be used.

9.23.13. — Roof and Ceiling Framing

Content not available for this version.

9.23.13.1. — Continuity of Rafters and Joists

(1) Roof rafters and joists and ceiling joists shall be continuous or shall be spliced over vertical supports that extend to suitable bearing.

Text · e-Laws consolidated snapshot

9.23.13.2. — Framing around Openings

(1) Roof and ceiling framing members shall be doubled on each side of openings greater than 2 rafter or joist spacings wide.

Text · e-Laws consolidated snapshot

9.23.13.3. — End Bearing Length

(1) The length of end bearing of joists and rafters shall be not less than 38 mm.

Text · e-Laws consolidated snapshot

9.23.13.4. — Location and Attachment of Rafters

(1) Rafters shall be located directly opposite each other and tied together at the peak, or may be offset by their own thickness if nailed to a ridge board not less than 17.5 mm thick.

(2) Except as permitted in Sentence (3), framing members shall be connected by gusset plates or nailing at the peak in conformance with Table 9.23.3.4.

(3) Where the roof framing on opposite sides of the peak is assembled separately, such as in the case of factory-built houses, the roof framing on opposite sides is permitted to be fastened together with galvanized-steel strips not less than 200 mm by 75 mm by 0.41 mm thick spaced not more than 1 200 mm apart and nailed at each end to the framing by at least two 63 mm nails.

Text · e-Laws consolidated snapshot

9.23.13.5. — Shaping of Rafters

(1) Rafters shall be shaped at supports to provide even bearing surfaces and supported directly above the exterior walls.

Text · e-Laws consolidated snapshot

9.23.13.6. — Hip and Valley Rafters

(1) Hip and valley rafters shall be not less than 50 mm greater in depth than the common rafters and not less than 38 mm thick, actual dimension.

Text · e-Laws consolidated snapshot

9.23.13.7. — Intermediate Support for Rafters and Joists

(1) Ceiling joists and collar ties of not less than 38 mm by 89 mm lumber are permitted to be assumed to provide intermediate support to reduce the span for rafters and joists where the roof slope is 1 in 3 or greater.

(2) Collar ties referred to in Sentence (1) more than 2 400 mm long shall be laterally supported near their centres by not less than 19 mm by 89 mm continuous members at right angles to the collar ties.

(3) Dwarf walls and struts may be used to provide intermediate support to reduce the span for rafters and joists.

(4) When struts are used to provide intermediate support they shall be not less than 38 mm by 89 mm material extending from each rafter to a loadbearing wall at an angle of not less than 45° to the horizontal.

(5) When dwarf walls are used for rafter support, they shall be framed in the same manner as loadbearing walls and securely fastened top and bottom to the roof and ceiling framing to prevent over-all movement.

(6) Solid blocking shall be installed between floor joists beneath dwarf walls referred to in Sentence (5) that enclose finished rooms.

Text · e-Laws consolidated snapshot

9.23.13.8. — Ridge Support

(1) Except as provided in Sentence (4), roof rafters and joists shall be supported at the ridge of the roof by,

(a) a loadbearing wall extending from the ridge to suitable bearing, or

(b) a ridge beam supported by not less than 89 mm length of bearing.

(2) Except as provided in Sentence (3), the ridge beam referred to in Sentence (1) shall conform to the sizes and spans shown in Table A-12, provided,

(a) the supported rafter or joist length does not exceed 4.9 m, and

(b) the roof does not support any concentrated loads.

(3) The ridge beam referred to in Sentence (1) need not comply with Sentence (2) where,

(a) the beam is of not less than 38 mm by 140 mm material, and

(b) the beam is supported at intervals not exceeding 1 200 mm by not less than 38 mm by 89 mm members extending vertically from the ridge to suitable bearing.

(4) When the roof slope is 1 in 3 or more, ridge support need not be provided when the lower ends of the rafters are adequately tied to prevent outward movement.

(5) Ties required in Sentence (4) are permitted to consist of tie rods or ceiling joists forming a continuous tie for opposing rafters and nailed in accordance with Table 9.23.13.8.

(6) Ceiling joists referred to in Sentence (5) shall be fastened together with at least one more nail per joist splice than required for the rafter to joist connection shown in Table 9.23.13.8.

(7) Members referred to in Sentence (6) are permitted to be fastened together either directly or through a gusset plate.

Editor's note

As filed in O. Reg. 350/06, the first Roof Snow Load column heading of Table 9.23.13.8. reads '1.0 or less' with a space between '1.0' and 'or'; the current e-Laws consolidation editorially removes the space, rendering it as the run-together '1.0or less', with no amending regulation making the change. This map preserves the as-filed spacing.

Text · e-Laws consolidated snapshot

Table 9.23.13.8. Rafter-to-Joist Nailing (Unsupported Ridge) Forming Part of Sentences 9.23.13.8.(5) and (6)

Col. 1

Col. 2

Col. 3

Col. 4

Col. 5

Col. 6

Col. 7

Col. 8

Col. 9

Col. 10

Col. 11

Col. 12

Col. 13

Col. 14

Roof Slope

Rafter Spacing, mm

Minimum Number of Nails not less than 75 mm Long

Rafter Tied to every Joist

Rafter Tied to Joist every 1.2 m

Building Width up to 8.0 m

Building width up to 9.8 m

Building Width up to 8.0 m

Building Width up to 9.8 m

Roof Snow Load, kPa

Roof Snow Load, kPa

Roof Snow Load, kPa

Roof Snow Load, kPa

1.0   or less

1.5

2.0 or more

1.0 or less

1.5

2.0 or more

1.0 or less

1.5

2.0 or more

1.0 or less

1.5

2.0 or more

1 in 3

400

4

5

6

5

7

8

11

600

6

8

9

8

11

1 in 2.4

400

4

4

5

5

6

7

7

10

9

600

5

7

8

7

9

11

7

10

1 in 2

400

4

4

4

4

4

5

6

8

9

8

600

4

5

6

5

7

8

6

8

9

8

1 in 1.71

400

4

4

4

4

4

4

5

7

8

7

9

11

600

4

4

5

5

6

7

5

7

8

7

9

11

1 in 1.33

400

4

4

4

4

4

4

4

5

6

5

6

7

600

4

4

4

4

4

5

4

5

6

5

6

7

1 in 1

400

4

4

4

4

4

4

4

4

4

4

4

5

600

4

4

4

4

4

4

4

4

4

4

4

5

9.23.13.9. — Restraint of Joist Bottoms

(1) Roof joists supporting a finished ceiling, other than plywood, OSB or waferboard, shall be restrained from twisting along the bottom edges by means of furring, blocking, cross bridging or strapping conforming to Article 9.23.9.3.

Text · e-Laws consolidated snapshot

9.23.13.10. — Ceiling Joists Supporting Roof Load

(1) Except as permitted in Sentence (2), ceiling joists supporting part of the roof load from the rafters shall be not less than 25 mm greater in depth than required for ceiling joists not supporting part of the roof load.

(2) When the roof slope is 1 in 4 or less, the ceiling joist sizes referred to in Sentence (1) shall be determined from the span tables for roof joists.

Text · e-Laws consolidated snapshot

9.23.13.11. — Wood Roof Trusses

(1) Roof trusses that are not designed in accordance with Part 4 shall,

(a) be capable of supporting a total ceiling load (dead load plus live load) of 0.35 kPa plus two and two-thirds times the specified live roof load for 24 h, and

(b) not exceed the deflections shown in Table 9.23.13.11. when loaded with the ceiling load plus one and one-third times the specified roof snow load for 1 h.

(2) The joint connections used in trusses described in Sentence (1) shall be designed in conformance with the requirements in Subsection 4.3.1.

(3) Where the length of compression web members in roof trusses described in Sentence (1) exceeds 1 830 mm, such web members shall be provided with continuous bracing to prevent buckling.

(4) Bracing required in Sentence (3) shall consist of not less than 19 mm by 89 mm lumber nailed at right angles to the web members near their centres with at least two 63 mm nails for each member.

(5) Where the ability of a truss design to satisfy the requirements of Sentence (1) is demonstrated by testing, it shall consist of a full scale load test carried out in conformance with CSA S307-M, “Load Test Procedure for Wood Trusses for Houses and Small Buildings”.

(6) Where the ability of a truss design to satisfy the requirements of Sentence (1) is demonstrated by analysis, it shall be carried out in accordance with good engineering practice such as described in TPIC, “Truss Design Procedures and Specifications for Light Metal Plate Connected Wood Trusses”.

Text · e-Laws consolidated snapshot

Table 9.23.13.11. Maximum Roof Truss Deflections Forming Part of Sentence 9.23.13.11.(1)

Column 1

Column 2

Column 3

Truss Span

Type of Ceiling

Maximum Deflection

4.3 m or less

Plaster or gypsum board

1/360 of the span

Other than plaster or gypsum board

1/180 of the span

Over 4.3 m

Plaster or gypsum board

1/360 of the span

Other than plaster or gypsum board

1/240 of the span

9.23.14. — Subflooring

Content not available for this version.

9.23.14.1. — Subflooring Required

(1) Subflooring shall be provided beneath finish flooring where the finish flooring does not have adequate strength to support the design loads.

Text · e-Laws consolidated snapshot

9.23.14.2. — Material Standards

(1) Except as provided in Sentence (2), wood-based panels for subfloors shall conform to,

(a) CSA O121-M, “Douglas Fir Plywood”,

(b) CSA O151, “Canadian Softwood Plywood”,

(c) CSA O153-M, “Poplar Plywood”,

(d) CAN/CSA-O325.0, “Construction Sheathing”, or

(e) CSA O437.0, “OSB and Waferboard”.

(2) Particleboard subflooring may be used only where a building is constructed in a factory so that the subfloor will not be exposed to the weather.

(3) Subflooring described in Sentence (2) shall conform to grade D-2 or D-3 in ANSI A208.1, “Particleboard, Mat-Formed Wood”.

(4) Subflooring described in Sentence (2) shall have its upper surface and all edges treated to restrict water absorption where the subfloor is used in bathrooms, kitchens, laundry rooms or other areas subject to periodic wetting.

Text · e-Laws consolidated snapshot

9.23.14.3. — Edge Support

(1) Where the edges of panel-type subflooring are required to be supported, such support shall consist of tongue-and-groove panel edges or not less than 38 mm by 38 mm blocking securely nailed between framing members.

Text · e-Laws consolidated snapshot

9.23.14.4. — Direction of Installation

(1) Plywood subflooring shall be installed with the surface grain at right angles to the joists and with joints parallel to floor joists staggered.

(2) OSB subflooring conforming to CAN/CSA-O325.0, “Construction Sheathing”, or to O-1 and O-2 grades in CSA O437.0, “OSB and Waferboard”, and waferboard subflooring conforming to R-1 grade in CSA O437.0 shall be installed with the direction of face orientation at right angles to the joists and the joints parallel to the floor joists are staggered.

Text · e-Laws consolidated snapshot

9.23.14.5. — Subfloor Thickness or Rating

(1) Except as provided in Sentences (2) and (3), subfloors shall conform to Table 9.23.14.5.A. or Table 9.23.14.5.B.

(2) Where the finished flooring consists of not less than 19 mm matched wood strip flooring laid at right angles to joists, spaced not more than 600 mm o.c., subflooring shall be permitted to consist of not less than,

(a) 12.5 mm thick plywood,

(b) 12.5 mm thick OSB conforming to O-2 grade,

(c) 12.7 mm thick OSB conforming to O-1 grade,

(d) 12.7 mm thick waferboard conforming to R-1 grade, or

(e) OSB conforming to 2R32 / 2F16 grade.

(3) Except where the flooring consists of ceramic tiles applied with adhesive, where a separate panel-type underlay or concrete topping is applied to a subfloor on joists spaced not more than 400 mm o.c., the subfloor may consist of not less than,

(a) 12.5 mm thick plywood,

(b) 12.5 mm thick OSB conforming to O-2 grade,

(c) 12.7 mm thick OSB conforming to O-1 grade,

(d) 12.7 mm thick waferboard conforming to R-1 grade, or

(e) OSB conforming to 2R32 / 2F16 grade.

Editor's note

As filed in O. Reg. 350/06, the first thickness-column heading of Table 9.23.14.5.A. reads 'Plywood and OSB, O-2 Grade' with a space between 'OSB,' and 'O-2'; the current e-Laws consolidation editorially removes the space, rendering it as the run-together 'Plywood and OSB,O-2 Grade', with no amending regulation making the change. This map preserves the as-filed spacing.

Text · e-Laws consolidated snapshot

Table 9.23.14.5.A. Thickness of Subflooring Forming Part of Sentences 9.23.14.5.(1) and 9.23.15.7.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Maximum Spacing of Supports, mm

Minimum Thickness, mm

Plywood and OSB, O-2 Grade

OSB, O-1 Grade, and Waferboard, R-1 Grade

Particleboard

Lumber

400

15.5

15.9

15.9

17.0

500

15.5

15.9

19.0

19.0

600

18.5

19.0

25.4

19.0

Table 9.23.14.5.B. Rating for Subfloor when Applying CAN/CSA-O325.0 Forming Part of Sentences 9.23.14.5.(1) and 9.23.15.7.(1)

Column 1

Column 2

Column 3

Maximum Spacing of Supports, mm

Panel Mark

Subfloor

Used with Panel-Type Underlay

400

1F16

2F16

500

1F20

2F20

600

1F24

2F24

9.23.14.6. — Annular Grooved Nails

(1) When resilient flooring is applied directly to an OSB, waferboard, particleboard or plywood subfloor, the subfloor shall be fastened to the supports with annular grooved nails.

Text · e-Laws consolidated snapshot

9.23.14.7. — Lumber Subflooring

(1) Lumber subflooring shall be laid at an angle of not less than 45° to the joists.

(2) Lumber subflooring shall be fully supported at the ends on solid bearing.

(3) Lumber for subflooring shall be of uniform thickness and not more than 184 mm wide.

Text · e-Laws consolidated snapshot

9.23.15. — Roof Sheathing

Content not available for this version.

9.23.15.1. — Required Roof Sheathing

(1) Except as provided in Section 9.26., continuous lumber or panel-type roof sheathing shall be installed to support the roofing.

Text · e-Laws consolidated snapshot

9.23.15.2. — Material Standards

(1) Wood-based panels used for roof sheathing shall conform to the requirements of,

(a) CSA O121-M, “Douglas Fir Plywood”,

(b) CSA O151, “Canadian Softwood Plywood”,

(c) CSA O153-M, “Poplar Plywood”,

(d) CAN/CSA-O325.0, “Construction Sheathing”, or

(e) CSA O437.0, “OSB and Waferboard”.

Text · e-Laws consolidated snapshot

9.23.15.3. — Direction of Installation

(1) Plywood roof sheathing shall be installed with the surface grain at right angles to the roof framing.

(2) OSB roof sheathing conforming to CAN/CSA-O325.0, “Construction Sheathing”, or to O-1 and O-2 grades as specified in CSA O437.0, “OSB and Waferboard”, shall be installed with the direction of face orientation at right angles to the roof framing members.

Text · e-Laws consolidated snapshot

9.23.15.4. — Joints in Panel-Type Sheathing

(1) Panel-type sheathing board shall be applied so that joints perpendicular to the roof ridge are staggered where,

(a) the sheathing is applied with the surface grain parallel to the roof ridge, and

(b) the thickness of the sheathing is such that the edges are required to be supported.

(2) A gap of not less than 2 mm shall be left between sheets of plywood, OSB or waferboard.

Text · e-Laws consolidated snapshot

9.23.15.5. — Lumber Roof Sheathing

(1) Lumber roof sheathing shall not be more than 286 mm wide and shall be applied so that all ends are supported with end joints staggered.

Text · e-Laws consolidated snapshot

9.23.15.6. — Edge Support

(1) Except as permitted in Sentence (2), where panel-type roof sheathing requires edge support, the support shall consist of,

(a) metal H clips, or

(b) not less than 38 mm by 38 mm blocking securely nailed between framing members.

(2) The supports referred to in Sentence (1) are not required when tongued-and-grooved edged panel-type sheathing board is used.

Text · e-Laws consolidated snapshot

9.23.15.7. — Thickness or Rating

(1) The thickness or rating of roof sheathing on a flat roof used as a walking deck shall conform to either Table 9.23.14.5.A. or Table 9.23.14.5.B. for subfloors.

(2) The thickness or rating of roof sheathing on a roof not used as a walking deck shall conform to either Table 9.23.15.7.A. or Table 9.23.16.7.B.v1

(3) Asphalt-coated or asphalt-impregnated fibreboard not less than 11.1 mm thick conforming to CAN/ULC-S706, “Wood Fibre Thermal Insulation for Buildings”, is permitted to be used as a roof sheathing over supports spaced not more than 400 mm o.c. provided the roofing consists of,

(a) a continuous sheet of galvanized steel not less than 0.33 mm in thickness, or

(b) a continuous sheet of aluminum not less than 0.61 mm in thickness.

(4) All edges of sheathing described in Sentence (3) shall be supported by blocking or framing.

Text · e-Laws consolidated snapshot

Table 9.23.15.7.A. Thickness of Roof Sheathing Forming Part of Sentence 9.23.15.7.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Maximum Spacing of Supports, mm

Minimum Thickness, mm

Plywood and OSB, O-2 Grade

OSB, O-1 Grade and Waferboard,
R-1 Grade

Lumber

Edges Supported

Edges Unsupported

Edges Supported

Edges Unsupported

300

7.5

7.5

9.5

9.5

17.0

400

7.5

9.5

9.5

11.1

17.0

600

9.5

12.5

11.1

12.7

19.0

Table 9.23.15.7.B. Rating for Roof Sheathing When Applying CAN/CSA-O325.0 Forming Part of Sentence 9.23.15.7.(2)

Column 1

Column 2

Column 3

Maximum Spacing of Supports, mm

Panel Mark

Edges Supported

Edges Unsupported

400

2R16

1R16

500

2R20

1R20

600

2R24

1R24

9.23.16. — Wall Sheathing

Content not available for this version.

9.23.16.1. — Required Sheathing

(1) Exterior walls and gable ends shall be sheathed when the exterior cladding requires intermediate fastening between supports or if the exterior cladding requires solid backing.

Text · e-Laws consolidated snapshot

9.23.16.2. — Thickness, Rating and Material Standards

(1) Where wall sheathing is required, it shall conform to Table 9.23.16.2.A. or Table 9.23.16.2.B.

Text · e-Laws consolidated snapshot

Table 9.23.16.2.A. Wall Sheathing Thickness and Specifications Forming Part of Sentence 9.23.16.2.(1)

Column 1

Column 2

Column 3

Column 4

Type of Sheathing

Minimum Thickness, mm(1)

Material Standards

With Supports 400 mm o.c.

With Supports 600 mm o.c.

Fibreboard (insulating)

9.5

11.1

CAN/ULC-S706

Gypsum Sheathing

9.5

12.7

CAN/CSA-A82.27-M

ASTM C79 / C79M

ASTM C1177 / C1177M

ASTM C1396 / C1396M

Lumber

17.0

17.0

See Table 9.3.2.1.v1

Mineral Fibre, Rigid Board, Type 2

25

25

CAN/ULC-S702

OSB, O-2 Grade

6.0

7.5

CSA O437.0

OSB, O-1 Grade, and Waferboard, R-1 Grade

6.35

7.9

CSA O437.0

Phenolic, faced

25

25

CAN/CGSB-51.25-M

Plywood (exterior type)

6

7.5

CSA O121-M

CSA O151

CSA O153-M

Polystyrene, Types 1 and 2

38

38

CAN/ULC-S701

Polystyrene, Types 3 and 4

25

25

CAN/ULC-S701

Polyurethane and Polyisocycanurate Type 1, faced

38

38

CAN/ULC-S704

Polyurethane and Polyisocycanurate Types 2 and 3, faced

25

25

CAN/ULC-S704

Notes to Table 9.23.16.2.A.:

(1)See also Sentences 9.27.5.1.(2) to (4).

Table 9.23.16.2.B. Rating For Wall Sheathing When Applying CAN/CSA-O325.0 Forming Part of Sentence 9.23.16.2.(1)

Column 1

Column 2

Maximum Spacing of Supports, mm

Panel Mark

400

W16

500

W20

600

W24

9.23.16.3. — Attachment of Cladding to Sheathing

(1) Gypsum sheathing, rigid insulation and fibreboard shall not be used for the attachment of siding materials.

(2) Nails used in attaching the materials listed in Sentence (1) shall be not less than 3.2 mm diam with a minimum head diameter of 11 mm.

Text · e-Laws consolidated snapshot

9.23.16.4. — Lumber Sheathing

(1) Lumber wall sheathing shall be applied so that all ends are supported.

(2) Where lumber wall sheathing is required to provide bracing according to Article 9.23.10.2., it shall be applied with end joints staggered.

Text · e-Laws consolidated snapshot

9.23.16.5. — Joints in Panel-Type Sheathing

(1) A gap of not less than 2 mm shall be left between sheets of plywood, OSB, waferboard or fibreboard.

Text · e-Laws consolidated snapshot

9.23.16.6. — Mansard Style Roofs

(1) Where the bottom portions of mansard style roofs are vented, the vertical framing members behind the sloping portions shall be considered on the same basis as exterior wall studs and shall conform to the appropriate requirements in Subsection 9.23.17.

Text · e-Laws consolidated snapshot

9.24. — Sheet Steel Stud Wall Framing

Content not available for this version.

9.24.1. — General

Content not available for this version.

9.24.1.1. — Application

(1) This Section applies to sheet steel studs for use in non-loadbearing exterior and interior walls.

(2) Where loadbearing steel studs are used, they shall be designed in conformance with Part 4.

Text · e-Laws consolidated snapshot

9.24.1.2. — Material Standards

(1) Steel studs and runners shall conform to CAN/CGSB-7.1, “Lightweight Steel Framing Components”.

Text · e-Laws consolidated snapshot

9.24.1.3. — Metal Thickness

(1) Metal thickness specified in this Section shall be the minimum base steel thickness exclusive of coatings.

Text · e-Laws consolidated snapshot

9.24.1.4. — Screws

(1) Screws for the application of cladding, sheathing or interior finish materials to steel studs, runners and furring channels shall conform to ASTM C1002, “Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs”.

Text · e-Laws consolidated snapshot

9.24.1.5. — Cladding, Sheathing and Interior Finish Required

(1) Cladding or sheathing, and interior finish shall be installed on steel stud framing and shall be fastened with screws,

(a) spaced at the appropriate spacing described in Section 9.29., and

(b) penetrating not less than 10 mm through the metal.

Text · e-Laws consolidated snapshot

9.24.2. — Size of Framing

Content not available for this version.

9.24.2.1. — Size and Spacing of Studs in Interior Walls

(1) Except as required in Articles 9.24.2.3. and 9.24.2.4., the size and spacing of steel studs for non-loadbearing interior walls shall conform to Table 9.24.2.1.

Text · e-Laws consolidated snapshot

Table 9.24.2.1. Steel Studs for Non-Loadbearing Interior Walls Forming Part of Sentence 9.24.2.1.(1)

Column 1

Column 2

Column 3

Minimum Stud Size, mm

Maximum Stud Spacing, mm

Maximum Wall Height, m

30 × 40

400

3.0

600

2.7

30 × 63

400

4.0

600

3.6

30 × 91

400

5.2

600

4.9

9.24.2.2. — Thickness of Studs

(1) Except as required in Article 9.24.2.4., steel studs in non-loadbearing interior walls shall have a metal thickness of not less than 0.46 mm.

Text · e-Laws consolidated snapshot

9.24.2.3. — Runners

(1) Runners for interior and exterior non-loadbearing walls shall have a thickness of not less than the thickness of the corresponding studs and shall have not less than 30 mm flanges.

Text · e-Laws consolidated snapshot

9.24.2.4. — Openings in Fire Separations

(1) Where openings for doors in non-loadbearing fire separations required to have a fire-resistance rating do not exceed 1 200 mm in width,

(a) the width of steel studs shall be not less than 63 mm, and

(b) the steel thickness shall be not less than 0.46 mm.

(2) Where openings described in Sentence (1) exceed 1 200 mm in width,

(a) the width of steel studs shall be not less than 91 mm, and

(b) the metal thickness shall be not less than 0.85 mm.

(3) The distance to the first stud beyond the jamb of any door opening in a fire separation required to have a fire-resistance rating shall not exceed 400 mm.

(4) Where the distance between the framing over the opening referred to in Sentence (3) and the top runner exceeds 400 mm in such walls, intermediate support shall be installed at intervals of not more than 400 mm above the opening.

Text · e-Laws consolidated snapshot

9.24.2.5. — Size and Spacing of Studs in Exterior Walls

(1) The size and spacing of non-loadbearing steel studs for exterior walls shall conform to Table 9.24.2.5.

Editor's note

As filed in O. Reg. 350/06, the column-heading row of Table 9.24.2.5. carries a typographical error: the second heading reads 'Column 1' (duplicating the first) where it should read 'Column 2'. The current e-Laws consolidation silently corrects this to 'Column 2', with no amending regulation making the change. This map preserves the heading as filed.

Text · e-Laws consolidated snapshot

Table 9.24.2.5. Size and Spacing of Steel Studs for Non-Loadbearing Exterior Walls Forming Part of Sentence 9.24.2.5.(1)

Column 1

Column 1

Column 3

Column 4

Column 5

Minimum Stud Size, mm

Minimum Metal

Thickness, mm

Maximum Stud Length, m

Spacing of Studs

300 mm (o.c.)

400 mm (o.c.)

600 mm (o.c.)

30 × 91

0.53

3.0

2.4

30 × 91

0.69

3.3

2.7

2.4

30 × 91

0.85

3.6

3.0

2.7

30 × 91

1.0

4.0

3.3

3.0

9.24.3. — Installation

Content not available for this version.

9.24.3.1. — Installation of Runners

(1) Runners shall be provided at the tops and bottoms of walls.

(2) Runners required in Sentence (1) shall be securely attached to the building at approximately 50 mm from the ends, and at intervals of not more than 600 mm o.c. for interior walls and 300 mm o.c. for exterior walls.

(3) Fasteners used for attachment described in Sentence (2) shall consist of the equivalent of 63 mm nails or 25 mm screws.

(4) Studs at openings and that are not full wall height shall be supported by a runner at the ends of the studs, securely fastened to the full length studs at the sides of the opening.

Text · e-Laws consolidated snapshot

9.24.3.2. — Fire-Rated Walls

(1) Steel studs used in walls required to have a fire-resistance rating shall be installed so that there is not less than a 12 mm clearance between the top of the stud and the top of the runner to allow for expansion in the event of fire.

(2) Except as provided in Article 9.24.3.6., studs in walls referred to in Sentence (1) shall not be attached to the runners in a manner that will prevent such expansion.

(3) Framing above doors with steel door frames in non-loadbearing fire separations required to have a fire-resistance rating shall consist of 2 runners on the flat fastened back to back.

(4) The lower runner required in Sentence (3) shall be cut through the flanges and be bent at each end to extend upwards at least 150 mm and fastened to the adjacent studs.

Text · e-Laws consolidated snapshot

9.24.3.3. — Orientation of Studs

(1) Steel studs shall be installed with webs at right angles to the wall face and, except at openings, shall be continuous for the full wall height.

Text · e-Laws consolidated snapshot

9.24.3.4. — Support for Cladding Materials

(1) Corners and intersections of walls shall be constructed to provide support for the cladding materials.

Text · e-Laws consolidated snapshot

9.24.3.5. — Framing around Openings

(1) Studs shall be doubled on each side of every opening where such openings involve more than 1 stud space, and shall be tripled where the openings in exterior walls exceed 2 400 mm in width.

(2) Studs described in Sentence (1) shall be fastened together by screws, crimping or welding to act as a single structural unit in resisting transverse loads.

Text · e-Laws consolidated snapshot

9.24.3.6. — Attachment of Studs to Runners

(1) Studs shall be attached to runners by screws, crimping or welding around wall openings, and elsewhere where necessary to keep the studs in alignment during construction.

(2) Where clearance for expansion is required in Article 9.24.3.2., attachment required in Sentence (1) shall be applied between studs and bottom runners only.

Text · e-Laws consolidated snapshot

9.24.3.7. — Openings for Fire Dampers

(1) Openings for fire dampers in non-loadbearing fire separations required to have a fire-resistance rating shall be framed with double studs on each side of the opening.

(2) The sill and header for openings described in Sentence (1) shall consist of a runner track with right angle bends made on each end so as to extend 300 mm above the header or below the sill and fastened to the studs.

(3) The openings described in Sentence (1) shall be lined with a layer of gypsum board at least 12.7 mm thick fastened to stud and runner webs.

Text · e-Laws consolidated snapshot

9.25. — Heat Transfer, Air Leakage and Condensation Control

Content not available for this version.

9.25.1. — Scope

Content not available for this version.

9.25.1.1. — Application

(1) This Section applies to the application of thermal insulation and measures to control condensation, heat transfer and air leakage for buildings of residential occupancy intended for use on a continuing basis during the winter months.

(2) Insulation and sealing of heating and ventilating ducts shall conform to Sections 9.32. and 9.33.

Text · e-Laws consolidated snapshot

9.25.1.2. — General

(1) Sheet and panel-type materials shall be installed in accordance with Sentence (2), if the material,

(a) has an air leakage characteristic less than 0.1 L/(s∙m2) at 75 Pa,

(b) has a water vapour permeance less than 60 ng/(Pa∙s∙m2) when measured in accordance with ASTM E96, “Water Vapor Transmission of Materials”, using the desiccant method (dry cup), and

(c) is incorporated into a building assembly required by Article 9.25.2.1. to be insulated.

(2) Sheet and panel-type material described in Sentence (1) shall be installed,

(a) on the warm face of the assembly,

(b) except as provided in Sentences (3) to (5), at a location where the ratio between the total thermal resistance of all materials outboard of its innermost impermeable surface and the total thermal resistance of all materials inboard of that surface is not less than that required in Table 9.25.1.2., or

(c) outboard of an air space that is vented to the outdoors and, for walls, drained.

(3) Wood-based sheathing materials not more than 12.5 mm thick and complying with Article 9.23.16.2.v1 need not comply with Sentence (1).

(4) Where the mild climate indicator, determined in accordance with Sentence (6), is greater than 6300, the position of low air- and vapour-permeance materials within the assembly relative to the position of materials providing thermal resistance shall be determined according to Part 5 where,

(a) the intended use of the interior space requires the indoor relative humidity to be maintained above 35% over the heating season and the ventilating and air-conditioning system is designed to maintain that relative humidity, or

(b) the intended use of the interior space will result in an indoor relative humidity above 35% over the heating season and the ventilating and air-conditioning system does not have the capacity to reduce the relative humidity to 35% for any period over that period.

(5) Where the mild climate indicator, determined in accordance with Sentence (6), is less than or equal to 6300, the position of low air- and vapour-permeance materials within the assembly relative to the position of materials providing thermal resistance shall be determined according to Part 5 where,

(a) the intended use of the interior space requires the indoor relative humidity to be maintained above 60% over the heating season and the ventilation and air-conditioning system is designed to maintain that relative humidity, or

(b) the intended use of the interior space will result in an indoor relative humidity above 60% over the heating season and the ventilating and air-conditioning system does not have the capacity to reduce the relative humidity above 60% for any period over that period.

(6) The mild climate indicator (MCI) shall be calculated according to the following formula:

MCI = abs(2.5% JMT) ∙ 200 + DD

where,

abs(2.5% JMT) = absolute value of 2.5% January mean temperature, and

DD = degree-days

(7) For walls, the air space described in Clause (2)(c) shall comply with Clause 9.27.2.2.(1)(a).

Editor's note

In the notes to Table-9.25.1.2., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.25.1.2. Ratio of Outboard to Inboard Thermal Resistance Forming Part of Sentence 9.25.1.2.(1)

Column 1

Column 2

Heating Degree Days of Building Location(1), Celsius Degree-days

Minimum Ratio, Total Thermal Resistance Outboard of Material’s Inner Surface to Total Thermal Resistance Inboard of Material’s Inner Surface

up to 4 999

0.20

5 000 to 5 999

0.30

6 000 to 6 999

0.35

7 000 to 7 999

0.40

8 000 to 8 999

0.50

9 000 to 9 999

0.55

10 000 to 10 999

0.60

11 000 to 11 999

0.65

12 000 to 12 999

0.75

Notes to Table 9.25.1.2.:

(1)See Supplementary Standard SB-1.

9.25.2. — Thermal Insulation

Content not available for this version.

9.25.2.1. — Required Insulation

(1) All walls, ceilings and floors separating heated space from unheated space, the exterior air or the exterior soil shall be provided with thermal insulation in conformance with Sections 12.2. and 12.3. to prevent moisture condensation on their room side during the winter and to ensure comfortable conditions for the occupants.

Text · e-Laws consolidated snapshot

9.25.2.2. — Insulation Materials

(1) Except as required in Sentence (2), thermal insulation shall conform to the requirements of,

(a) CAN/CGSB-51.25-M, “Thermal Insulation, Phenolic, Faced”,

(b) CAN/CGSB-51-GP-27M, “Thermal Insulation, Polystyrene, Loose Fill”,

(c) CAN/ULC-S701, “Thermal Insulation, Polystyrene, Boards and Pipe Covering”,

(d) CAN/ULC-S702 “Mineral Fibre Thermal Insulation for Buildings”,

(e) CAN/ULC-S703, “Cellulose Fibre Insulation (CFI) for Buildings”,

(f) CAN/ULC-S704, “Thermal Insulation, Polyurethane and Polyisocyanurate, Boards, Faced”,

(g) CAN/ULC-S705.1, “Thermal Insulation – Spray Applied Rigid Polyurethane Foam, Medium Density – Material Specification”, or

(h) CAN/ULC-S706, “Wood Fibre Thermal Insulation for Buildings”.

(2) The flame-spread rating requirements contained in the standards listed in Sentence (1) shall not apply.

(3) Insulation in contact with the ground shall be inert to the action of soil and water and be such that its insulative properties are not significantly reduced by moisture.

(4) Type 1 expanded polystyrene insulation as described in CAN/ULC-S701, “Thermal Insulation, Polystyrene, Boards and Pipe Covering”, shall not be used as roof insulation applied above the roofing membrane.

Text · e-Laws consolidated snapshot

9.25.2.3. — Installation of Thermal Insulation

(1) Insulation shall be installed so that there is a reasonably uniform insulating value over the entire face of the insulated area.

(2) Insulation shall be applied to the full width and length of the space between furring or framing.

(3) Except where the insulation provides the principal resistance to air leakage, thermal insulation shall be installed so that at least 1 face is in full and continuous contact with an element with low air permeance.

(4) Insulation on the interior of foundation walls enclosing a crawl space shall be applied so that there is not less than a 50 mm clearance above the crawl space floor if the insulation is of a type that may be damaged by water.

(5) Insulation around concrete slabs-on-ground shall be located so that heat from the building is not restricted from reaching the ground beneath the perimeter, where exterior walls are not supported by footings extending below frost level.

(6) Where insulation is exposed to the weather and subject to mechanical damage, it shall be protected with not less than,

(a) 6 mm asbestos-cement board,

(b) 6 mm preservative-treated plywood, or

(c) 12 mm cement parging on wire lath applied to the exposed face and edge.

(7) Except as permitted in Sentence (8) insulation and vapour barrier shall be protected from mechanical damage by a covering such as gypsum board, plywood, particleboard, OSB, waferboard or hardboard.

(8) In unfinished basements, the protection required in Sentence (7) need not be provided for mineral fibre insulation provided it is covered with polyethylene vapour barrier of at least 0.15 mm in thickness.

(9) Insulation in factory-built buildings shall be installed so that it will not become dislodged during transportation.

Text · e-Laws consolidated snapshot

9.25.2.4. — Installation of Loose-Fill Insulation

(1) Except as provided in Sentences (2) to (5), loose-fill insulation shall be used on horizontal surfaces only.

(2) Where loose-fill insulation is installed in an unconfined sloped space, such as an attic space over a sloped ceiling, the supporting slope shall not be more than,

(a) 4.5 in 12 for mineral fibre or cellulose fibre insulation, and

(b) 2.5 in 12 for other types of insulation.

(3) Loose-fill insulation may be used in wood-frame walls of existing buildings.

(4) Where blown-in insulation is installed in above-ground or below-ground wood frame walls of new buildings,

(a) the density of the installed insulation shall be sufficient to preclude settlement,

(b) the insulation shall be installed behind a membrane that will permit visual inspection prior to installation of the interior finish,

(c) the insulation shall be installed in a manner that will not interfere with the installation of the interior finish, and

(d) no water shall be added to the insulation, unless it can be shown that the added water will not adversely affect other materials in the assembly.

(5) Water repellent loose-fill insulation may be used between the outer and inner wythes of masonry cavity walls.

(6) Where soffit venting is used, measures shall be taken,

(a) to prevent loose-fill insulation from blocking the soffit vents and to maintain an open path for circulation of air from the vents into the attic or roof space, and

(b) to minimize air flow into the loose-fill insulation near the soffit vents to maintain the thermal performance of the material.

Text · e-Laws consolidated snapshot

9.25.2.5. — Installation of Spray-applied Polyurethane

(1) Spray-applied polyurethane insulation shall be installed in accordance with CAN/ULC-S705.2, “Thermal Insulation – Spray-Applied Rigid Polyurethane Foam, Medium Density, Installer’s Responsibilities – Specification”.

Text · e-Laws consolidated snapshot

9.25.3. — Air Barrier Systems

Content not available for this version.

9.25.3.1. — Required Barrier to Air Leakage

(1) Thermally insulated wall, ceiling and floor assemblies shall be constructed so as to include an air barrier system that will provide a continuous barrier to air leakage,

(a) from the interior of the building into wall, floor, attic or roof spaces sufficient to prevent excessive moisture condensation in such spaces during the winter, and

(b) from the exterior inward sufficient to prevent moisture condensation on the room side during winter.

Text · e-Laws consolidated snapshot

9.25.3.2. — Air Barrier System Properties

(1) Sheet and panel type materials intended to provide the principal resistance to air leakage shall have an air leakage characteristic not greater than 0.02 L/(s∙m2) measured at an air pressure differential of 75 Pa.

(2) Where polyethylene sheet used to provide the air-tightness in the air barrier system shall conform to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet for Use in Building Construction”.

Text · e-Laws consolidated snapshot

9.25.3.3. — Continuity of the Air Barrier System

(1) Where the air barrier system consists of an air-impermeable panel-type material, all joints shall be sealed to prevent air leakage.

(2) Where the air barrier system consists of flexible sheet material, all joints shall be,

(a) sealed, or

(b) lapped not less than 100 mm and clamped, such as between framing members, furring or blocking and rigid panels.

(3) Where an interior wall meets an exterior wall, ceiling, floor or roof required to be provided with an air barrier protection, the air barrier system shall extend across the intersection.

(4) Where an interior wall projects through a ceiling or extends to become an exterior wall, spaces in the wall shall be blocked to provide continuity across those spaces with the air barrier system in the abutting walls or ceiling.

(5) Where an interior floor projects through an exterior wall or extends to become an exterior floor, continuity of the air barrier system shall be maintained from the abutting walls across the floor assembly.

(6) Penetrations of the air barrier system, such as those created by the installation of doors, windows, electrical wiring, electrical boxes, piping or ductwork, shall be sealed to maintain the integrity of the air barrier system over the entire surface.

(7) Access hatches installed through assemblies constructed with an air barrier system shall be weatherstripped around their perimeters to prevent air leakage.

(8) Clearances between chimneys or gas vents and the surrounding construction that would permit air leakage from within the building into a wall or attic or roof space shall be sealed by noncombustible material to prevent such leakage.

Text · e-Laws consolidated snapshot

9.25.3.4. — 9.25.3.4.

Not in force at this date.

9.25.4. — Vapour Barriers

Content not available for this version.

9.25.4.1. — Required Barrier to Vapour Diffusion

(1) Thermally insulated wall, ceiling and floor assemblies shall be constructed with a vapour barrier sufficient to prevent condensation in the wall spaces, floor spaces or attic or roof spaces.

Text · e-Laws consolidated snapshot

9.25.4.2. — Vapour Barrier Materials

(1) Vapour barriers shall have a permeance not greater than 60 ng/(Pa∙s∙m2), measured in accordance with ASTM E96, “Water Vapor Transmission of Materials”, using the desiccant method (dry cup).

(2) Where the mild climate indicator, determined in accordance with Sentence 9.25.1.2.(6)v1, is greater than 6300, vapour barriers shall be designed according to Part 5, where,

(a) the intended use of the interior space requires the indoor relative humidity to be maintained above 35% over the heating season and the ventilating and air-conditioning system is designed to maintain that relative humidity, or

(b) the intended use of the interior space results in an average monthly indoor relative humidity above 35% over the heating season and the ventilating and air-conditioning system does not have the capacity to reduce the average monthly relative humidity to 35% or less over that period.

(3) Where the mild climate indicator, determined in accordance with Sentence 9.25.1.2.(6)v1, is less than or equal to 6300, vapour barriers shall be designed according to Part 5, where,

(a) the intended use of the interior space requires the indoor relative humidity to be maintained above 60% over the heating season and the ventilating and air-conditioning system is designed to maintain that relative humidity, or

(b) the intended use of the interior space results in an average monthly indoor relative humidity above 60% over the heating season and the ventilating and air-conditioning system does not have the capacity to reduce the average monthly relative humidity to 60% over that period.

(4) Where polyethylene is installed to serve as the vapour barrier, it shall conform to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet for Use in Building Construction”.

(5) Membrane-type vapour barriers other than polyethylene shall conform to CAN/CGSB-51.33-M, “Vapour Barrier, Sheet, Excluding Polyethylene, for Use in Building Construction”.

(6) Where a coating is applied to gypsum board to function as the vapour barrier, the permeance of the coating shall be determined in accordance with CAN/CGSB-1.501-M, “Method for Permeance of Coated Wallboard”.

Text · e-Laws consolidated snapshot

9.25.4.3. — Installation of Vapour Barriers

(1) Vapour barriers shall be installed to protect the entire surfaces of thermally insulated wall, ceiling and floor assemblies.

(2) Vapour barriers shall be installed sufficiently close to the warm side of insulation to prevent condensation at design conditions.

Text · e-Laws consolidated snapshot

9.26. — Roofing

Content not available for this version.

9.26.1. — General

Content not available for this version.

9.26.1.1. — Purpose of Roofing

(1) Roofs shall be protected with roofing, including flashing, installed to shed rain effectively and prevent water due to ice damming from entering the roof.

(2) For the purpose of Sentence (1), roofs shall include platforms that effectively serve as roofs with respect to accumulation or drainage of precipitation.

Text · e-Laws consolidated snapshot

9.26.1.2. — Alternate Installation Methods

(1) Methods described in CAN3-A123.51-M, “Asphalt Shingle Application on Roof Slopes 1:3 and Steeper”, or CAN3-A123.52-M, “Asphalt Shingle Application on Roof Slopes 1:6 to Less than 1:3”, are permitted to be used for asphalt shingle applications not described in this Section.

Text · e-Laws consolidated snapshot

9.26.1.3. — Solar Collector Systems

(1) A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1)v1.

Text · e-Laws consolidated snapshot

9.26.2. — Roofing Materials

Content not available for this version.

9.26.2.1. — Material Standards

(1) Roofing materials shall conform to,

(a) CAN/CGSB-37.4-M, “Fibrated, Cutback Asphalt, Lap Cement for Asphalt Roofing”,

(b) CAN/CGSB-37.5-M, “Cutback Asphalt Plastic, Cement”,

(c) CAN/CGSB-37.8-M, “Asphalt, Cutback, Filled, for Roof Coating”,

(d) CGSB 37-GP-9Ma, “Primer, Asphalt, Unfilled, for Asphalt Roofing, Dampproofing and Waterproofing”,

(e) CGSB 37-GP-21M, “Tar, Cutback, Fibrated, for Roof Coating”,

(f) CAN/CGSB-37.50-M, “Hot Applied, Rubberized Asphalt for Roofing and Waterproofing”,

(g) CGSB 37-GP-52M, “Roofing and Waterproofing Membrane, Sheet Applied, Elastomeric”,

(h) CAN/CGSB-37-GP-54, “Polyvinyl Chloride Roofing and Waterproofing Membrane”,

(i) CGSB 37-GP-56M, “Membrane, Modified, Bituminous, Prefabricated, and Reinforced for Roofing”,

(j) CGSB 41-GP-6M, “Sheets, Thermosetting Polyester Plastics, Glass Fiber Reinforced”,

(k) CAN/CGSB-51.32-M, “Sheathing, Membrane, Breather Type”,

(l) CAN/CSA-A123.1, “Asphalt Shingles Made from Organic Felt and Surfaced with Mineral Granules”,

(m) CSA A123.2, “Asphalt Coated Roofing Sheets”,

(n) CAN/CSA-A123.3, “Asphalt or Tar Saturated Roofing Felt”,

(o) CAN/CSA-A123.4, “Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems”,

(p) CAN/CSA-A123.5, “Asphalt Shingles Made from Glass Felt and Saturated with Mineral Granules”,

(q) CSA A123.17, “Asphalt-Saturated Felted Glass-Fibre Mat for Use in Construction of Built-Up Roofs”,

(r) CAN/CSA-A220.0-M, “Performance of Concrete Roof Tiles”,

(s) CSA O118.1, “Western Cedars Shakes and Shingles”, or

(t) CSA O118.2-M, “Eastern White Cedar Shingles”.

Text · e-Laws consolidated snapshot

9.26.2.2. — Nails

(1) Nails used for roofing shall be corrosion-resistant roofing or shingle nails conforming to CSA B111, “Wire Nails, Spikes and Staples”.

(2) Nails shall have sufficient length to penetrate through or 12 mm into roof sheathing.

(3) Nails used with asphalt roofing shall have a head diameter of not less than 9.5 mm and a shank thickness of not less than 2.95 mm.

(4) Nails used with wood shingles or shakes shall have a head diameter of not less than 4.8 mm and a shank thickness of not less than 2.0 mm and shall be stainless steel, aluminum or hot-dipped galvanized.

Text · e-Laws consolidated snapshot

9.26.2.3. — Staples

(1) Staples used to apply asphalt or wood shingles shall be corrosion-resistant and shall be driven with the crown parallel to the eaves.

(2) Staples used with asphalt shingles shall be not less than 19 mm long, 1.6 mm diam or thickness, with not less than a 25 mm crown, except that an 11 mm crown may be used as provided in Sentence 9.26.7.4.(2).

(3) Staples used with wood shingles shall be not less than 29 mm long, 1.6 mm diam or thickness, with not less than a 9.5 mm crown and shall be stainless steel or aluminum.

Text · e-Laws consolidated snapshot

9.26.3. — Slope of Roof Surfaces

Content not available for this version.

9.26.3.1. — Slope

(1) Except as provided in Sentences (2) and (3), the slopes on which roof coverings may be applied shall conform to Table 9.26.3.1.

(2) Asphalt and gravel or coal tar and gravel roofs may be constructed with lower slopes than required in Sentence (1) when effective drainage is provided by roof drains located at the lowest points on the roofs.

(3) Profiled metal roof cladding systems specifically designed for low-slope applications are permitted to be installed with lower slopes than required in Sentence (1), provided they are installed in conformance with the manufacturer’s written recommendations.

(4) Except where back-slope will not adversely affect adjacent supported or supporting elements due to water ingress, roofs and elements that effectively serve as roofs shall be constructed with sufficient slope away from,

(a) exterior walls, and

(b) guards that are connected to the roof, or to an element that effectively serves as a roof, by other than pickets or posts.

(5) The slope required in Sentence (4) shall be sufficient to maintain a positive slope,

(a) after expected shrinkage of the building frame, where these surfaces are supported by exterior walls and on exterior columns, and

(b) once design loading is taken into consideration, where these surfaces are cantilevered from exterior walls.

Editor's note

In the notes to Table-9.26.3.1., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.26.3.1. Roofing Types and Slope Limits Forming Part of Sentence 9.26.3.1.(1)

Column 1

Column 2

Column 3

Type of Roofing

Minimum Slope

Maximum Slope

Asbestos-Cement Corrugated Sheets

1 in 4

no limit

Asphalt Shingles

Low slope application

1 in 6

no limit

Normal application

1 in 3

no limit

Built-up Roofing

Asphalt base (without gravel)

1 in 25

1 in 2

Asphalt base (gravelled)

1 in 50(1)

1 in 4

Coal-tar base (gravelled)

1 in 50(1)

1 in 25

Cold process

1 in 25

1 in 1.33

Cedar Shakes

1 in 3

no limit

Clay Tile

1 in 2

no limit

Glass Fibre Reinforced Polyester Roofing Panels

1 in 4

no limit

Modified Bituminous Membranes

1 in 50

1 in 4

Profiled Metal Roofing

1 in 4(2)

no limit

Roll Roofing

480 mm wide selvage asphalt roofing

1 in 6

no limit

Cold application felt

1 in 50

1 in 1.33

Smooth and mineral surfaced

1 in 4

no limit

Sheet Metal Shingles

1 in 4(2)

no limit

Slate Shingles

1 in 2

no limit

Wood Shingles

1 in 4

no limit

Notes to Table 9.26.3.1.:

(1)See Sentence 9.26.3.1.(2).

(2)See Sentence 9.26.3.1.(3).

9.26.4. — Flashing at Intersections

Content not available for this version.

9.26.4.1. — Required Flashing at Intersections

(1) Except where the omission will not adversely affect adjacent supported or supporting elements, flashing shall be installed at junctions between roofs and,

(a) walls that rise above the roof, and

(b) guards that are connected to the roof by other than pickets or posts.

(2) For the purpose of Sentence (1), roofs shall include platforms that effectively serve as roofs with respect to accumulation or drainage of precipitation.

Text · e-Laws consolidated snapshot

9.26.4.2. — Materials

(1) Sheet metal flashing shall consist of not less than,

(a) 1.73 mm thick sheet lead,

(b) 0.33 mm thick galvanized steel,

(c) 0.33 mm thick copper,

(d) 0.35 mm thick zinc, or

(e) 0.48 mm thick aluminum.

Text · e-Laws consolidated snapshot

9.26.4.3. — Valley Flashing

(1) Where sloping surfaces of shingled roofs intersect to form a valley, the valley shall be flashed.

(2) Valley flashing shall be installed over continuous sheathing.

(3) Closed valleys shall not be used with rigid shingles on slopes of less than 1 in 1.2.

(4) Closed valley flashing shall consist of sheet metal, self sealing composite membranes consisting of polyethylene and bituminous material or one layer of either Type S smooth surface roll roofing or Type M mineral surface roll roofing (mineral surface down) not less than 600 mm wide, and nails shall not penetrate the flashing within 75 mm of its edge or 124 mm of the bottom of the valley centreline.

(5) Open valleys shall be flashed with,

(a) at least one layer of sheet metal not less than 600 mm wide, or

(b) no fewer than 2 layers of roll roofing.

(6) The bottom layer of roofing required in Sentence (4) shall consist of not less than Type S smooth roll roofing or Type M mineral surface roll roofing (mineral surface down) not less than 457 mm wide, centred in the valley and fastened with nails spaced not more than 450 mm o.c. located 25 mm away from the edges.

(7) The top layer of roofing required in Sentence (4) shall consist of not less than Type M mineral surface roll roofing (mineral surface up), 914 mm wide, centred in the valley, applied over a 100 mm wide strip of cement along each edge of the bottom layer, and fastened with a sufficient number of nails to hold it in place until the shingles are applied.

Text · e-Laws consolidated snapshot

9.26.4.4. — Intersection of Shingle Roofs and Masonry

(1) The intersection of shingle roofs and masonry walls or chimneys shall be protected with flashing.

(2) Counter flashing required in Sentence (1) shall be embedded not less than 25 mm in the masonry and shall extend not less than 150 mm down the masonry and lap the lower flashing not less than 100 mm.

(3) Flashing along the slopes of a roof described in Sentence (1) shall be stepped so that there is not less than a 75 mm head lap in both the lower flashing and counter flashing.

(4) Where the roof described in Sentence (1) slopes upwards from the masonry, the flashing shall extend up the roof slope to a point equal in height to the flashing on the masonry, but not less than 1.5 times the shingle exposure.

Text · e-Laws consolidated snapshot

9.26.4.5. — Intersection of Shingle Roofs and Walls Other Than Masonry

(1) The intersection of shingle roofs and walls clad with other than masonry shall be protected with flashing.

(2) Flashing required in Sentence (1) shall be installed so that it extends up the wall not less than 75 mm behind the sheathing paper, and extends not less than 75 mm horizontally.

(3) Along the slope of the roof, the flashing required in Sentence (1) shall be stepped with not less than a 75 mm head lap.

Text · e-Laws consolidated snapshot

9.26.4.6. — Intersection of Built-Up Roofs and Masonry

(1) The intersection of built-up roofs with masonry walls or chimneys shall have a cant strip at the intersection and a roofing membrane shall be mopped over the cant strip and not less than 150 mm up the wall.

(2) Counter flashing installed over the intersection referred to in Sentence (1) shall be embedded not less than 25 mm in the masonry, and shall be of sufficient length to extend down not less than 150 mm, lapping the membrane on the masonry not less than 100 mm.

Text · e-Laws consolidated snapshot

9.26.4.7. — Intersection of Built-Up Roofs and Walls other than Masonry

(1) The intersection of built-up roofs with walls clad with other than masonry shall have a cant strip at the intersection.

(2) The roofing membrane shall be mopped over the cant strip referred to in Sentence (1).

(3) Flashing plies shall extend not less than 150 mm up the wall referred to in Sentence (1) behind the sheathing paper.

Text · e-Laws consolidated snapshot

9.26.4.8. — Chimney Saddles

(1) Except as otherwise permitted in Sentence (5), chimney saddles shall be installed where the upper side of a chimney on a sloping roof is more than 750 mm wide.

(2) Chimney saddles shall be covered with sheet metal or roofing material of equivalent weight and quality equivalent to the roofing.

(3) Saddles shall be flashed where they intersect the roof.

(4) The intersection of the saddle and the chimney shall be flashed and counterflashed as in Article 9.26.4.4.

(5) A chimney saddle need not be installed if the intersection between the chimney and roof is protected by sheet metal flashing that extends up the chimney to a height equal to at least one sixth the width of the chimney, but not less than 150 mm, and up the roof slope to a point equal in height to the flashing on the chimney, but not less than 1.5 times the shingle exposure.

(6) Flashing described in Sentence (5) at the chimney shall be counterflashed as required by Article 9.26.4.4.

Text · e-Laws consolidated snapshot

9.26.5. — Eave Protection for Shingles and Shakes

Content not available for this version.

9.26.5.1. — Required Eave Protection

(1) Except as provided in Sentence (2), eave protection shall be provided on shingle, shake or tile roofs, extending from the edge of the roof a minimum of 900 mm up the roof slope to a line not less than 300 mm inside the inner face of the exterior wall.

(2) Eave protection is not required,

(a) over unheated garages, carports and porches,

(b) where the roof overhang exceeds 900 mm measured along the roof slope from the edge of the roof to the inner face of the exterior wall,

(c) on roofs of asphalt shingles installed in accordance with Subsection 9.26.8.,

(d) on roofs with slopes of 1 in 1.5 or greater, or

(e) in regions with 3 500 or fewer degree-days.

Text · e-Laws consolidated snapshot

9.26.5.2. — Materials

(1) Eave protection shall be laid beneath the starter strip and shall consist of,

(a) No. 15 asphalt-saturated felt laid in two plies lapped 480 mm and cemented together with lap cement,

(b) Type M or S roll roofing laid with not less than 100 mm head and end laps cemented together with lap cement,

(c) glass fibre or polyester fibre coated base sheets, or

(d) self-sealing composite membranes consisting of modified bituminous coated material.

Text · e-Laws consolidated snapshot

9.26.6. — Underlay Beneath Shingles

Content not available for this version.

9.26.6.1. — Materials

(1) Except as required in Sentence (2), when underlay is used beneath shingles, it shall be,

(a) asphalt-saturated sheathing paper weighing not less than 0.195 kg/m², or

(b) No. 15 plain or perforated asphalt-saturated felt.

(2) Underlay used beneath wood shingles shall be breather type.

Text · e-Laws consolidated snapshot

9.26.6.2. — Installation

(1) When used with shingles, underlay shall be installed parallel to the eaves with head and end lap of not less than 50 mm.

(2) The top edge of each strip referred to in Sentence (1) shall be fastened with sufficient roofing nails to hold it in place until the shingles are applied.

(3) The underlay referred to in Sentence (1) shall overlap the eave protection by not less than 100 mm

Editor's note

As filed in O. Reg. 350/06, Sentence (3) of Article 9.26.6.2. ends without a terminal period ('...shall overlap the eave protection by not less than 100 mm'); the current e-Laws consolidation editorially supplies the missing period, with no amending regulation making the change. This map preserves the sentence as filed.

9.26.7. — Asphalt Shingles on Slopes of 1 in 3 or Greater

Content not available for this version.

9.26.7.1. — Coverage

(1) Coverage shall be not less than 2 thicknesses of shingle over the entire roof, disregarding cutouts.

Text · e-Laws consolidated snapshot

9.26.7.2. — Starter Strip

(1) A starter strip shall be installed along the lower edge of the roof so that it extends approximately 12 mm beyond the eaves and rake of the roof and fastened along the bottom edge with nails spaced not more than 300 mm o.c.

(2) Starter strips shall be at least Type M mineral-surfaced roll roofing not less than 300 mm wide, or shingles of the same weight and quality as those used as a roof covering with tabs facing up the roof slope.

(3) Starter strips need not be provided where eave protection of not less than Type M mineral-surfaced roll roofing is provided or self-sealing composite membranes consisting of polyethylene and bituminous material is provided.

Text · e-Laws consolidated snapshot

9.26.7.3. — Head Lap

(1) Shingles shall have a head lap of not less than 50 mm.

Text · e-Laws consolidated snapshot

9.26.7.4. — Fasteners

(1) Except as provided in Sentence (2), shingles shall be fastened with at least 4 nails or staples for 1 000 mm wide shingles so that no nails or staples are exposed.

(2) Where staples with an 11 mm crown are used, shingles shall be fastened with at least 6 staples.

(3) Fasteners may be reduced for narrower shingles in proportion to the width of the shingle or when shingles incorporating interlocking devices are used.

(4) Fasteners referred to in Sentences (1) and (2) shall be located 25 mm to 40 mm from each end of each strip shingle with other fasteners equally spaced between them.

(5) Fasteners referred to in Sentences (1) and (2) shall be located not less than 12 mm above the tops of the cutouts.

Text · e-Laws consolidated snapshot

9.26.7.5. — Securing of Tabs

(1) Shingle tabs shall be secured by a spot of plastic cement not exceeding 25 mm diam under the centre of each tab or by interlocking devices or self-sealing strips.

Text · e-Laws consolidated snapshot

9.26.7.6. — Hips and Ridges

(1) Shingles on hips and ridges shall be applied so they extend not less than 100 mm on either side of the hip or ridge, and shall be lapped not less than 150 mm.

(2) Shingles referred to in Sentence (1) shall be fastened with nails or staples on each side located not more than 25 mm from the edge and 25 mm above the butt of the overlying shingle.

Text · e-Laws consolidated snapshot

9.26.7.7. — Eave Protection

(1) Eave protection shall conform to Subsection 9.26.5.

Text · e-Laws consolidated snapshot

9.26.7.8. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.8. — Asphalt Shingles on Slopes of Less Than 1 in 3

Content not available for this version.

9.26.8.1. — Coverage

(1) Except for the first 2 courses, coverage shall be not less than 3 thicknesses of shingle over the entire roof, disregarding cutouts.

Text · e-Laws consolidated snapshot

9.26.8.2. — Starter Strip

(1) A starter strip shall be installed as in Article 9.26.7.2.

(2) Starter strips required in Sentence (1) shall be laid in a continuous band of cement not less than 200 mm wide.

Text · e-Laws consolidated snapshot

9.26.8.3. — Securing of Tabs

(1) Shingle tabs shall be secured with cold application cement applied at the rate of not less than 0.5 L/m² of cemented area, or hot application asphalt applied at the rate of 1 kg/m² of cemented area.

Text · e-Laws consolidated snapshot

9.26.8.4. — Securing of Shingle Courses

(1) The first course of shingles shall be secured by a continuous band of cement along the eaves applied so that the width of the band equals the shingle exposure plus 100 mm.

(2) The succeeding courses of shingles shall be secured by a continuous band of cement applied so that the width of the band equals the shingle exposure plus 50 mm.

(3) The band required in Sentence (2) shall be located not more than 50 mm above the butt of the overlying course of shingles.

Text · e-Laws consolidated snapshot

9.26.8.5. — Hips and Ridges

(1) Shingles on hips and ridges shall be not less than 300 mm wide applied to provide triple coverage.

(2) Shingles referred to in Sentence (1) shall be cemented to the roof shingles and to each other with a coat of cement and fastened with nails or staples located 40 mm above the butt of the overlying shingle and 50 mm from each edge.

Text · e-Laws consolidated snapshot

9.26.8.6. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.8.7. — Fastening

(1) Shingles shall be fastened in accordance with Article 9.26.7.4.

Text · e-Laws consolidated snapshot

9.26.9. — Wood Roof Shingles

Content not available for this version.

9.26.9.1. — Decking

(1) Decking for wood shingled roofs may be continuous or spaced.

Text · e-Laws consolidated snapshot

9.26.9.2. — Grade

(1) Western cedar shingles shall be not less than No. 2 grade.

(2) Eastern white cedar shingles shall be not less than B (clear) grade.

Text · e-Laws consolidated snapshot

9.26.9.3. — Size

(1) Wood shingles shall be not less than 400 mm long and not less than 75 mm nor more than 350 mm wide.

Text · e-Laws consolidated snapshot

9.26.9.4. — Spacing and Joints

(1) Shingles shall be spaced approximately 6 mm apart and offset at the joints in adjacent courses not less than 40 mm so that joints in alternate courses are staggered.

Text · e-Laws consolidated snapshot

9.26.9.5. — Fastening

(1) Shingles shall be fastened with 2 nails or staples located approximately 20 mm from the sides of the shingle and 40 mm above the exposure line.

Text · e-Laws consolidated snapshot

9.26.9.6. — Exposure

(1) The exposure of wood roof shingles shall conform to Table 9.26.9.6.

Text · e-Laws consolidated snapshot

Table 9.26.9.6. Exposure of Wood Shingles Forming Part of Sentence 9.26.9.6.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Roof Slope

Maximum Exposure, mm

No. 1 or A Grade Length of Shingle, mm

No. 2 or B Grade Length of Shingle, mm

400

450

600

400

450

600

<1 in 3

100

115

165

90

100

140

≥1 in 3

125

140

190

100

115

165

9.26.9.7. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.9.8. — Eave Protection

(1) Eave protection shall conform to Subsection 9.26.5.

Text · e-Laws consolidated snapshot

9.26.10. — Cedar Roof Shakes

Content not available for this version.

9.26.10.1. — Size and Thickness

(1) Shakes shall be not less than 450 mm long and not less than 100 mm nor more than 350 mm wide with a butt thickness of not more than 32 mm and not less than 9 mm.

Text · e-Laws consolidated snapshot

9.26.10.2. — Underlay

(1) Where eave protection is not provided, an underlay conforming to the requirements in Article 9.26.6.1. for wood shingles shall be laid as a strip not less than 900 mm wide along the eaves.

(2) A strip of material similar to that described in Sentence (1) not less than 450 mm wide shall be interlayed between each course of shakes with the bottom edge of the strip positioned above the butt line at a distance equal to double the exposure of the shakes.

(3) Interlayed strips in Sentence (2) shall be lapped at least 150 mm at hips and ridges in a manner that will prevent water from reaching the roof sheathing.

Text · e-Laws consolidated snapshot

9.26.10.3. — Spacing and Joints

(1) Shakes shall be spaced 6 mm to 9 mm apart and the joints in one course shall be separated not less than 40 mm from joints in adjacent courses.

Text · e-Laws consolidated snapshot

9.26.10.4. — Fastening

(1) Shakes shall be fastened with nails located approximately 20 mm from the sides of the shakes and 40 mm above the exposure line.

Text · e-Laws consolidated snapshot

9.26.10.5. — Exposure

(1) The exposure of wood shakes shall not exceed,

(a) 190 mm for shakes not less than 450 mm long, and

(b) 240 mm for shakes not less than 600 mm long.

Text · e-Laws consolidated snapshot

9.26.10.6. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.10.7. — Eave Protection

(1) Eave protection shall conform to Subsection 9.26.5.

Text · e-Laws consolidated snapshot

9.26.10.8. — Grade

(1) Shakes shall be not less than No. 1 or Handsplit grade.

Text · e-Laws consolidated snapshot

9.26.11. — Built-Up Roofs

Content not available for this version.

9.26.11.1. — Quantity of Materials

(1) The quantities of bituminous materials used on built-up roofs shall conform to Table 9.26.11.1.

Text · e-Laws consolidated snapshot

Table 9.26.11.1. Quantities of Bitumen for Built-Up Roofs Forming Part of Sentence 9.26.11.1.(1)

Column 1

Column 2

Column 3

Type of Roof

Amount of Bitumen per Square Metre of Roof Surface

Mopping Coats Between Layers

Flood Coat

Asphalt and aggregate

1 kg

3 kg

Coal-tar and aggregate

1.2 kg

3.6 kg

Cold process roofing

0.75 L cold process cement

2 L cold process top coating

9.26.11.2. — Coal-Tar and Asphalt Products

(1) Coal-tar products and asphalt products shall not be used together in built-up roof construction.

Text · e-Laws consolidated snapshot

9.26.11.3. — Roof Felts

(1) Bitumen roofing felts shall be not less than No.15 felt.

Text · e-Laws consolidated snapshot

9.26.11.4. — Aggregate Surfacing

(1) Aggregate used for surfacing built-up roofs shall be clean, dry and durable and shall consist of particles of gravel, crushed stone or air-cooled blast furnace slag having a size of from 6 mm to 15 mm.

(2) The minimum amount of aggregate surfacing per square metre of roof surface shall be 15 kg gravel or crushed stone or 10 kg crushed slag.

Text · e-Laws consolidated snapshot

9.26.11.5. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.11.6. — Number of Layers

(1) Built-up roofing shall consist of at least 3 mopped-down layers of roofing felt flood coated with bitumen.

Text · e-Laws consolidated snapshot

9.26.11.7. — Installation of Layers

(1) In hot process applications each layer of bitumen-saturated felt shall be laid while the bitumen is hot, with each layer overlapping the previous one.

(2) The full width under each lap referred to in Sentence (1) shall be coated with bitumen so that in no place does felt touch felt.

(3) Felt shall be laid free of wrinkles and shall be rolled directly into the hot bitumen and broomed forward and outward from the centre to ensure complete adhesion.

Text · e-Laws consolidated snapshot

9.26.11.8. — Roofing over Wood-Based Sheathing

(1) Except as permitted in Sentence (2), built-up roofing applied over wood, plywood, OSB or waferboard roof sheathing shall be laid over an additional base layer of felt laid dry over the entire roof deck with at least a 50 mm headlap and a 50 mm sidelap between each sheet.

(2) Where plywood, OSB or waferboard roof sheathing is used, the dry layer of felt required in Sentence (1) may be omitted when the joints are taped and the sheathing is primed with asphalt.

Text · e-Laws consolidated snapshot

9.26.11.9. — Attachment to Decking

(1) Roofing shall be securely attached to the decking or where insulation is applied above the deck, the insulation shall be securely attached to the deck before the first layer of felt is fastened to the insulation.

Text · e-Laws consolidated snapshot

9.26.11.10. — Cant Strips

(1) Except as permitted in Sentence (4), a cant strip shall be provided at the edges of roofs.

(2) No fewer than 2 plies of the roofing membrane shall be carried over the top of the cant strip.

(3) Flashing shall extend over the top of the cant strip and be shaped to form a drip.

(4) The cant strip required in Sentence (1) may be omitted where a gravel stop is provided at the edge of roofs.

(5) The roofing membranes shall be carried over the edge of the roof before the gravel stop is fastened and 2 plies of roofing membrane mopped to the top surface of the gravel stop referred to in Sentence (4) before the flood coat is applied.

(6) The gravel stop referred to in Sentence (4) shall extend over the edge of the roof to form a drip or shall be flashed so that the flashing extends over the edge to form a drip.

Text · e-Laws consolidated snapshot

9.26.12. — Selvage Roofing

Content not available for this version.

9.26.12.1. — Double Coverage

(1) Wide selvage asphalt roofing shall provide double coverage over the entire roof surface.

Text · e-Laws consolidated snapshot

9.26.12.2. — Joints

(1) Plies of selvage roofing shall be cemented together to ensure a water-tight joint.

Text · e-Laws consolidated snapshot

9.26.13. — Sheet Metal Roofing

Content not available for this version.

9.26.13.1. — Thickness

(1) Sheet metal roofing shall be not less than,

(a) 0.33 mm thick galvanized steel,

(b) 0.46 mm thick copper,

(c) 0.46 mm thick zinc, or

(d) 0.48 mm thick aluminum.

Text · e-Laws consolidated snapshot

9.26.13.2. — Support

(1) Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be designed to support the specified live loads for roofs.

Text · e-Laws consolidated snapshot

9.26.14. — Glass Reinforced Polyester Roofing

Content not available for this version.

9.26.14.1. — Support

(1) Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced supports, the panels shall be designed to support the specified roof loads.

Text · e-Laws consolidated snapshot

9.26.15. — Hot Applied Rubberized Asphalt Roofing

Content not available for this version.

9.26.15.1. — Installation

(1) Hot applied rubberized asphalt roofing shall be installed in accordance with CAN/CGSB-37.51-M, “Application for Hot Applied Rubberized Asphalt for Roofing and Waterproofing”.

Text · e-Laws consolidated snapshot

9.26.16. — Polyvinyl Chloride Sheet Roofing

Content not available for this version.

9.26.16.1. — Installation

(1) Polyvinyl chloride sheet applied roofing membrane shall be installed in accordance with CGSB 37-GP-55M, “Application of Sheet Applied Flexible Polyvinyl Chloride Roofing Membrane”.

Text · e-Laws consolidated snapshot

9.26.17. — Concrete Roof Tiles

Content not available for this version.

9.26.17.1. — Installation

(1) Concrete roof tiles shall be installed according to CAN/CSA-A220.1-M, “Installation of Concrete Roof Tiles”.

Text · e-Laws consolidated snapshot

9.26.18. — Roof Drains and Downspouts

Content not available for this version.

9.26.18.1. — Roof Drains

(1) When roof drains are provided they shall conform to Part 7.

Text · e-Laws consolidated snapshot

9.26.18.2. — Downspouts

(1) Where downspouts are provided and are not connected to a sewer, extensions shall be provided to carry rainwater away from the building in a manner that will prevent soil erosion.

Text · e-Laws consolidated snapshot

9.27. — Cladding

Content not available for this version.

9.27.1. — Application

Content not available for this version.

9.27.1.1. — General

(1) Where lumber, wood shingles, shakes, fibre-cement shingles, planks and sheets, plywood, OSB, waferboard, hardboard, vinyl, aluminum and steel, including trim and soffits, are installed as cladding on wood-frame walls exposed to precipitation, the cladding assembly shall comply with,

(a) Subsections 9.27.2. to 9.27.13., or

(b) Part 5.

(2) Where stucco is installed as cladding on wood-frame or masonry walls exposed to precipitation, the cladding assembly shall comply with,

(a) Subsections 9.27.2. to 9.27.4., and Section 9.28., or

(b) Part 5.

(3) Where masonry serves as cladding on wood-frame or masonry walls exposed to precipitation, the cladding assembly shall comply with,

(a) Subsections 9.27.2. to 9.27.4., and Section 9.20., or

(b) Part 5.

(4) Where asphalt shingles are installed as cladding on wood-frame walls exposed to precipitation, the cladding assembly shall comply with,

(a) Subsections 9.26.7. and 9.27.2. to 9.27.4., or

(b) Part 5.

(5) Where cladding materials other than those described in Sentences (1) to (4) are installed, or where these are installed on substrates other than those identified in Sentences (1) to (4), the materials and installation shall comply with Part 5.

Text · e-Laws consolidated snapshot

9.27.2. — Required Protection from Precipitation

Content not available for this version.

9.27.2.1. — Minimizing and Preventing Ingress and Damage

(1) Except where exterior walls are protected from precipitation or where it can be shown that ingress will not adversely affect occupant health or safety, exterior walls shall be designed and constructed to,

(a) minimize the ingress of precipitation into the assembly, and

(b) prevent ingress into interior space.

(2) Except where exterior walls are protected from specific mechanisms of deterioration, such as mechanical impact and ultraviolet radiation, exterior walls shall be designed and constructed to minimize the likelihood of their required performance being reduced to an unacceptable level as a result of those mechanisms.

Text · e-Laws consolidated snapshot

9.27.2.2. — Minimum Protection from Precipitation Ingress

(1) Exterior walls exposed to precipitation shall be protected against ingress of precipitation with an exterior cladding assembly consisting of a first plane of protection and a second plane of protection where the wall encloses spaces of residential occupancy or spaces that directly serve spaces of residential occupancy.

Text · e-Laws consolidated snapshot

9.27.2.3. — First and Second Planes of Protection

(1) Where walls required to provide protection from precipitation comprise assemblies with first and second planes of protection,

(a) the first plane of protection shall,

(i) consist of cladding, with appropriate trim, accessory pieces and fasteners, and

(ii) be designed and constructed to minimize the passage of rain and snow into the wall by minimizing holes and managing precipitation ingress caused by kinetic energy of raindrops, surface tension, capillarity, gravity, and air pressure differences,

(b) the second plane of protection shall be designed and constructed to,

(i) intercept all precipitation that gets past the first plane of protection, and

(ii) effectively dissipate any precipitation to the exterior, and

(c) the protection provided by the first and second planes of protection shall be maintained at,

(i) wall penetrations created by the installation of components and services such as windows, doors, ventilation ducts, piping, wiring and electrical outlets, and

(ii) the interface with other wall assemblies.

Text · e-Laws consolidated snapshot

9.27.2.4. — Protection of Cladding from Moisture

(1) A clearance of not less than 200 mm shall be provided between finished ground and cladding that is adversely affected by moisture, such as untreated wood, plywood, OSB, waferboard and hardboard.

(2) A clearance of not less than 50 mm shall be provided between a roof surface and cladding that is adversely affected by moisture, such as untreated wood, plywood, OSB, waferboard and hardboard.

Text · e-Laws consolidated snapshot

9.27.3. — Second Plane of Protection

Content not available for this version.

9.27.3.1. — Elements of the Second Plane of Protection

(1) The second plane of protection shall consist of a drainage plane with appropriate inner boundary and flashing to dissipate rainwater to the exterior.

(2) The inner boundary of the drainage plane shall comply with Articles 9.27.3.2.v1 to 9.27.3.6.

(3) The protection provided by the second plane of protection shall be maintained,

(a) at wall penetrations created by the installation of components and services such as windows, doors, ventilation ducts, piping, wiring and electrical outlets, and

(b) at the interface with other wall assemblies.

(4) Flashing material and installation shall comply with Articles 9.27.3.7. and 9.27.3.8.

Text · e-Laws consolidated snapshot

9.27.3.2. — Sheathing Membrane Material Standard

(1) Sheathing membranes shall conform to the performance requirements of CAN/CBSB-51.32-M, “Sheathing, Membrane, Breather Type”.

Text · e-Laws consolidated snapshot

9.27.3.3. — Required Sheathing Membrane and Installation

(1) Except as provided in Articles 9.27.3.4. to 9.27.3.6., at least one layer of sheathing membrane shall be applied beneath siding, stucco or masonry veneer.

(2) Sheathing membrane required in Sentence (1) shall be applied so that joints are lapped not less than 100 mm.

(3) Where sheathing membrane required in Sentence (1) is applied horizontally, the upper sheets shall overlap the lower sheets.

Text · e-Laws consolidated snapshot

9.27.3.4. — Insulating Sheathing in Lieu of Sheathing Membrane

(1) Where non-wood-based rigid exterior insulating sheathing, or exterior insulating sheathing with an integral sheathing membrane is installed, a separate sheathing membrane is not required.

(2) Where insulating sheathing is installed as provided in Sentence (1),

(a) sheathing panels subject to moisture deterioration shall be sealed at all joints, and

(b) the joints of sheathing panels not subject to moisture deterioration shall be,

(i) sealed at all joints, or

(ii) lapped or tongue and groove, and detailed to ensure drainage of water to the exterior.

Text · e-Laws consolidated snapshot

9.27.3.5. — Sheathing Membranes in Lieu of Sheathing

(1) Except as provided in Article 9.27.3.6., where no sheathing is used, at least 2 layers of sheathing membrane shall be applied beneath the cladding.

(2) All joints in the sheathing membrane required in Sentence (1) shall occur over framing, and the membrane shall be fastened to the framing with roofing nails or staples spaced not more than 150 mm along the edges of the outer layer of sheathing paper.

(3) Wall sheathing is permitted to be used in lieu of 1 layer of sheathing membrane required in Sentence (1), and the thickness need not conform to Table 9.23.16.2.A.v1

Text · e-Laws consolidated snapshot

9.27.3.6. — Face Sealed Cladding

(1) Sheathing membrane is permitted to be omitted beneath cladding when the joints in the cladding are formed to effectively prevent the passage of wind and rain in conformance with Sentence (2) or (3), as applicable.

(2) Cladding consisting of sheets of plywood, hardboard, OSB, waferboard or fibre cement is considered to meet the requirements of Sentence (1), provided the cladding is applied so that

(a) all edges are directly supported by framing, and

(b) the vertical joints between adjacent sheets are sealed and,

(i) covered with battens,

(ii) shiplapped, or

(iii) otherwise matched to provide weathertight joints, and

(c) the horizontal joints between adjacent sheets are sealed and,

(i) shiplapped, or

(ii) otherwise matched to provide weathertight joints.

(3) Metal siding consisting of sheets of metal is considered to meet the requirements of Sentence (1) where the joints between sheets are of the locked-seam type.

Text · e-Laws consolidated snapshot

9.27.3.7. — Flashing Materials

(1) Flashing shall consist of not less than,

(a) 1.73 mm thick sheet lead,

(b) 0.33 mm thick galvanized steel,

(c) 0.46 mm thick copper,

(d) 0.46 mm thick zinc,

(e) 0.48 mm thick aluminum, or

(f) 1.02 mm thick vinyl.

Text · e-Laws consolidated snapshot

9.27.3.8. — Flashing Installation

(1) Except as provided in Sentence (2), flashing shall be installed at,

(a) every horizontal junction between claddings elements,

(b) every horizontal offset in the cladding, and

(c) every horizontal line where the cladding substrates change and where,

(i) the substrates differ sufficiently for stresses to be concentrated along that line, or

(ii) the installation of the cladding on the lower substrate may compromise the drainage of moisture from behind the cladding above.

(2) Flashing need not be installed as described in Sentence (1),

(a) where the upper cladding elements overlap the lower cladding elements by not less than 25 mm,

(b) where,

(i) the cladding above and below the joint is installed outboard of a drained and vented air space, and

(ii) the horizontal detail is constructed so as to minimize ingress of precipitation into the air space, or

(c) at horizontal construction joints in stucco, where,

(i) the joint is finished with an expansion-contraction strip, and

(ii) the cladding is installed outboard of a drained and vented air space.

(3) Except as provided in Sentence (6), flashing shall be installed over exterior wall openings where the vertical distance from the bottom of the eave to the top of the trim is more than one-quarter of the horizontal overhang of the eave.

(4) Flashing described in Sentences (1) and (3) shall,

(a) extend not less that 50 mm upward inboard of the sheathing membrane or sheathing installed in lieu of the sheathing membrane,

(b) have a slope of not less than 6% toward the exterior after the expected shrinkage of the building frame,

(c) terminate at each end with an end-dam,

(i) with a height in millimetres not less than 25 mm or 1/10 of the value of the 1 in 5 driving rain wind pressure in Pa, and

(ii) at the height defined in Subclause (c)(i), extending to the face of the adjacent cladding,

(d) lap not less than 10 mm vertically over the building element below, and

(e) terminate in a drip extending not less than 5 mm outward from the outer face of the building element below.

(5) Except as provided in Sentence (6), where the sills of windows and doors installed in exterior walls are not self-flashing, flashing shall be installed between the underside of the window or door and the wall construction below.

(6) Where a window or exterior door is provided with an integral exterior flange and is designed to be installed on the exterior of essentially flat lock-seam metal cladding without a head or sill flashing, the flange shall be,

(a) bedded into a non-hardening sealant material, and

(b) screwed down over the sealant through to the wall framing to form a waterproof joint.

Editor's note

As filed in O. Reg. 350/06, Subclause (4)(c)(ii) of Article 9.27.3.8. cites 'the height defined in Subclause (c)(i)' with the full clause-and-subclause designation; the current e-Laws consolidation editorially abbreviates the citation to 'Subclause (i)', with no amending regulation making the change. Both forms refer to the same subclause, and this map preserves the citation as filed.

9.27.4. — Caulking

Content not available for this version.

9.27.4.1. — Required Caulking

(1) Caulking shall be provided where required to prevent the entry of water into the structure.

(2) Caulking shall be provided between masonry, siding or stucco and the adjacent door and window frames or trim, including sills unless such locations are completely protected from the entry of rain.

(3) Caulking shall be provided at vertical joints between different cladding materials unless the joint is suitably lapped or flashed to prevent the entry of rain.

Text · e-Laws consolidated snapshot

9.27.4.2. — Materials

(1) Caulking shall be,

(a) a non-hardening type suitable for exterior use,

(b) selected for its ability to resist the effects of weathering, and

(c) compatible with and adhere to the substrate to which it is applied.

(2) Caulking shall conform to,

(a) CGSB 19-GP-5M, “Sealing Compound, One Component, Acrylic Base, Solvent Curing”,

(b) CAN/CGSB-19.13-M, “Sealing Compound, One Component, Elastomeric, Chemical Curing”,

(c) CGSB 19-GP-14M, “Sealing Compound, One Component, Butyl-Polyisobutylene Polymer Base, Solvent Curing”, or

(d) CAN/CGSB-19.24-M, “Multicomponent, Chemical Curing Sealing Compound”.

Text · e-Laws consolidated snapshot

9.27.5. — Attachment of Cladding

Content not available for this version.

9.27.5.1. — Attachment

(1) Except as permitted in Sentences (2) to (7), cladding shall be fastened to the framing members or furring members, or to blocking between the framing members.

(2) Vertical lumber and stucco lath or reinforcing are permitted to be attached to sheathing only where the sheathing consists of not less than,

(a) 14.3 mm lumber,

(b) 12.5 mm plywood, or

(c) 12.5 mm OSB or waferboard.

(3) Vertically applied metal siding and wood shingles and shakes are permitted to be attached to the sheathing only where the sheathing consists of not less than,

(a) 14.3 mm lumber,

(b) 7.5 mm plywood, or

(c) 7.5 mm OSB or waferboard.

(4) Asbestos-cement shingles are permitted to be attached to the sheathing only when the sheathing consists of not less than,

(a) 14.3 mm lumber,

(b) 9.5 mm plywood, or

(c) 9.5 mm OSB or waferboard.

(5) Where wood shingles or shakes are applied to sheathing that is not suitable for attaching the shingles or shakes, the shingles or shakes may be attached to a wood lath not less than 38 mm by 9.5 mm thick securely nailed to the framing and applied as described in Article 9.27.7.5.

(6) Where asbestos-cement shingles are applied to sheathing that is not suitable for attaching the shingles, the shingles may be fastened to a wood lath not less than 89 mm by 9.5 mm thick securely nailed to the framing.

(7) Lath referred to in Sentence (6) shall be applied so that it overlaps the preceding shingle course by not less than 20 mm.

Text · e-Laws consolidated snapshot

9.27.5.2. — Blocking

(1) Blocking for the attachment of cladding shall be not less than 38 mm by 38 mm lumber securely nailed to the framing and spaced not more than 600 mm o.c.

Text · e-Laws consolidated snapshot

9.27.5.3. — Furring

(1) Except as permitted in Sentences 9.27.5.1.(5) and (6), furring for the attachment of cladding shall be not less than 19 mm by 38 mm lumber when applied over sheathing.

(2) When applied without sheathing, furring referred to in Sentence (1) shall be not less than,

(a) 19 mm by 64 mm lumber on supports spaced not more than 400 mm o.c., or

(b) 19 mm by 89 mm on supports spaced not more than 600 mm o.c.

(3) Furring referred to in Sentence (1) shall be,

(a) securely fastened to the framing, and

(b) spaced not more than 600 mm o.c.

Text · e-Laws consolidated snapshot

9.27.5.4. — Size and Spacing of Fasteners

(1) Nail or staple size and spacing for the attachment of cladding and trim shall conform to Table 9.27.5.4.

Text · e-Laws consolidated snapshot

Table 9.27.5.4. Attachment of Cladding Forming Part of Sentence 9.27.5.4.(1)

Column 1

Column 2

Column 3

Column 4

Type of Cladding

Minimum Nail or Staple Length, mm

Minimum Number of Nails or Staples

Maximum Nail or Staple Spacing, mm (o.c.)

Wood trim

51

600

Lumber siding or horizontal siding made from sheet metal

51

600

Metal cladding

38

600 (nailed to framing)

400 (nailed to sheathing only)

Wood shakes

up to 200 mm in width

51

2

over 200 mm in width

51

3

Wood shingles

200 mm in width

32

2

over 200 mm in width

32

3

Asbestos-cement shingles

32

2

Panel or sheet type cladding

up to 7 mm thick

38

150 (along edges)

more than 7 mm thick

51

300 (along intermediate supports)

9.27.5.5. — Fastener Materials

(1) Nails or staples for the attachment of cladding and wood trim shall be corrosion-resistant and shall be compatible with the cladding material.

Text · e-Laws consolidated snapshot

9.27.5.6. — Expansion and Contraction

(1) Fasteners for metal or vinyl cladding shall be positioned to permit expansion and contraction of the cladding.

Text · e-Laws consolidated snapshot

9.27.5.7. — Penetration of Fasteners

(1) Fasteners for shakes and shingles shall penetrate through the nail-holding base or not less than 19 mm into the framing.

(2) Fasteners for cladding other than that described in Sentence (1) shall penetrate through the nail-holding base or not less than 25 mm into the framing.

Text · e-Laws consolidated snapshot

9.27.6. — Lumber Siding

Content not available for this version.

9.27.6.1. — Materials

(1) Lumber siding shall be sound, free of knot holes, loose knots, through checks or splits.

Text · e-Laws consolidated snapshot

9.27.6.2. — Thickness and Width

(1) Drop, rustic, novelty, lapped board and vertical wood siding shall be not less than 14.3 mm thick and not more than 286 mm wide.

(2) Bevel siding shall be,

(a) not less than 5 mm thick at the top, and

(b) not less than,

(i) 12 mm thick at the butt for sidings 184 mm or less in width, and

(ii) 14.3 mm thick at the butt for sidings wider than 184 mm.

(3) Bevel siding shall be not more than 286 mm wide.

Text · e-Laws consolidated snapshot

9.27.6.3. — Joints

(1) Lumber siding shall prevent water from entering at the joints by the use of lapped or matched joints or by vertical wood battens.

(2) Siding shall overlap not less than 1 mm per 16 mm width of lumber, but not less than,

(a) 9.5 mm for matched siding,

(b) 25 mm for lapped bevel siding, or

(c) 12 mm for vertical battens.

Text · e-Laws consolidated snapshot

9.27.7. — Wood Shingles and Shakes

Content not available for this version.

9.27.7.1. — Materials

(1) Shingles and shakes shall conform to,

(a) CSA O118.1, “Western Cedars Shakes and Shingles”, or

(b) CSA O118.2-M, “Eastern White Cedar Shingles”.

(2) Western cedar shakes shall be not less than No. 1 grade or Handsplit grade, and western cedar shingles not less than No. 2 grade, except that No. 3 grade may be used for undercoursing.

(3) Eastern white cedar shakes shall be at least B (clear) grade, except that C grade may be used for undercoursing.

Text · e-Laws consolidated snapshot

9.27.7.2. — Width

(1) Shingles and shakes shall be not less than 65 mm or more than 350 mm wide.

Text · e-Laws consolidated snapshot

9.27.7.3. — Fasteners

(1) Shingles or shakes shall be fastened with nails located approximately 20 mm from each edge and not less than 25 mm above the exposure line for single-course applications, or approximately 50 mm above the butt for double-course applications.

Text · e-Laws consolidated snapshot

9.27.7.4. — Offsetting of Joints

(1) In single-course application, joints in succeeding courses shall be offset at least 40 mm so that joints in any 2 of 3 consecutive courses are staggered.

(2) In double-course application, joints in the outer course shall be offset from joints in the under-course by not less than 40 mm, and joints in succeeding courses shall be offset not less than 40 mm.

Text · e-Laws consolidated snapshot

9.27.7.5. — Fastening to Lath

(1) When lath is used with double-course application (see Sentence 9.27.5.1.(5)), it shall be spaced according to the exposure and securely fastened to the framing.

(2) The butts of the under-course of the application referred to in Sentence (1) shall rest on the top edge of the lath.

(3) The outer course of the application referred to in Sentence (1) shall be fastened to the lath with nails of sufficient length to penetrate through the lath.

(4) The butts of the shingles or shakes shall be so located that they project not less than 12 mm below the bottom edge of the lath referred to in Sentence (1).

(5) If wood lath is not used, the butts of the under-course shingles or shakes of the application referred to in Sentence (1) shall be located 12 mm above the butts of the outer course.

Text · e-Laws consolidated snapshot

9.27.7.6. — Exposure and Thickness

(1) The exposure and butt thickness of shingles and shakes shall conform to Table 9.27.7.6.

Text · e-Laws consolidated snapshot

Table 9.27.7.6. Exposure and Thickness of Wood Shingles and Shakes Forming Part of Sentence 9.27.7.6.(1)

Column 1

Column 2

Column 3

Column 4

Shake or Shingle Length, mm

Maximum Exposure, mm

Minimum Butt Thickness, mm

Single Coursing

Double Coursing

400

190

305

10

450

216

356

11

600

292

406

13

9.27.8. — Asbestos-Cement Shingles and Sheets

Content not available for this version.

9.27.8.1. — Material Standards

(1) Asbestos-cement shingles and sheets shall conform to,

(a) CAN/CGSB-34.4-M, “Siding, Asbestos-Cement, Shingles and Clapboards”,

(b) CAN/CGSB-34.5-M, “Sheets, Asbestos-Cement, Corrugated”,

(c) CAN/CGSB-34.14-M, “Sheets, Asbestos-Cement, Decorative”,

(d) CAN/CGSB-34.16, “Sheets, Asbestos-Cement, Flat, Fully Compressed”,

(e) CAN/CGSB-34.17-M, “Sheets, Asbestos-Cement, Flat, Semicompressed”, or

(f) CAN/CGSB-34.21-M, “Panels, Sandwich Asbestos-Cement with Insulating Cores”.

Text · e-Laws consolidated snapshot

9.27.8.2. — Weight and Thickness

(1) Asbestos-cement shingles shall weigh not less than 8.06 kg/m².

(2) Asbestos-cement sheet shall be not less than,

(a) 4.75 mm thick where applied to studs spaced not more than 400 mm o.c., and,

(b) 6 mm thick where applied to studs spaced not more than 600 mm o.c.

(3) Where applied over sheathing, the thickness of asbestos-cement sheet shall be not less than 3.15 mm.

Text · e-Laws consolidated snapshot

9.27.8.3. — Fastening of Shingles

(1) Asbestos-cement shingles shall be fastened with nails located not less than 25 mm above the exposure line.

Text · e-Laws consolidated snapshot

9.27.8.4. — Joints of Shingles

(1) Asbestos-cement shingles shall be installed so that vertical joints in succeeding courses are staggered.

(2) Asphalt-coated backer strips shall be installed behind each vertical joint.

(3) Shingles referred to in Sentence (1) shall have not less than a 25 mm head lap.

Text · e-Laws consolidated snapshot

9.27.8.5. — Joints in Panels

(1) Vertical joints of asbestos-cement panels shall be protected with batten strips, caulking or other suitable method.

(2) Horizontal joints of asbestos-cement panels shall be lapped, flashed, caulked or otherwise suitably protected.

Text · e-Laws consolidated snapshot

9.27.9. — Plywood

Content not available for this version.

9.27.9.1. — Material Standards

(1) Plywood cladding shall be exterior type conforming to,

(a) CSA O115-M, “Hardwood and Decorative Plywood”,

(b) CSA O121-M, “Douglas Fir Plywood”,

(c) CSA O151, “Canadian Softwood Plywood”, or

(d) CSA O153-M, “Poplar Plywood”.

Text · e-Laws consolidated snapshot

9.27.9.2. — Thickness

(1) Plywood cladding shall be not less than 6 mm thick when applied directly to sheathing.

(2) When applied directly to framing or over furring strips, plywood cladding thickness shall conform to Table 9.27.9.2.

(3) The thickness of grooved or textured plywood shall be measured at the point of least thickness.

Text · e-Laws consolidated snapshot

Table 9.27.9.2. Minimum Plywood Cladding Thickness Forming Part of Sentence 9.27.9.2.(2)

Column 1

Column 2

Column 3

Spacing of Supports, mm

Minimum Thickness, mm, where Face Grain Parallel to Supports

Minimum Thickness, mm, where Face Grain at Right Angles to Supports

400

8

6

600

11

8

9.27.9.3. — Edge Treatment

(1) The edges of plywood cladding shall be treated with a suitable paint or sealer.

Text · e-Laws consolidated snapshot

9.27.9.4. — Panel Cladding

(1) Plywood applied in panels shall have all edges supported.

(2) Not less than a 2 mm gap shall be provided between panels referred to in Sentence (1).

(3) Vertical joints in cladding referred to in Sentence (1) shall be protected with batten strips or caulking when the plywood joints are not matched.

(4) Horizontal joints in cladding referred to in Sentence (1) shall be lapped not less than 25 mm or shall be suitably flashed.

Text · e-Laws consolidated snapshot

9.27.9.5. — Lapped Strip Siding

(1) Plywood applied in horizontal lapped strips shall have not less than a 2 mm gap provided at the butted ends, which shall be caulked.

(2) The horizontal joints of siding described in Sentence (1) shall be lapped not less than 25 mm.

(3) Wedges shall be inserted under all vertical butt joints and at all corners when horizontal lapped plywood is applied without sheathing.

Text · e-Laws consolidated snapshot

9.27.10. — Hardboard

Content not available for this version.

9.27.10.1. — Material Standards

(1) Factory-finished hardboard cladding shall conform to CAN/CGSB-11.5M, “Hardboard, Precoated, Factory-Finished, for Exterior Cladding”.

(2) Hardboard cladding that is not factory finished shall conform to Types 1, 2 or 5 in CAN/CGSB-11.3-M, “Hardboard”.

Text · e-Laws consolidated snapshot

9.27.10.2. — Thickness

(1) Type 1 or 2 hardboard cladding shall be not less than,

(a) 6.0 mm thick when applied over sheathing that provides continuous support, and

(b) 7.5 mm thick when applied to furring or framing members not more than 400 mm o.c.

(2) Type 5 hardboard cladding shall be not less than 9.0 mm thick when applied over sheathing that provides continuous support or over furring or framing members spaced not more than 400 mm o.c.

(3) Where hardboard cladding is grooved, the grooves shall not extend more than 1.5 mm into the minimum required thickness.

Text · e-Laws consolidated snapshot

9.27.10.3. — Panel Cladding

(1) Hardboard cladding applied in panels shall have all edges supported with not less than a 5 mm gap provided between sheets.

(2) Vertical joints in cladding described in Sentence (1) shall be protected with batten strips or caulking when the joints are not matched.

(3) Horizontal joints in cladding described in Sentence (1) shall be lapped not less than 25 mm or shall be suitably flashed.

Text · e-Laws consolidated snapshot

9.27.10.4. — Lapped Strip Siding

(1) Hardboard applied in horizontal lapped strips shall have not less than a 5 mm gap provided at the butted ends, which shall be caulked or otherwise protected with suitable mouldings.

(2) The horizontal joints of siding described in Sentence (1) shall overlap not less than 1 mm per 16 mm width of siding board but not less than 9.5 mm for matched joint siding or 25 mm for lapped siding.

Text · e-Laws consolidated snapshot

9.27.10.5. — Clearance

(1) Not less than 3 mm clearance shall be provided between hardboard siding and door or window frames.

Text · e-Laws consolidated snapshot

9.27.11. — OSB and Waferboard

Content not available for this version.

9.27.11.1. — Material Standard

(1) OSB and waferboard cladding shall conform to CSA O437.0, “OSB and Waferboard”.

Text · e-Laws consolidated snapshot

9.27.11.2. — Thickness

(1) OSB conforming to O-2 grade shall be not less than 6.0 mm thick where applied directly to sheathing.

(2) OSB conforming to O-2 grade applied directly to framing or over furring strips, shall conform to the thickness shown for plywood in Table 9.27.9.2.

(3) OSB conforming to O-1 grade and waferboard conforming to R-1 grade shall be not less than 7.9 mm thick where applied directly to sheathing.

(4) Where applied directly to framing or over furring strips, OSB conforming to O-1 grade and waferboard conforming to R-1 grade shall be not less than,

(a) 9.5 mm thick on supports spaced not more than 400 mm o.c., and

(b) 12.7 mm thick on supports spaced not more than 600 mm o.c.

Text · e-Laws consolidated snapshot

9.27.11.3. — Panel Cladding

(1) OSB and waferboard applied in panels shall have all edges supported and treated with a primer or sealer.

(2) Not less than a 3 mm gap shall be provided between sheets in cladding described in Sentence (1).

(3) Vertical joints in cladding described in Sentence (1) shall be protected with batten strips or caulking when the OSB and waferboard joints are not matched.

(4) Horizontal joints in cladding described in Sentence (1) shall be lapped not less than 25 mm or shall be suitably flashed.

Text · e-Laws consolidated snapshot

9.27.11.4. — Clearance

(1) At least a 3 mm clearance shall be provided between OSB and waferboard cladding and door or window frames.

Text · e-Laws consolidated snapshot

9.27.12. — Metal

Content not available for this version.

9.27.12.1. — Material Standards

(1) Horizontal and vertical strip steel siding, including flashing and trim accessories, shall conform to CAN/CGSB-93.4, “Galvanized Steel and Aluminum-Zinc Alloy Coated Steel Siding, Soffits and Fascia, Prefinished, Residential”.

(2) Steel sheet cladding shall have a minimum thickness of 0.3 mm and conform to CAN/CGSB-93.3-M, “Prefinished Galvanized and Aluminum-Zinc Alloy Steel Sheet for Residential Use”.

(3) Horizontal and vertical strip aluminum siding, including flashing and trim accessories, shall conform to CAN/CGSB-93.2-M, “Prefinished Aluminum Siding, Soffits and Fascia, for Residential Use”.

(4) Aluminum sheet cladding shall conform to CAN/CGSB-93.1-M, “Sheet, Aluminum Alloy, Prefinished, Residential” and shall have a thickness of not less than 0.58 mm, except that siding supported by backing or sheathing shall have a thickness of not less than 0.46 mm.

Text · e-Laws consolidated snapshot

9.27.13. — Vinyl Siding

Content not available for this version.

9.27.13.1. — Material Standard

(1) Vinyl siding, including flashing and trim accessories, shall conform to CAN/CGSB-41.24, “Rigid Vinyl Siding, Soffits and Fascia”.

Text · e-Laws consolidated snapshot

9.27.13.2. — Attachment

(1) The attachment of vinyl siding shall conform to the requirements in Subsection 9.27.5. for metal siding.

Text · e-Laws consolidated snapshot

9.28. — Stucco

Content not available for this version.

9.28.1. — General

Content not available for this version.

9.28.1.1. — Sheathing Beneath Stucco

(1) Sheathing shall be provided beneath stucco applied over wood-frame walls except as permitted in Article 9.28.4.2.

(2) Where applied beneath stucco, sheathing shall conform to Subsection 9.23.16.

Text · e-Laws consolidated snapshot

9.28.1.2. — Lath and Reinforcing

(1) Stucco lath or reinforcing shall be used to attach stucco to any substrate other than masonry.

(2) Stucco lath or reinforcing shall be used to attach stucco to masonry where,

(a) the masonry is soft-burned tile or brick of less strength than the stucco, or

(b) the masonry surface is not sound, clean and sufficiently rough to provide a good key.

(3) Stucco applied over masonry chimneys shall be reinforced.

Text · e-Laws consolidated snapshot

9.28.1.3. — Concrete Masonry Units

(1) Stucco finish shall not be applied over concrete masonry units less than one month old unless the units have been cured by the autoclave process.

Text · e-Laws consolidated snapshot

9.28.1.4. — Clearance over Ground Level

(1) Stucco shall be not less than 200 mm above finished ground level except when it is applied over concrete or masonry.

Text · e-Laws consolidated snapshot

9.28.1.5. — Flashing and Caulking

(1) Flashing and caulking used with stucco shall conform to Subsections 9.27.3. and 9.27.4., except that if aluminum flashing is used, it shall be separated from the stucco by an impervious membrane or coating.

Text · e-Laws consolidated snapshot

9.28.2. — Stucco Materials

Content not available for this version.

9.28.2.1. — Portland Cement

(1) Portland cement shall conform to CAN/CSA-A3001, “Cementitious Materials for Use in Concrete”.

Text · e-Laws consolidated snapshot

9.28.2.2. — Aggregate

(1) Aggregate shall be clean, well-graded natural sand or sand manufactured from crushed stone, gravel or air-cooled blast furnace slag and shall contain no significant amounts of deleterious material.

(2) Aggregate grading shall conform to Table 9.28.2.2.

Text · e-Laws consolidated snapshot

Table 9.28.2.2. Aggregate Grading for Stucco Forming Part of Sentence 9.28.2.2.(2)

Column 1

Column 2

Column 3

Sieve Sizes, mm

% Aggregate Passing Sieve

Maximum

Minimum

4

100

2

90

1

90

60

0.5

60

45

0.25

30

10

0.125

5

9.28.2.3. — Water

(1) Water shall be clean and free of significant amounts of deleterious material.

Text · e-Laws consolidated snapshot

9.28.3. — Fasteners

Content not available for this version.

9.28.3.1. — Materials

(1) Fasteners for stucco lath or reinforcing shall be corrosion-resistant and of a material other than aluminum.

Text · e-Laws consolidated snapshot

9.28.3.2. — Nails and Staples

(1) Nails for stucco lath or reinforcing shall be not less than 3.2 mm diam with a head diameter of not less than 11.1 mm.

(2) Staples for stucco lath reinforcing shall be not less than 1.98 mm diam or thickness.

(3) Staples and nails for attaching stucco lath or reinforcing to vertical surfaces shall be of sufficient length to penetrate 25 mm into framing members or to the full depth of the sheathing where the sheathing is used for attachment.

(4) On horizontal surfaces nails for stucco lath or reinforcing shall be not less than 38 mm long.

Text · e-Laws consolidated snapshot

9.28.4. — Stucco Lath

Content not available for this version.

9.28.4.1. — Materials

(1) Rib lath or expanded metal stucco mesh shall be,

(a) copper-alloy steel coated with rust-inhibitive paint after fabrication, or

(b) galvanized.

(2) Woven or welded wire mesh shall be galvanized.

Text · e-Laws consolidated snapshot

9.28.4.2. — No Sheathing Required

(1) Sheathing need not be provided beneath stucco where not less than 1.19 mm diam galvanized wire is applied horizontally to the framing at vertical intervals not exceeding 150 mm, or where paper-backed welded wire metal lath is used.

Text · e-Laws consolidated snapshot

9.28.4.3. — Stucco Lath Specifications

(1) Stucco lath shall conform to Table 9.28.4.3.

Text · e-Laws consolidated snapshot

Table 9.28.4.3. Stucco Lath Forming Part of Sentence 9.28.4.3.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Location

Type of Lath

Minimum Diam. of Wire, mm

Maximum Mesh Opening

Minimum Mass, kg/m2

Vertical surfaces

Welded or woven wire

1.15

25 mm

1.30

38 mm

1.50

51 mm

Stucco mesh reinforcing (expanded metal)

25.8 cm2

0.98

Horizontal surfaces

9.5 mm rib lath

1.84

Cedar lath

9.28.4.4. — Self-Furring Devices

(1) Stucco lath shall be held not less than 6 mm away from the backing by means of suitable self-furring devices.

Text · e-Laws consolidated snapshot

9.28.4.5. — Application of Stucco Lath

(1) Stucco lath shall be applied with the long dimension horizontal.

(2) Horizontal and vertical joints in stucco lath shall be lapped not less than 50 mm.

(3) End joints of stucco lath shall be staggered and shall occur over framing members.

(4) External corners of stucco lath shall be reinforced with a vertical strip of lath or reinforcing extending not less than 150 mm on both sides of the corner, or the lath or reinforcing shall extend around corners not less than 150 mm.

Text · e-Laws consolidated snapshot

9.28.4.6. — Fastening

(1) Stucco lath shall be fastened in conformance with Subsection 9.27.5.

(2) Fasteners on vertical surfaces shall be spaced not more than,

(a) 150 mm o.c. vertically and 400 mm o.c. horizontally, or

(b) 100 mm o.c. vertically and 600 mm o.c. horizontally.

(3) Nailing patterns other than those required in Sentence (2) are permitted to be used provided there are not fewer than 20 fasteners per square metre of wall surface.

(4) Fasteners on horizontal surfaces shall be spaced not more than,

(a) 150 mm o.c. along the framing members when members are spaced not more than 400 mm o.c., and

(b) 100 mm o.c. along members when members are spaced not more than 600 mm o.c.

Text · e-Laws consolidated snapshot

9.28.5. — Stucco Mixes

Content not available for this version.

9.28.5.1. — Mixes

(1) Stucco mixes shall conform to Table 9.28.5.1.

Text · e-Laws consolidated snapshot

Table 9.28.5.1. Stucco Mixes Forming Part of Sentence 9.28.5.1.(1)

Column 1

Column 2

Column 3

Column 4

Materials, volume

Portland Cement

Masonry Cement

Lime

Aggregate

1

0.25 to 1

3.25 to 4 parts per part of cementitious material

1

1

9.28.5.2. — Pigments

(1) Pigment if used shall consist of pure mineral oxides inert to the action of sun, lime and cement.

(2) Pigment shall not exceed 6% of the portland cement by weight.

Text · e-Laws consolidated snapshot

9.28.5.3. — Mixing

(1) Materials shall be thoroughly mixed before and after water is added.

(2) Stucco shall be applied not later than 3 h after the initial mixing.

Text · e-Laws consolidated snapshot

9.28.6. — Stucco Application

Content not available for this version.

9.28.6.1. — Low Temperature Conditions

(1) The base for stucco shall be maintained above freezing.

(2) Stucco shall be maintained at a temperature of not less than 10°C during application and for not less than 48 h afterwards.

Text · e-Laws consolidated snapshot

9.28.6.2. — Number of Coats and Total Thickness

(1) Stucco shall be applied with at least 2 base coats and one finish coat, providing a total thickness of not less than 15 mm, measured from the face of the lath or face of the masonry where no lath is used.

Text · e-Laws consolidated snapshot

9.28.6.3. — First Coat

(1) The first coat shall be not less than 6 mm thick, measured from the face of the lath or masonry, fully embedding the lath.

(2) The surface of the first coat shall be scored to provide a key with the second coat.

Text · e-Laws consolidated snapshot

9.28.6.4. — Second Coat

(1) The second coat shall be not less than 6 mm thick.

(2) The surface of the second shall be lightly roughened to provide a key with the finish coat if the finish coat is other than stone dash.

Text · e-Laws consolidated snapshot

9.28.6.5. — Finish Coat

(1) When the finish coat is other than stone dash, the base shall be dampened but not saturated before the finish coat is applied.

(2) The thickness of the finish coat shall be not less than 3 mm.

(3) When a stone dash finish is used, the stone shall be partially embedded in the second coat before the second coat starts to set or stiffen.

Text · e-Laws consolidated snapshot

9.29. — Interior Wall and Ceiling Finishes

Content not available for this version.

9.29.1. — General

Content not available for this version.

9.29.1.1. — Fire Protection and Sound Control

(1) A wall or ceiling finish shall also conform to the appropriate requirements in Sections 9.10. and 9.11. in addition to the requirements in this Section.

Text · e-Laws consolidated snapshot

9.29.2. — Waterproof Wall Finish

Content not available for this version.

9.29.2.1. — Where Required

(1) Waterproof finish shall be provided to a height of not less than,

(a) 1 800 mm above the floor in shower stalls,

(b) 1 200 mm above the rims of bathtubs equipped with showers, and

(c) 400 mm above the rims of bathtubs not equipped with showers.

Text · e-Laws consolidated snapshot

9.29.2.2. — Materials

(1) Waterproof finish shall consist of ceramic, plastic or metal tile, sheet vinyl, tempered hardboard, laminated thermosetting decorative sheets or linoleum.

Text · e-Laws consolidated snapshot

9.29.3. — Wood Furring

Content not available for this version.

9.29.3.1. — Size and Spacing of Furring

(1) Wood furring for the attachment of wall and ceiling finishes shall conform to Table 9.29.3.1.

Text · e-Laws consolidated snapshot

Table 9.29.3.1. Size and Spacing of Furring Forming Part of Sentence 9.29.3.1.(1)

Column 1

Column 2

Column 3

Column 4

Maximum Spacing of Furring, mm

Minimum Size of Furring, mm

Maximum Spacing of Furring Supports

Continuous Supports

400 mm (o.c.)

600 mm (o.c.)

300

19 × 38

19 × 38

19 × 64

400

19 × 38

19 × 38

19 × 64

600

19 × 38

19 × 64

19 × 89

9.29.3.2. — Fastening

(1) Furring shall be fastened to the framing or to wood blocks with not less than 51 mm nails.

Text · e-Laws consolidated snapshot

9.29.4. — Plastering

Content not available for this version.

9.29.4.1. — Application

(1) Application of plaster wall and ceiling finishes including installation of metal or gypsum lath, shall conform to CSA A82.30-M, “Interior Furring, Lathing and Gypsum Plastering”.

Text · e-Laws consolidated snapshot

9.29.5. — Gypsum Board Finish (Taped Joints)

Content not available for this version.

9.29.5.1. — Application

(1) The requirements for application of gypsum board in this Subsection apply to the single layer application of gypsum board to wood furring or framing using nails or screws.

(2) Gypsum board applications not described in this Subsection shall conform to CSA A82.31-M, “Gypsum Board Application”.

Text · e-Laws consolidated snapshot

9.29.5.2. — Materials

(1) Gypsum products shall conform to,

(a) CAN/CSA-A82.27-M, “Gypsum Board”,

(b) ASTM C36 / C36M, “Gypsum Wallboard”,

(c) ASTM C37 / C37M, “Gypsum Lath”,

(d) ASTM C442 / C442M, “Gypsum Backing Board, and Gypsum Coreboard, and Gypsum Shaftliner Board”,

(e) ASTM C558 / C588M, “Gypsum Base for Veneer Plaster”,

(f) ASTM C630 / C630M, “Water-Resistant Gypsum Backing Board”,

(g) ASTM C931 / C931M, “Exterior Gypsum Soffit Board”,

(h) ASTM C960 / C960M, “Predecorated Gypsum Board”,

(i) ASTM C1178 / C1178M, “Glass Mat Water-Resistant Gypsum Backing Panel”,

(j) ASTM C1395 / C1395M, “Gypsum Ceiling Board”, or

(k) ASTM C1396 / C1396M, “Gypsum Board”.

Text · e-Laws consolidated snapshot

9.29.5.3. — Maximum Spacing of Supports

(1) Maximum spacing of supports for gypsum board applied as a single layer shall conform to Table 9.29.5.3.

Text · e-Laws consolidated snapshot

Table 9.29.5.3. Spacing of Supports for Gypsum Board Forming Part of Sentence 9.29.5.3.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Thickness, mm

Orientation of Board to Framing

Maximum Spacing of Supports, mm o.c.

Walls

Ceilings

Painted Finish

Water-Based Texture Finish

Gypsum board conforming to Clauses 9.29.5.2.(1)(a)v1v2 to (i) and (k)

9.5

parallel

perpendicular

400

400

12.7

parallel

600

400

perpendicular

600

600

400

15.9

parallel

600

400

perpendicular

600

600

600

Gypsum board conforming to Clause 9.29.5.2.(1)(j)v1v2

12.7

parallel

600

400

perpendicular

600

600

600

9.29.5.4. — Support of Insulation

(1) Gypsum board supporting insulation shall be at least 12.7 mm thick.

Text · e-Laws consolidated snapshot

9.29.5.5. — Length of Fasteners

(1) The length of fasteners for gypsum board shall conform to Table 9.29.5.5., except that lesser depths of penetration are permitted for assemblies required to have a fire-resistance rating provided it can be shown, on the basis of fire tests, that such depths are adequate for the required rating.

Text · e-Laws consolidated snapshot

Table 9.29.5.5. Fastener Penetration into Wood Supports Forming Part of Sentence 9.29.5.5.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Required Fire-Resistance Rating of Assembly

Minimum Penetration, mm

Walls

Ceilings

Nails

Screws

Nails

Screws

Not required

20

15

20

15

45 min

20

20

30

30

1 h

20

20

45

45

1.5 h

20

20

60

60

9.29.5.6. — Nails

(1) Nails for fastening gypsum board to wood supports shall conform to CSA B111, “Wire Nails, Spikes and Staples”.

Text · e-Laws consolidated snapshot

9.29.5.7. — Screws

(1) Screws for fastening gypsum board to wood supports shall conform to ASTM C1002, “Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs”.

Text · e-Laws consolidated snapshot

9.29.5.8. — Spacing of Nails

(1) For single-layer application on ceilings, nails shall be spaced,

(a) not more than 180 mm o.c. on ceiling supports, or

(b) every 300 mm o.c. along ceiling supports, in pairs about 50 mm apart.

(2) Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent to nailing at this location.

(3) Except as required by Sentence (4), for single-layer application on walls, nails shall be spaced,

(a) not more than 200 mm o.c. on vertical wall supports, or

(b) every 300 mm o.c. along vertical wall supports, in pairs about 50 mm apart.

(4) For single-layer application on walls, where gypsum board is required to provide bracing, lateral support or fire protection, nails shall be spaced not more than 200 mm o.c. on,

(a) vertical wall supports, and

(b) top and bottom plates.

(5) The uppermost nails on vertical wall supports shall be not more than 200 mm below the ceiling.

(6) Nails shall be located not less than 10 mm from the side or edge of the board.

(7) Nails shall be driven so that the heads do not puncture the paper.

Text · e-Laws consolidated snapshot

9.29.5.9. — Spacing of Screws

(1) For single-layer application on a ceiling, screws shall be spaced not more than 300 mm o.c. on ceiling supports.

(2) Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent to screwing at this location.

(3) Except as required by Sentence (4), for single-layer application on walls, screws shall be spaced,

(a) not more than 300 mm o.c. on vertical wall supports where the supports are more than 400 mm o.c., or

(b) not more than 400 mm o.c. on vertical wall supports where the supports are not more than 400 mm o.c.

(4) Except as required by Sentence (5), for single-layer application on walls, where gypsum board is required to provide bracing, lateral support or fire protection, screws shall be spaced not more than 300 mm o.c. on,

(a) vertical wall supports, and

(b) top and bottom plates.

(5) Where a fire-resistance rating is determined based on Supplementary Standard SB-3, Sentence (4) need not apply for the purpose of fire protection.

(6) Screws shall be located not less than 10 mm from the side or edge of the board.

(7) Screws shall be driven so that the heads do not puncture the paper.

Text · e-Laws consolidated snapshot

9.29.5.10. — Low Temperature Conditions

(1) In cold weather, heat shall be provided to maintain a temperature of not below 10°C for 48 h prior to taping and finishing and maintained for not less than 48 h after that.

Text · e-Laws consolidated snapshot

9.29.6. — Plywood Finish

Content not available for this version.

9.29.6.1. — Thickness

(1) Except as provided in Sentences (2) and (3), the minimum thickness of plywood interior finish shall conform to Table 9.29.6.1.

(2) A manufacturing tolerance of – 0.4 mm may be applied to the thicknesses listed in Table 9.29.6.1.

(3) No minimum thickness is required where plywood is applied over continuous backing.

Editor's note

In the notes to Table-9.29.6.1., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.29.6.1. Thickness of Plywood Interior Finish Forming Part of Articles 9.29.6.1., 9.29.6.2. and 9.29.9.2.

Column 1

Column 2

Column 3

Maximum Spacing of Supports, mm o.c.

Minimum Thickness, mm(1), on Supports with no Horizontal Blocking

Minimum Thickness, mm(1), on Supports with Blocking at Vertical Intervals not Exceeding 1.2 m

400

4.7

4.0

600

8.0

4.7

Notes to Table 9.29.6.1.

(1)Thickness limits shall apply to the net effective thickness (NET) of grooved, striated, textured and/or embossed panels and to the actual thickness of flat panels.

9.29.6.2. — Grooved Plywood

(1) Except as permitted in Sentence (2), where plywood for interior finish is grooved, the grooves shall not extend through the face ply and into the plies below the face ply unless the groove is supported by framing or furring.

(2) If the grain of the face ply is at right angles to the supporting members, the groove is permitted to extend into the plies below the face ply provided the thickness of the plywood exceeds the value shown in Table 9.29.6.1. by an amount equal to not less than the depth of penetration of the grooves into the plies below the face ply.

Text · e-Laws consolidated snapshot

9.29.6.3. — Nails and Staples

(1) Nails for attaching plywood finishes shall not be less than 38 mm casing or finishing nails spaced not more than 150 mm o.c. along edge supports and 300 mm o.c. along intermediate supports, except that staples providing equivalent lateral resistance may also be used.

Text · e-Laws consolidated snapshot

9.29.6.4. — Edge Support

(1) All plywood edges shall be supported by furring, blocking or framing.

Text · e-Laws consolidated snapshot

9.29.7. — Hardboard Finish

Content not available for this version.

9.29.7.1. — Material Standard

(1) Hardboard shall conform to CAN/CGSB-11.3-M, “Hardboard”.

Text · e-Laws consolidated snapshot

9.29.7.2. — Thickness

(1) Hardboard shall be not less than,

(a) 3 mm thick where applied over continuous back-up,

(b) 6 mm thick where applied to supports spaced not more than 400 mm o.c., and

(c) 9 mm thick where applied to supports spaced not more than 600 mm o.c.

Text · e-Laws consolidated snapshot

9.29.7.3. — Nails

(1) Nails for fastening hardboard shall be casing or finishing nails not less than 38 mm long, spaced not more than 150 mm o.c. along edge supports and 300 mm o.c. along intermediate supports.

Text · e-Laws consolidated snapshot

9.29.7.4. — Edge Support

(1) All hardboard edges shall be supported by furring, blocking or framing where the back-up is not continuous.

Text · e-Laws consolidated snapshot

9.29.8. — Insulating Fibreboard Finish

Content not available for this version.

9.29.8.1. — Material Standard

(1) Insulating fibreboard shall conform to CAN/ULC-S706, “Wood Fibre Thermal Insulation for Buildings”.

Text · e-Laws consolidated snapshot

9.29.8.2. — Thickness

(1) Insulating fibreboard sheets shall be not less than 11.1 mm thick on supports not more than 400 mm o.c.

(2) Insulating fibreboard tile shall be not less than 12.7 mm thick on supports spaced not more than 400 mm o.c.

Text · e-Laws consolidated snapshot

9.29.8.3. — Nails

(1) Nails for fastening fibreboard sheets shall be not less than 2.6 mm shank diameter casing or finishing nails of sufficient length to penetrate not less than 20 mm into the supports.

(2) Nails shall be spaced not more than 100 mm o.c. along edge supports and 200 mm o.c. along intermediate supports.

Text · e-Laws consolidated snapshot

9.29.8.4. — Edge Support

(1) All fibreboard edges shall be supported by blocking, furring or framing.

Text · e-Laws consolidated snapshot

9.29.9. — Particleboard, OSB or Waferboard Finish

Content not available for this version.

9.29.9.1. — Material Standard

(1) Particleboard finish shall conform to ANSI A208.1, “Particleboard, Mat-Formed Wood”.

(2) OSB or waferboard finish shall conform to,

(a) CAN/CSA-O.325, “Construction Sheathing”, or

(b) CSA O437.0, “OSB and Waferboard”.

Text · e-Laws consolidated snapshot

9.29.9.2. — Minimum Thickness

(1) Except as provided in Sentences (2) and (3), the minimum thickness of O-2 grade OSB used as an interior finish shall conform to that shown for plywood in Table 9.29.6.1.

(2) Thickness listed in Table 9.29.6.1. shall permit a manufacturing tolerance of – 0.4 mm.

(3) No minimum thickness is required where O-2 grade OSB is applied over continuous backing.

(4) OSB conforming to O-1 grade, waferboard conforming to R-1 grade and particleboard shall be,

(a) not less than 6.35 mm thick on supports not more than 400 mm o.c.,

(b) not less than 9.5 mm thick on supports not more than 600 mm o.c., and

(c) not less than 6.35 mm thick on supports not more than 600 mm o.c. in walls where blocking is provided at midwall height.

(5) OSB conforming to CAN/CSA-O325.0, “Construction Sheathing”, shall meet the minimum panel mark of,

(a) W16, on supports not more than 400 mm o.c.,

(b) W24, on supports not more than 600 mm o.c., and

(c) W16, on supports not more than 600 mm o.c. where blocking is provided at midwall height.

Text · e-Laws consolidated snapshot

9.29.9.3. — Nails

(1) Nails for fastening particleboard, OSB or waferboard shall be not less than 38 mm casing or finishing nails spaced not more than 150 mm o.c. along edge supports and 300 mm o.c. along intermediate supports.

Text · e-Laws consolidated snapshot

9.29.9.4. — Edge Support

(1) All particleboard, OSB or waferboard edges shall be supported by furring, blocking or framing.

Text · e-Laws consolidated snapshot

9.29.10. — Wall Tile Finish

Content not available for this version.

9.29.10.1. — Tile Application

(1) Ceramic tile shall be set in a mortar base or applied with an adhesive.

(2) Plastic tile shall be applied with an adhesive.

Text · e-Laws consolidated snapshot

9.29.10.2. — Mortar Base

(1) When ceramic tile is applied to a mortar base the cementitious material shall consist of 1 part Portland cement to not more than one-quarter part lime by volume.

(2) The cementitious material described in Sentence (1) shall be mixed with no fewer than 3 nor more than 5 parts of aggregate per part of cementitious material by volume.

(3) Mortar shall be applied over metal lath or masonry.

(4) Ceramic tile applied to a mortar base shall be thoroughly soaked and pressed into place forcing the mortar into the joints while the tile is wet.

Text · e-Laws consolidated snapshot

9.29.10.3. — Adhesives

(1) Adhesives to attach ceramic and plastic tile shall be applied to the finish coat or brown coat of plaster that has been steel-trowelled to an even surface or to gypsum board or to masonry provided the masonry has an even surface.

Text · e-Laws consolidated snapshot

9.29.10.4. — Moisture Resistant Backing

(1) Ceramic and plastic tile installed on walls around bathtubs or showers shall be applied over moisture resistant backing.

Text · e-Laws consolidated snapshot

9.29.10.5. — Joints between Tiles and Bathtub

(1) The joints between wall tiles and a bathtub or shower shall be suitably caulked with material conforming to CAN/CGSB-19.22-M, “Mildew Resistant Sealing Compound for Tubs and Tile”.

Text · e-Laws consolidated snapshot

9.30. — Flooring

Content not available for this version.

9.30.1. — General

Content not available for this version.

9.30.1.1. — Required Finish Flooring

(1) Finished flooring shall be provided in all residential occupancies.

Text · e-Laws consolidated snapshot

9.30.1.2. — Water Resistance

(1) Finished flooring in bathrooms, kitchens, public entrance halls, laundry and general storage areas shall consist of resilient flooring, felted-synthetic-fibre floor coverings, concrete, terrazzo, ceramic tile, mastic or other types of flooring providing similar degrees of water resistance.

Text · e-Laws consolidated snapshot

9.30.1.3. — Sleepers

(1) Wood sleepers supporting finished flooring over a concrete base supported on the ground shall be not less than 19 mm by 38 mm and shall be treated with a wood preservative.

Text · e-Laws consolidated snapshot

9.30.1.4. — Finish Quality

(1) Finished flooring shall have a surface that is smooth, even and free from roughness or open defects.

Text · e-Laws consolidated snapshot

9.30.2. — Panel-Type Underlay

Content not available for this version.

9.30.2.1. — Required Underlay

(1) A panel-type underlay shall be provided under resilient flooring, parquet flooring, ceramic tile, felted-synthetic-fibre floor coverings or carpeting laid over lumber subflooring.

(2) A panel-type underlay shall be provided under resilient flooring, parquet flooring, felted-synthetic-fibre floor coverings or carpeting on panel-type subflooring whose edges are unsupported.

(3) Panel-type underlay shall be provided under ceramic tile applied with adhesive.

(4) Panel-type underlay shall be provided under resilient flooring on waferboard or strandboard subflooring.

Text · e-Laws consolidated snapshot

9.30.2.2. — Materials and Thickness

(1) Panel-type underlay shall be not less than 6 mm thick and shall conform to,

(a) ANSI A208.1, “Particleboard, Mat-Formed Wood”,

(b) CAN/CGSB-11.3-M, “Hardboard”,

(c) CSA O115-M, “Hardwood and Decorative Plywood”,

(d) CSA O121-M, “Douglas Fir Plywood”,

(e) CSA O151, “Canadian Softwood Plywood”,

(f) CSA O153-M, “Poplar Plywood”, or

(g) CSA O437.0, “OSB and Waferboard”.

Text · e-Laws consolidated snapshot

9.30.2.3. — Fastening

(1) Panel-type underlay shall be fastened to the subfloor with staples, annular grooved flooring nails or spiral nails, spaced not more than 150 mm o.c. along the edges and 200 mm o.c. both ways at other locations.

(2) Nails for panel-type underlay shall be not less than 19 mm long for 6 mm thick underlay and 22 mm long for 7.9 mm thick underlay.

(3) Staples for panel-type underlay shall,

(a) have not less than a 1.2 mm shank diameter or thickness with a 4.7 mm crown, and

(b) be not less than,

(i) 22 mm long for 6 mm underlay, and

(ii) 28 mm long for 7.9 mm and 9.5 mm underlay.

Text · e-Laws consolidated snapshot

9.30.2.4. — Joints Offset

(1) Where panel-type underlay is required to be installed over plywood, or OSB or waferboard, the joints in the underlay shall be offset at least 200 mm from the joints in the underlying subfloor.

Text · e-Laws consolidated snapshot

9.30.2.5. — Surface Defects

(1) Underlay beneath resilient or ceramic floors applied with an adhesive shall have all holes or open defects on the surface patched so that the defects will not be transmitted to the finished surface.

Text · e-Laws consolidated snapshot

9.30.3. — Wood Strip Flooring

Content not available for this version.

9.30.3.1. — Thickness

(1) The thickness of wood strip flooring shall conform to Table 9.30.3.1.

Text · e-Laws consolidated snapshot

Table 9.30.3.1. Thickness of Wood Strip Flooring Forming Part of Sentence 9.30.3.1.(1)

Column 1

Column 2

Column 3

Column 4

Type of Flooring

Maximum Joist Spacing, mm

Minimum Thickness of Flooring, mm

With Subfloor

No Subfloor

Matched hardwood (interior use only)

400

7.9

19.0

600

7.9

33.3

Matched softwood (interior or exterior use)

400

19.0

19.0

600

19.0

31.7

Square edge softwood (exterior use only)

400

25.4

600

38.1

9.30.3.2. — Strip Direction and End Joints

(1) Wood strip flooring shall not be laid parallel to lumber subflooring unless a separate underlay is provided.

(2) If wood strip flooring is applied without a subfloor, it shall be laid at right angles to the joists so that the end joints are staggered and occur over supports or are end matched.

(3) If the flooring is end matched, it shall be laid so that no 2 adjoining strips break joints in the same space between supports and each strip bears on no fewer than 2 supports.

Text · e-Laws consolidated snapshot

9.30.3.3. — Nailing

(1) When nails are used, wood strip flooring shall be toe nailed or face nailed with at least 1 nail per strip at the spacings shown in Table 9.30.3.3., except that face nailed strips of more than 25 mm in width shall have at least 2 nails per strip.

(2) Face nails shall be countersunk.

Editor's note

In the notes to Table-9.30.3.3., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.30.3.3. Nailing of Wood Strip Flooring Forming Part of Sentence 9.30.3.3.(1)

Column 1

Column 2

Column 3

Finish Floor Thickness, Mm

Minimum Length of Flooring Nails, mm

Maximum Spacing of Flooring Nails, mm

7.9

38(1)

200

11.1

51

300

19.0

57

400

25.4

63

400

31.7

70

600

38.1

83

600

Notes to Table 9.30.3.3.:

(1)See Article 9.30.3.4.

9.30.3.4. — Staples

(1) Staples are permitted to be used to fasten wood strip flooring not more than 7.9 mm in thickness and not more than 50 mm in width provided the staples,

(a) are not less than 29 mm long,

(b) have a shank diameter of not less than 1.19 mm,

(c) have a crown of not less than 4.7 mm, and

(d) are spaced not more than 400 mm o.c.

(2) Staples are permitted to be used to fasten wood strip flooring not more than 19 mm in thickness and not more than 83 mm in width provided the staples,

(a) are not less than 51 mm long,

(b) have a shank diameter of not less than 1.82 mm,

(c) have a crown of not less than 12.7 mm, and

(d) are spaced not more than 400 mm o.c.

Text · e-Laws consolidated snapshot

9.30.4. — Parquet Flooring

Content not available for this version.

9.30.4.1. — Adhesive

(1) Adhesive used to attach parquet block flooring shall be suitable for bonding wood to the applicable subfloor material.

Text · e-Laws consolidated snapshot

9.30.5. — Resilient Flooring

Content not available for this version.

9.30.5.1. — Materials

(1) Resilient flooring used on concrete slabs supported on ground shall consist of asphalt, rubber, vinyl-asbestos, unbacked vinyl or vinyl with an inorganic type backing.

(2) Flooring described in Sentence (1) shall be attached to the base with a suitable waterproof and alkali-resistant adhesive.

Text · e-Laws consolidated snapshot

9.30.6. — Ceramic Tile

Content not available for this version.

9.30.6.1. — Application

(1) Ceramic tile shall be set in a mortar bed or applied to a sound smooth base with a suitable adhesive.

(2) Panel-type subfloor to which ceramic tile is to be applied with adhesive shall have its edges supported according to Article 9.23.14.3.

Text · e-Laws consolidated snapshot

9.30.6.2. — Ceramic Tile Set in Mortar Bed

(1) When ceramic tile is set in mortar bed, the bed shall be not less than 32 mm thick. A 50 mm by 50 mm galvanized wire mesh shall be placed in the mortar bed, and asphalt sheathing paper, felt or polyethylene film shall be applied under the mortar bed when the mortar is applied over wood subfloors.

(2) The mortar bed described in Sentence (1) shall consist of by volume,

(a) 1 part Portland cement,

(b) 4 parts sand, and

(c) 1 part water.

(3) The tile joints for the ceramic tile in Sentence (1) shall be grouted with cement grout which shall be compressed into joints between the tiles and then wiped smooth.

Text · e-Laws consolidated snapshot

9.30.6.3. — Reinforcement for Panel-Type Wood Sheathing

(1) Except as permitted in Article 9.30.6.4.v1, when ceramic floor tiles are set on panel-type wood sheathing, one of the following assemblies for reinforcing the floor assembly shall be used:

(a) 20 mm thick plywood or waferboard with all edges supported by at least 38 mm by 38 mm blocking with floor joists spaced not more than 400 mm o.c., with 6 mm underlay,

(b) sheathing with a thickness that conforms to Table 9.23.14.5.A. or a rating that complies to Table 9.23.14.5.B. and has an underlay consisting of 15.9 mm plywood or waferboard with offsetting joints, with a 4 mm gap between the sheets, or

(c) subfloor sheathing reinforced with close spaced 38 mm by 38 mm blocking at spacings at least half that of the floor joist spacing.

Text · e-Laws consolidated snapshot

9.30.6.4. — Ceramic Tile Applied to Mortar Bed with Adhesive

(1) When ceramic tile is applied to a mortar bed with adhesive, the bed shall be not less than 12.5 mm thick.

(2) The mortar bed described in Sentence (1) shall consist of by volume,

(a) 1 part Portland cement,

(b) 3 parts sand, and

(c) 1 part water.

(3) At least one layer of galvanized diamond mesh wire lath shall be imbedded in the mortar bed.

(4) Joints in the wire lath required by Sentence (3) shall be overlapped not less than 12 mm.

(5) The wire lath required in Sentence (3) shall be fastened to the subfloor with,

(a) lath nails not less than 38 mm length spaced not more than 150 mm o.c., or

(b) staples not less than 38 mm in length spaced not more than 150 mm o.c.

(6) Asphalt sheathing paper, felt or polyethylene film shall be applied between the mortar bed and the wood subfloor.

(7) Floor joists supporting the mortar bed described in Sentence (1) shall,

(a) be spaced not more than 400 mm o.c., and

(b) have no fewer than two rows of 38 mm × 38 mm cross bridging.

(8) The tile joints for the ceramic tile in Sentence (1) shall be grouted with cement grout which shall be compressed into joints between the tiles and then wiped smooth.

Text · e-Laws consolidated snapshot

9.31. — Plumbing Facilities

Content not available for this version.

9.31.1. — Scope

Content not available for this version.

9.31.1.1. — Application

(1) Except as provided in Sentence (2), this Section applies to plumbing facilities and plumbing systems serving dwelling units.

(2) Plumbing facilities, grab bars, floor drains and floor and wall finishes around urinals shall conform to Subsection 3.7.4. and Article 7.1.5.2. in,

(a) a recreational camp,

(b) a camp for housing of workers, or

(c) all other buildings not described in Sentence (1).

(3) Medical gas piping systems shall conform to Subsection 3.7.5.

Text · e-Laws consolidated snapshot

9.31.2. — General

Content not available for this version.

9.31.2.1. — General

(1) The construction of plumbing systems shall conform to Part 7.

Text · e-Laws consolidated snapshot

9.31.2.2. — Corrosion Protection

(1) Metal pipes in contact with cinders or other corrosive material shall be protected by a heavy coating of bitumen or other corrosion protection.

Text · e-Laws consolidated snapshot

9.31.2.3. — Grab Bars

(1) When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.

Text · e-Laws consolidated snapshot

9.31.3. — Water Supply and Distribution

Content not available for this version.

9.31.3.1. — Reserved.

Content not available for this version.

Editor's note

As filed in O. Reg. 350/06, the heading of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed heading is retained here.

9.31.3.2. — Required Connections

(1) In a dwelling unit with a water distribution system, piping for hot and cold water shall be connected to every kitchen sink, lavatory, bathtub, shower, slop sink and laundry area.

(2) Piping for cold water shall be run to every water closet.

Text · e-Laws consolidated snapshot

9.31.4. — Required Facilities

Content not available for this version.

9.31.4.1. — Required Fixtures

(1) In a dwelling unit with a water distribution system, a kitchen sink, lavatory, bathtub or shower stall and water closet shall be provided.

Text · e-Laws consolidated snapshot

9.31.4.2. — Laundry Fixtures

(1) Laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.

Text · e-Laws consolidated snapshot

9.31.4.3. — Hot Water Supply

(1) In a dwelling unit with a water distribution system, a hot water supply shall be provided.

(2) A water distribution system supplying hot water to plumbing fixtures shall conform to the requirements in Subsection 7.6.5.

Text · e-Laws consolidated snapshot

9.31.4.4. — Floor Drains

(1) A floor drain shall be installed in a basement forming part of a dwelling unit.

Text · e-Laws consolidated snapshot

9.31.5. — Reserved.

Content not available for this version.

Editor's note

As filed in O. Reg. 350/06, the heading of this subsection reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed heading is retained here.

9.31.6. — Service Water Heating Facilities

Content not available for this version.

9.31.6.1. — Hot Water Temperature

(1) Where a hot water supply is required by Article 9.31.4.3., equipment shall be installed to provide to every dwelling unit an adequate supply of service hot water with a temperature range from 45°C to 60°C.

Text · e-Laws consolidated snapshot

9.31.6.2. — Equipment and Installation

(1) Every service water heater and its installation shall conform to Part 7.

(2) Reserved.

(3) Where the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55, service water heaters shall be secured to the structure to resist overturning and displacement.

Editor's note

As filed in O. Reg. 350/06, Sentence (2) of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed text is retained here.

9.31.6.3. — Corrosion-Resistant Coating

(1) Where storage tanks for service water heaters are steel, they shall be coated with zinc, vitreous enamel (glass lined), hydraulic cement or other corrosion-resistant material.

Text · e-Laws consolidated snapshot

9.31.6.4. — Fuel-Burning Heaters

(1) Fuel-burning service water heaters shall be connected to a chimney flue conforming to Section 9.21.

Text · e-Laws consolidated snapshot

9.31.6.5. — Heating Coils

(1) Heating coils of service water heaters shall not be installed in a flue or in the combustion chamber of a boiler or furnace heating a building.

Text · e-Laws consolidated snapshot

9.32. — Ventilation

Content not available for this version.

9.32.1. — General

Content not available for this version.

9.32.1.1. — Application

(1) This Section applies to the ventilation of rooms and spaces in residential occupancies by natural ventilation and to self-contained mechanical ventilation systems serving only one dwelling unit.

(2) Mechanical ventilation systems, other than self-contained systems serving single dwelling units, shall conform to Part 6.

(3) Ventilation of rooms and spaces in other than residential occupancies shall conform to Part 6.

(4) A storage garage for more than 5 cars shall be ventilated in accordance with Part 6.

(5) A clothes dryer exhaust duct system shall conform to Part 6.

Text · e-Laws consolidated snapshot

9.32.1.2. — Mechanical Ventilation for Dwelling Units

(1) Every dwelling unit that is supplied with electrical power shall be provided with a mechanical ventilation system in accordance with Subsection 9.32.3.

Text · e-Laws consolidated snapshot

9.32.1.3. — Ventilation of Rooms and Spaces

(1) Except as permitted in Sentence (2), rooms or spaces in a dwelling unit shall be ventilated by natural means in accordance with Subsection 9.32.2.

(2) The natural ventilation of rooms or spaces required in Sentence (1) may be provided by mechanical means.

(3) Where a room or space is not provided with natural ventilation as described in Sentence (1), mechanical ventilation shall be provided to exhaust inside air from or to introduce outside air to that room or space at the rate of one-half air change per hour if the room or space is mechanically cooled in summer, and one air change per hour if it is not.

Text · e-Laws consolidated snapshot

9.32.2. — Natural Ventilation

Content not available for this version.

9.32.2.1. — Natural Ventilation Area

(1) The unobstructed openable ventilation area to the outdoors for rooms and spaces in residential buildings ventilated by natural means shall conform to Table 9.32.2.1.

(2) Where a vestibule opens directly off a living or dining room within a dwelling unit, ventilation to the outdoors for such rooms may be through the vestibule.

Text · e-Laws consolidated snapshot

Table 9.32.2.1. Natural Ventilation Forming Part of Sentence 9.32.2.1.(1)

Column 1

Column 2

Column 3

Location

Minimum Unobstructed Area

Within a dwelling unit

Bathrooms or water closet rooms

0.09 m²

Unfinished basement space

0.2 per cent of the floor area

Dining rooms, living rooms, bedrooms, kitchens, combined rooms, dens, recreation rooms and all other finished rooms

0.28 m² per room or combination of rooms

Other than within a dwelling unit

Bathrooms or water closet rooms

0.09 m² per water closet

Sleeping areas

0.14 m² per occupant

Laundry rooms, kitchens, recreation rooms

4 per cent of the floor area

Corridors, storage rooms and other similar public rooms or spaces

2 per cent of the floor area

Unfinished basement space not used on a shared basis

0.2 per cent of the floor area

9.32.2.2. — Protection from Weather and Insects

(1) Openings for natural ventilation other than windows shall be constructed to provide protection from the weather and insects.

(2) Screening shall be of rust-proof material.

Text · e-Laws consolidated snapshot

9.32.3. — Mechanical Ventilation

Content not available for this version.

9.32.3.1. — General

(1) For the purposes of this Subsection a non-solid fuel-fired appliance shall be classified as,

(a) direct vented whereby the combustion air is supplied directly from the outdoors to the combustion chamber via a sealed passageway, and the products of combustion are exhausted directly outdoors through an independent sealed vent,

(b) mechanically vented induced draft whereby combustion air is supplied from within the building envelope and the products of combustion are positively conveyed to the outdoors by means of a dedicated sealed vent, or

(c) natural draft whereby combustion air is supplied from within the building envelope and the products of combustion are conveyed to the outdoors through a chimney or Type B vent.

(2) For the purposes of this Subsection a dwelling unit shall be categorized as,

(a) Type I when,

(i) all fuel-fired combustion appliances located in the dwelling unit are direct vented or except for fireplaces, are mechanically vented induced draft, and

(ii) the dwelling unit does not contain a solid fuel-fired combustion appliance,

(b) Type II when a solid fuel-fired combustion appliance is installed in a Type I dwelling unit,

(c) Type III when a mechanically vented induced draft non-solid fuel-fired fireplace or a natural draft appliance is present, or

(d) Type IV when electric space heating is present.

Text · e-Laws consolidated snapshot

9.32.3.2. — Required Mechanical Ventilation

(1) The mechanical ventilation system required in Article 9.32.1.2. shall comply with,

(a) Part 6, or

(b) this Subsection for a mechanical ventilation system in a Type I, Type II or Type IV dwelling unit.

Text · e-Laws consolidated snapshot

9.32.3.3. — Total Ventilation Capacity

(1) The minimum total ventilation capacity of the ventilation system required in Clauses 9.32.3.2.(1)(b) shall be the sum of the individual room capacities given in Table 9.32.3.3.

Editor's note

In the notes to Table-9.32.3.3., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.32.3.3. Ventilation Capacity Forming Part of Sentence 9.32.3.3.(1)

Column 1

Column 2

Room

Capacity, L/s

Master bedroom(1)

10

Other bedrooms

5

Living room(2)

5

Dining room(2)

5

Kitchen

5

Family room(2)

5

Recreation room

5

Basement(3)

10

Other habitable rooms(4)

5

Bathroom or water closet room

5

Laundry room

5

Utility room

5

Notes to Table 9.32.3.3.:

(1)At least one bedroom in each dwelling unit shall be designated as the master bedroom.

(2)Ventilation capacities assigned to any combined living/dining or family/dining space shall be determined as if the spaces were individual rooms.

(3)Where a basement incorporates rooms of the types designated in this Table, the assigned ventilation capacities for each room shall be as specified for those types of rooms. Basement areas used for other purposes that exceed ⅔ of the total basement floor area shall be assigned a fan capacity of 10 L/s. Those that are less than ⅔ of the total floor area shall be assigned 5 L/s.

(4)Other habitable rooms shall be assigned a ventilation capacity of 5 L/s. This does not include spaces intended solely for access, egress, storage or service equipment.

9.32.3.4. — Principal Exhaust

(1) A principal exhaust fan shall be installed and shall be rated to provide not less than the capacity given in Table 9.32.3.4.A.

(2) Except as permitted in Sentence (3), the principal exhaust fan shall be controlled by a manual switch.

(3) A principal exhaust fan required under this Article may be controlled by a dehumidistat or other automatic control device where the manual switch required in Sentence (2) is capable of activating the fan regardless of the setting of the automatic control.

(4) The switches required in Sentences (2) and (3) shall be centrally located in the dwelling unit and shall be identified with the words VENTILATION FAN.

(5) The principal exhaust required in this Article may be provided by means of a heat recovery ventilator installed in accordance with Article 9.32.3.11.

(6) Where the installed capacity of the principal exhaust fan exceeds the minimum capacity required in Sentence (1) by more than 50%, the control required in Sentence (2) shall include provision to allow reduction of the flow to within ±10% of the minimum capacity specified in Sentence (1).

(7) Where an exhaust air intake for the principal exhaust fan is connected directly to the duct system of a forced air heating system or other central air circulating system, it shall,

(a) be connected to the return air side of the system, and

(b) be connected not less than 1 000 mm upstream from any outdoor air supply duct.

(8) Where an exhaust air intake for the principal exhaust fan is located in the kitchen, it shall be located in the ceiling or on the wall within 300 mm of the ceiling. 

(9) Single or multiple exhaust ducts serving the principal exhaust fan required by Sentence (1) shall be sized according to Part 6 except that they may be sized according to Table 9.32.3.4.B where

(a) the longest total duct length, from intake grille to outdoor hood, does not exceed 12 m, and

(b) the number of elbows does not exceed 4, but, in any case, they shall not be smaller than recommended by the manufacturer of the fan.

(10) In applying Table 9.32.3.4.B.,

(a) where there is more than one exhaust air inlet duct connected directly to the fan, the diameter of the inlet ducts may be decreased by 25 mm, and

(b) where the exhaust duct is connected to the duct system of a forced air heating system, the duct diameter shall be increased by 25 mm.

Editor's note

As filed in O. Reg. 350/06, Sentence (9) of Article 9.32.3.4. cites 'Table 9.32.3.4.B' without a trailing period after the table letter ('they may be sized according to Table 9.32.3.4.B where'); the current e-Laws consolidation editorially supplies the trailing period ('Table 9.32.3.4.B.'), with no amending regulation making the change. This map preserves the citation as filed.

Text · e-Laws consolidated snapshot

Table 9.32.3.4.A. Principal Exhaust Fan Capacity Forming Part of Sentence 9.32.3.4.(1)

Column 1

Column 2

Number of Bedrooms in Dwelling Unit

Capacity, L/s

1

15

2

22.5

3

30

4

37.5

More than 4

Part 6 design

Table 9.32.3.4.B. Principal Exhaust Duct Size Forming Part of Sentence 9.32.3.4.(9)

Column 1

Column 2

Column 3

Column 4

Column 5

Number of Bedrooms in Dwelling Unit

Minimum Exhaust Duct Diameter

Ducts Connected to Inlet and Outlet of Principal Exhaust Fan

Ducts Connected to One Side Only of Principal Exhaust Fan

Smooth Duct, mm

Flexible Duct, mm

Smooth Duct, mm

Flexible Duct, mm

1

100

125

100

125

2

125

150

125

150

3

125

150

150

175

4

150

175

150

175

More than 4

Part 6 design

Part 6 design

Part 6 design

Part 6 design

9.32.3.5. — Supplemental Exhaust

(1) Additional supplemental exhaust capacity shall be installed as necessary so that the total capacity of all kitchen, bathroom, water closet room and other supplemental exhaust air intakes is not less than the total ventilation capacity, as required in Article 9.32.3.3.v1, minus the principal exhaust fan capacity, as required in Article 9.32.3.4.v1

(2) An exhaust air intake shall be installed in each kitchen, bathroom and water closet room.

(3) Where the intake for a supplemental exhaust fan other than a range hood or range-top fan is installed in a kitchen, it shall be installed in the ceiling or on the wall within 300 mm of the ceiling.

(4) Exhaust ducts serving the required kitchen, bathroom, water closet room and other supplemental exhaust air intakes shall be sized according to Part 6 except that they may be sized according to Table 9.32.3.5. where

(a) the total duct length does not exceed 9 m, and

(b) the number of elbows does not exceed 4, but, in any case, they shall not be smaller than recommended by the manufacturers of the fans.

(5) A supplemental exhaust fan required by this Article shall be controlled by a manual switch located in the room served by the exhaust fan.

(6) Where the supplemental exhaust is provided by an exhaust fan serving multiple exhaust air intakes required in rooms described in Sentence (2), the exhaust fan shall be controlled by a manual switch located in each room served by that exhaust fan and wired in parallel.

(7) Where the supplemental exhaust is provided by a principal exhaust fan serving multiple exhaust air intakes required in rooms described in Sentence (2), the principal exhaust fan shall be controlled by a manual switch located in each room served by that exhaust fan and wired in parallel with the manual switch required in Sentence 9.32.3.4.(5)v1.

(8) Where a supplemental fan required by this Article is controlled by a dehumidistat or other automatic control in addition to the manual switch required by Sentences (5) to (7), the manual switch shall be capable of activating the fan regardless of the setting of the automatic control.

(9) Supplemental exhaust required in this Article may be provided by means of a heat recovery ventilator installed in accordance with Article 9.32.3.11.

Text · e-Laws consolidated snapshot

Table 9.32.3.5. Kitchen, Bathroom and Water Closet Room Exhaust Duct Size Forming Part of Sentence 9.32.3.5.(4)

Column 1

Column 2

Column 3

Fan Capacity, L/s

Minimum Exhaust Duct Diameter(1)

Ducts Connected to Inlet and Outlet of Exhaust Fan, mm

Ducts Connected to One Side Only of Exhaust Fan, mm

25

125

125

50

150

150

Notes to Table 9.32.3.5.:

(1) Where flexible duct is used, the duct diameter shall be increased by 25 mm.

9.32.3.6. — Ventilation Systems Coupled with Forced Air Heating Systems

(1) This Article applies to a mechanical ventilation system in a dwelling unit that contains a forced air heating system and the forced air heating system is used for delivery of ventilation air.

(2) In a Type I dwelling unit, a ventilation supply inlet is not required.

(3) In a Type II dwelling unit, the mechanical ventilation system shall include a heat recovery ventilator, coupled to the forced air heating system, installed in accordance with Article 9.32.3.11.

(4) The forced air heating system circulation fan shall be controlled by a manual switch located adjacent to the ventilation fan switch required in Sentence 9.32.3.4.(4)v1.

(5) The switch required in Sentence (4) shall be identified by the words CIRCULATION FAN.

Text · e-Laws consolidated snapshot

9.32.3.7. — Ventilation Systems Not Coupled with Forced Air Heating Systems

(1) This Article applies to a mechanical ventilation system in a dwelling unit that,

(a) does not contains a forced air heating system, or

(b) contains a forced air heating system and the forced air heating system is not used for circulation of the ventilation air.

(2) The mechanical ventilation system shall introduce air to and circulate air throughout the dwelling unit in compliance with this Article.

(3) The mechanical system in this Article shall include a heat recovery ventilator installed in accordance with Article 9.32.3.11.

(4) Outdoor air shall be distributed by a ductwork system from the heat recovery ventilator required in Sentence (3) to each bedroom, to any storey without a bedroom and, if there is no storey without a bedroom, to the principal living area.

(5) A supply duct from the outdoors to the heat recovery ventilator required and a main distribution trunk duct shall be provided and shall be sized according to Part 6, except that, the supply duct and the main distribution trunk duct may be sized according to Table 9.32.3.7.A. where,

(a) the total duct length from the outdoor hood to any supply register does not exceed 21 m, and

(b) the total number of fittings does not exceed 8.

(6) The outside air supply duct required by Sentence (5) shall not be considered to provide combustion and/or dilution air to fuel-burning appliances.

(7) Branch supply ducts leading from the main distribution trunk duct required by Sentence (5) to the rooms to which outdoor air is to be distributed shall be provided and shall be sized according to Part 6 except that the branch supply ducts may be sized according to Table 9.32.3.7.B. where,

(a) the total duct length from outdoor hood to supply register does not exceed 21 m, and

(b) the total number of fittings does not exceed 8.

(8) In applying Sentence (7), where the dwelling unit has more than 4 bedrooms, ducting shall be sized according to Part 6.

(9) All branch supply ducts that are not fitted with diffusers with adjustable balance stops shall be supplied with accessible dampers that can be adjusted and fixed in their adjusted positions and that include devices to indicate the positions of the dampers.

(10) Provision shall be made for the free flow of air to all rooms by leaving gaps beneath doors, using louvred doors or installing grilles in doors.

Text · e-Laws consolidated snapshot

Table 9.32.3.7.A. Minimum Outdoor Air Supply and Main Trunk Duct Sizes Forming Part of Sentence 9.32.3.7.(5)

Column 1

Column 2

Number of Bedrooms in Dwelling Unit

Minimum Outdoor Air Supply and Main Distribution Trunk Duct Diameter, mm

1

150

2

150

3

175

4

175

More than 4

Part 6 design

Table 9.32.3.7.B. Minimum Branch Supply Duct Sizes Forming Part of Sentence 9.32.3.7.(7)

Column 1

Column 2

Column 3

Room, Space or Storey Served

Minimum Branch Supply Duct Diameter, mm

1 and 2 Bedroom Dwelling Units

3 and 4 Bedroom Dwelling Units

Master bedroom

10

100

Other bedrooms

75

75

Storey with no bedrooms or living area

75

100

9.32.3.8. — Protection Against Depressurization

(1) When determining the need to provide protection against depressurization, consideration must be given to,

(a) whether the presence of soil gas is deemed to be a problem, and

(b) the presence of solid fuel-fired combustion appliances.

(2) Where a solid fuel-fired combustion appliance is installed, the ventilation system shall include a heat recovery ventilator that is designed to operate so that the flow of exhaust air does not exceed the flow of intake air in any operating mode, and that complies with the requirements of Article 9.32.3.11.

Text · e-Laws consolidated snapshot

9.32.3.9. — Fan Ratings

(1) Except as provided in Sentence (4), capacity ratings for required fans shall be determined in accordance with,

(a) CAN/CSA-C260-M, “Rating the Performance of Residential Mechanical Ventilating Equipment”, or

(b) HVI 916, “Airflow Test Procedure”.

(2) Sound ratings for required fans shall be determined in accordance with,

(a) CAN/CSA-C260-M, “Rating the Performance of Residential Mechanical Ventilating Equipment”, or

(b) HVI 915, “Procedure for Loudness Rating of Residential Fan Products”.

(3) Capacity ratings for required fans shall be based on a static pressure differential of 50 Pa, 25 Pa or 7.5 Pa depending on whether the fan is installed with ductwork connected on both sides, one side or neither side, respectively.

(4) Except for heat recovery ventilators, exhaust fans required to make up any part of the total ventilation capacity required by Article 9.32.3.3.v1 shall have a sound rating not greater than that specified in Table 9.32.3.9.

(5) Required fans shall be installed according to the manufacturer's instructions.

(6) Mechanical ventilation devices shall conform to CSA C22.2 No. 113-M, “Fans and Ventilators”.

Text · e-Laws consolidated snapshot

Table 9.32.3.9. Fan Sound Rating Forming Part of Sentence 9.32.3.9.(4)

Column 1

Column 2

Column 3

Fan Application

Maximum Sound Rating, sones

Rated according to CAN/CSA-C260-M

Rated according to HVI 915

Principal exhaust fan

2.0

2.5

Supplemental exhaust fans installed in bathrooms and water closet rooms and their make-up air fans

2.5

3.5

Supplemental exhaust fans installed in kitchens and their make-up air fans

no rating required

no rating required

9.32.3.10. — Ducts

(1) Ventilation ducts shall conform to the requirements of Part 6 for supply ducts except that exhaust ducts that serve only a bathroom or water closet room may be of combustible material provided the duct is reasonably airtight and constructed of a material impervious to water.

(2) Exhaust ducts shall not discharge into heated or unheated enclosed spaces.

(3) Where an exhaust duct passes through or is adjacent to unheated space, the duct shall be insulated to not less than RSI 0.5.

(4) Where a supply duct carrying outdoor air that is not tempered or not mixed with indoor air passes through heated space, it shall be insulated to not less than RSI 0.5 except that, where such a duct is exposed in the heated space for more than 3 m of length in the heated space, it shall be insulated to not less than the values listed in Table 9.32.3.10.A.

(5) A kitchen exhaust duct not equipped with a filter at the inlet end shall be designed and installed so that the entire duct can be cleaned.

(6) Ductwork for range hoods and range-top fans shall be of noncombustible, corrosion-resistant material and shall lead directly to the outdoors without connection to other exhaust fans or ducts.

(7) Ductwork for range hoods and range-top fans shall be equipped with a grease filter at the intake.

(8) All ductwork shall be permanently supported or clipped to prevent sagging, excessive movement and vibration.

(9) All ducting connected to supply and exhaust fans shall be constructed so as to inhibit air leakage at joints.

(10) Where rectangular duct is used in place of round duct, it shall be selected according to Table 9.32.3.10.B.

Editor's note

This map follows the as-filed text of O. Reg. 350/06, whose member dimensions in the tables under Article 9.32.3.10. use the letter 'x' (e.g. '82 x 250'). The e-Laws consolidation editorially substitutes the multiplication sign '×'; no amending regulation makes this change.

Text · e-Laws consolidated snapshot

Table 9.32.3.10.A. Insulation of Fresh Air Supply Ducts Forming Part of Sentence 9.32.3.10.(4)

Column 1

Column 2

Outside Winter Design Temperature as per Supplementary Standard SB-1(1), °C

Minimum Thermal Resistance, RSI

–7 to –11

0.5

–12 to –17

0.9

–18 to –24

1.2

–25 to –29

1.4

–30 to –34

1.8

–35 and colder

2.1

Notes to Table 9.32.3.10.A:

(1) The outside winter design temperatures shall be those listed for the January 2.5 percent values.

Table 9.32.3.10.B. Equivalent Duct Sizes Forming Part of Sentence 9.32.3.10.(10)

Column 1

Column 2

Column 3

Column 4

Column 5

Required Round Duct Size, mm

Permitted Equivalent Rectangular Duct Size, mm

Stack Duct

100 mm Depth

125 mm Depth

150 mm Depth

75

82 × 250

57 × 100

100

82 × 250

89 × 100

75 × 125

75 × 150

125

82 × 250

125 × 100

100 × 125

89 × 150

150

82 × 300

200 × 100

150 × 125

125 × 150

175

82 × 350

275 × 100

200 × 125

175 × 150

More than 175

Part 6 design

Part 6 design

Part 6 design

Part 6 design

9.32.3.11. — Heat Recovery Ventilators

(1) Where a heat recovery ventilator is installed to provide all or part of the requirements of this Subsection, this Article shall apply.

(2) Heat recovery ventilators shall be designed to provide a minimum 55% sensible heat recovery efficiency when tested to the low temperature thermal and ventilation performance test method set out in CAN/CSA-C439, “Rating the Performance of Heat/Energy-Recovery Ventilators”, at a Station 1 test temperature of -25°C at an air flow not less than 30 L/s.

(3) Where a heat recovery ventilator is connected to a forced air heating system, the supply side of the ventilator shall be directly connected to the return air side of the forced air heating system.

(4) Two or more heat recovery ventilators shall not be connected in parallel air flow to a common air supply duct unless specifically recommended by the manufacturer.

(5) Two or more heat recovery ventilators shall not be connected in parallel air flow to a common downstream exhaust duct.

(6) Heat recovery ventilators installed in unheated spaces shall be installed so as to avoid condensation of moisture on fans and motors in exhaust air, in accordance with the manufacturer's instructions.

(7) All start-up procedures recommended by the manufacturer including air balancing and air-flow determination shall be followed.

(8) Free flow of condensate shall be provided in accordance with the manufacturer's recommendations or, in their absence, a condensate drain of minimum ½ inch nominal pipe size pitched in the direction of flow and complete with a trap or condensate pump with sufficient capacity shall be installed.

(9) The heat recovery ventilator and all condensate lines shall be installed in a space where the ambient temperature will not adversely affect the operation of the system.

(10) When operating at the rate required in Article 9.32.3.4.v1, the supply and exhaust airflow rates of the heat recovery ventilator shall be balanced so that the value of the lesser flow shall be at least 90% of the value of the greater flow, unless otherwise recommended by the manufacturer.

Text · e-Laws consolidated snapshot

9.32.3.12. — Outdoor Intake and Exhaust Openings

(1) Separate air intake and exhaust outlet openings, when located on the same wall or roof, shall be installed so as to avoid contamination of the ventilation air by the exhaust air.

(2) Intake openings shall be located so as to avoid contamination of the ventilation air from other local sources such as automobile exhausts and exhaust from adjacent buildings.

(3) The distance from the bottom of an air intake opening to finished ground level or to any nearer and lower permanent horizontal surface shall be not less than 450 mm or the depth of expected snow accumulation, whichever is greater.

(4) The distance separating air intakes from building envelope penetrations that are potential sources of contaminants, such as gas vents or oil fill pipes, shall be not less than 900 mm.

(5) Air intakes shall be clearly labelled as such for identification from locations outside the dwelling unit.

(6) The distance from the bottom of an exhaust outlet to finished ground level or to any nearer and lower permanent horizontal surface shall be not less than 100 mm.

(7) Where air intake and exhaust openings are in exposed locations, provision shall be made to protect them from the entry of precipitation by the use of louvres, weather cowls or other suitable protection.

(8) Air intake openings shall incorporate screens or grilles to protect against the entry of animals and insects.

(9) Except for exhaust outlets serving heat recovery ventilators, exhaust outlets shall incorporate backdraft dampers.

(10) Except for clothes dryers, exhaust outlets shall be fitted with screens of mesh not larger than 15 mm, except where climatic conditions may require larger openings.

(11) Where a screen or grille required by Sentences (8) and (10) has a screen mesh less than 6 mm, the screen or grille shall be removable for cleaning.

(12) The gross area of the screens or grilles installed in intake and exhaust openings shall be three times that of the duct served.

(13) Screens and grilles shall be of corrosion-resistant material.

(14) The net free area of an air intake or exhaust outlet shall be equal to or greater than the cross-sectional area of the duct served.

Text · e-Laws consolidated snapshot

9.32.3.13. — Installation

(1) Installation of fans and heat recovery ventilators shall be in accordance with manufacturer's instructions for minimizing noise and vibration transmission and achieving the required sound rating.

(2) Where flow-regulating dampers are required, they shall be adjustable and accessible without requiring the removal of fans, motors, or insulating materials and without the need for specialized tools.

(3) Ventilation equipment shall be accessible for inspection, maintenance, repair and cleaning.

(4) Ventilation equipment installed in unheated spaces shall be installed so as to avoid condensation of moisture on fans and motors in accordance with the manufacturer's instructions.

Text · e-Laws consolidated snapshot

9.33. — Heating and Air-Conditioning

Content not available for this version.

9.33.1. — General

Content not available for this version.

9.33.1.1. — Design and Installation Requirements

(1) The design and installation of central heating systems including requirements for combustion air, shall conform to the requirements in Part 6 and to this Section.

(2) The design and installation of air-conditioning systems shall conform to Part 6.

(3) Repairs, adjustments or component replacements that change the capacity or extent of safety of an existing heating, ventilating or air-conditioning system and that alter the method of operation shall conform to this Code.

Text · e-Laws consolidated snapshot

9.33.1.2. — Solid Fuel-Burning Appliances

(1) The design, construction and installation, including the provision of combustion air, of solid-fuel burning appliances and equipment, including stoves, ranges and space heaters, shall conform to CAN/CSA-B365-M, “Installation Code for Solid-Fuel-Burning Appliances and Equipment”.

Text · e-Laws consolidated snapshot

9.33.1.3. — Structural Movement

(1) Where the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55, heating and air-conditioning equipment with fuel or power connections shall be secured to the structure to resist overturning and displacement.

Text · e-Laws consolidated snapshot

9.33.2. — Required Heating Systems

Content not available for this version.

9.33.2.1. — Residential Heating Systems

(1) Residential buildings intended for use in the winter months on a continuing basis shall be equipped with heating facilities conforming to this Section.

Text · e-Laws consolidated snapshot

9.33.3. — Design Temperatures

Content not available for this version.

9.33.3.1. — Indoor Design Temperatures

(1) At the outside design temperature, required heating facilities shall be capable of maintaining an indoor air temperature of not less than,

(a) 22°C in all living spaces,

(b) 22°C in unfinished basements, and

(c) 15°C in heated crawl spaces.

Text · e-Laws consolidated snapshot

9.33.3.2. — Outdoor Design Temperatures

(1) The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be the appropriate values for the Municipality as set out in Supplementary Standard SB-1, using 2.5 per cent design temperature criteria.

Text · e-Laws consolidated snapshot

9.33.4. — Carbon Monoxide Detectors

Content not available for this version.

9.33.4.1. — Application

(1) This Subsection applies to every building that,

(a) contains a residential occupancy, and

(b) contains a fuel-burning appliance or a storage garage.

Text · e-Laws consolidated snapshot

9.33.4.2. — Location of Carbon Monoxide Detectors

(1) Where a fuel-burning appliance is installed in a suite of residential occupancy, a carbon monoxide detector shall be installed adjacent to each sleeping area in the suite.

(2) Where a fuel-burning appliance is installed in a service room that is not in a suite of residential occupancy, a carbon monoxide detector shall be installed,

(a) adjacent to each sleeping area in every suite of residential occupancy that is adjacent to the service room, and

(b) in the service room.

(3) Where a storage garage is located in a building containing a residential occupancy, a carbon monoxide detector shall be installed adjacent to each sleeping area in every suite of residential occupancy that is adjacent to the storage garage.

(4) Where a storage garage serves only the dwelling unit to which it is attached or built in, a carbon monoxide detector shall be installed adjacent to each sleeping area in the dwelling unit.

Text · e-Laws consolidated snapshot

9.33.4.3. — Installation and Conformance to Standards

(1) The carbon monoxide detector required by Article 9.33.4.2. shall,

(a) be permanently connected to an electrical circuit and shall have no disconnect switch between the overcurrent device and the carbon monoxide detector,

(b) be wired so that its activation will activate all carbon monoxide detectors within the suite, where located within a suite of residential occupancy,

(c) be equipped with an alarm that is audible within bedrooms when the intervening doors are closed, where located adjacent to a sleeping area, and

(d) conform to,

(i) CAN/CSA-6.19, “Residential Carbon Monoxide Alarming Devices”, or

(ii) UL 2034, “Single and Multiple Station Carbon Monoxide Alarms”.

Text · e-Laws consolidated snapshot

9.34. — Electrical Facilities

Content not available for this version.

9.34.1. — General

Content not available for this version.

9.34.1.1. — Reserved.

Content not available for this version.

Editor's note

As filed in O. Reg. 350/06, the heading of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed heading is retained here.

9.34.1.2. — Required Facilities

(1) Where electrical services are available, electrical facilities shall be provided for every building in conformance with this Section.

Text · e-Laws consolidated snapshot

9.34.1.3. — Location of Equipment in Public Areas

(1) Entrance switches, meters, panel boxes, splitter boxes, time clocks and other similar equipment shall not be located in any public area unless adequate precautions are taken to prevent interference with the equipment.

Text · e-Laws consolidated snapshot

9.34.1.4. — Recessed Lighting Fixtures

(1) Recessed lighting fixtures shall not be located in insulated ceilings unless the fixtures are designed for such installations.

Text · e-Laws consolidated snapshot

9.34.1.5. — Wiring and Cables

(1) Except for dwelling units and except as required in Sentence (2), electrical wiring and cables installed in buildings permitted to be of combustible construction shall conform to Sentence 3.1.4.3.(1).

(2) Where a concealed space in a floor or ceiling assembly is used as a plenum, electrical wiring and cables within the plenum shall conform to Sentence 3.6.4.3.(1).

Text · e-Laws consolidated snapshot

9.34.2. — Lighting Outlets

Content not available for this version.

9.34.2.1. — Lighting of Entrances

(1) An exterior lighting outlet with fixture controlled by a wall switch located within the building shall be provided at every entrance to buildings of residential occupancy.

Text · e-Laws consolidated snapshot

9.34.2.2. — Outlets in Dwelling Units

(1) Except as provided in Sentence (2), a lighting outlet with fixture controlled by a wall switch shall be provided in kitchens, bedrooms, living rooms, utility rooms, laundry rooms, dining rooms, bathrooms, water closet rooms, vestibules and hallways in dwelling units.

(2) Where a receptacle controlled by a wall switch is provided in bedrooms or living rooms, such rooms need not conform to the requirements of Sentence (1).

Text · e-Laws consolidated snapshot

9.34.2.3. — Stairways

(1) Every stairway shall be lighted.

(2) Except as provided in Sentence (3), 3-way wall switches located at the head and foot of every stairway shall be provided to control at least one lighting outlet with fixture for stairways with 4 or more risers in dwelling units.

(3) The stairway lighting for basements that do not contain finished space or lead to an outside entrance or built-in garage and that serve not more than one dwelling unit is permitted to be controlled by a single switch located at the head of the stairs.

Text · e-Laws consolidated snapshot

9.34.2.4. — Basements

(1) A lighting outlet with fixture shall be provided for each 30 m² of floor area or fraction of it in unfinished basements.

(2) The outlet required in Sentence (1) nearest the stairs shall be controlled by a wall switch located at the head of the stairs.

Text · e-Laws consolidated snapshot

9.34.2.5. — Storage Rooms

(1) A lighting outlet with fixture shall be provided in storage rooms.

Text · e-Laws consolidated snapshot

9.34.2.6. — Garages and Carports

(1) A lighting outlet with fixture shall be provided for an attached, built-in or detached garage or carport.

(2) Except as provided in Sentence (3), lighting outlets required in Sentence (1) shall be controlled by a wall switch near the doorway.

(3) Where the lighting outlet and fixture required in Sentence (1) are ceiling mounted above an area not normally occupied by a parked car; or are wall mounted, a fixture with a built-in switch is permitted to be used.

(4) Where a carport is lighted by a light at the entrance to a dwelling unit, additional carport lighting is not required.

Text · e-Laws consolidated snapshot

9.34.2.7. — Public and Service Areas

(1) Every public or service area in buildings, including a recreational camp and a camp for housing of workers, shall have lighting outlets with fixtures controlled by a wall switch or panel.

(2) When provided by incandescent lighting, illumination required in Sentence (1) shall conform to Table 9.34.2.7.

(3) When other types of lighting are used, illumination equivalent to that shown in Table 9.34.2.7. shall be provided.

Text · e-Laws consolidated snapshot

Table 9.34.2.7. Lighting for Public Areas Forming Part of Sentences 9.34.2.7.(2) and (3)

Column 1

Column 2

Column 3

Room or Space

Minimum Illumination, lx

Minimum Lighting Power Density, W/M2 of floor area (incandescent lighting)

Storage rooms

50

5

Service rooms and laundry areas

200

20

Garages

50

5

Public water closet rooms

100

10

Service hallways and stairways

50

5

Recreation rooms

100

10

Recreational camps and camps for housing of workers hallways, corridors, stairways and sleeping areas

100

10

Kitchen

500

50

All other rooms

250

25

9.34.3. — Emergency Lighting

Content not available for this version.

9.34.3.1. — Emergency Lighting

(1) Emergency lighting shall conform to Subsection 9.9.11.

Text · e-Laws consolidated snapshot

9.34.4. — Service Entrance Requirements

Content not available for this version.

9.34.4.1. — Meter Mounting Device

(1) Except in the case of externally mounted read-outs, each new residential consumer service of 200 amperes or less shall have a meter mounting device located outdoors in an accessible location.

(2) For the purposes of this Subsection, the front of the building is the side nearest the utility distribution line.

Text · e-Laws consolidated snapshot

9.34.4.2. — Location of Meter Mounting Device

(1) Meter mounting devices shall be installed on the wall of the building or where that is not possible, on a separate support, so that the midpoint of the meter after installation will be 1 750 mm ±100 mm from finished grade.

(2) Meter mounting devices shall be located not more than 3 m back from the front of the single family and semi-detached homes.

Text · e-Laws consolidated snapshot

9.34.4.3. — Location of Consumer Service Standpipe

(1) For an underground supply, the bottom of the consumer service standpipe shall be located not more than 3 m from the corner of the building.

(2) For an overhead supply, the top of the consumer service standpipe shall be located not more than 3 m from the corner of the building except that where this location does not permit a 4.5 m clearance at the point of attachment of the service conductors to the building, the top of the standpipe may be extended to a point not more than half way along the building.

Text · e-Laws consolidated snapshot

9.34.4.4. — Meter Mounting Device

(1) The meter mounting device shall be,

(a) one hundred ampere capacity except when the service equipment is to be greater,

(b) standardized for each service size, and

(c) capable of accepting 2 in. IPS conduit of steel, aluminum, copper or PVC if intended for underground service entrance.

Text · e-Laws consolidated snapshot

9.34.4.5. — Underground Service

(1) For consumer services supplied underground,

(a) a 2 in. IPS steel, aluminum, copper or PVC conduit shall be attached to the bottom of the meter-mounting device and shall terminate in the earth at a point at least 900 mm below grade and a conduit bushing shall be attached to the conduit in the earth, and

(b) the conductors on the line side of the meter and those on the load side of the meter shall not be installed in the same conduit.

Text · e-Laws consolidated snapshot

9.35. — Garages and Carports

Content not available for this version.

9.35.1. — Scope

Content not available for this version.

9.35.1.1. — Application

(1) This Section applies to garages and carports serving a single dwelling unit.

Text · e-Laws consolidated snapshot

9.35.1.2. — Construction Requirements

(1) The construction of a garage or carport shall conform to the requirements for other buildings in this Part except as provided in this Section.

Text · e-Laws consolidated snapshot

9.35.2. — General

Content not available for this version.

9.35.2.1. — Carport Considered to be Garage

(1) Where a roofed enclosure used for the storage or parking of motor vehicles has more than 60 per cent of the total perimeter enclosed by walls, doors or windows, the enclosure shall be considered a garage.

Text · e-Laws consolidated snapshot

9.35.2.2. — Garage Floor

(1) Where an attached or built-in garage is provided, the garage floor shall be sloped to drain liquids to the outdoors.

Text · e-Laws consolidated snapshot

9.35.3. — Foundations

Content not available for this version.

9.35.3.1. — Foundation Required

(1) Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors.

Text · e-Laws consolidated snapshot

9.35.3.2. — Protection from Damage due to Soil Movement

(1) In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the main building foundation.

(2) Where slab-on-ground construction is used, a construction joint shall be provided between the main building slab and the garage or breezeway or carport slab.

(3) Except as provided in Section 9.12., foundations for attached unheated garages or carports shall be below frost level.

Text · e-Laws consolidated snapshot

9.35.3.3. — Small Garages

(1) Detached garages of less than 50 m² floor area and not more than 1 storey in height may be supported on wood mud sills provided the garage is not of masonry or masonry veneer construction.

Text · e-Laws consolidated snapshot

9.35.3.4. — Column Piers

(1) Piers for the support of carport columns shall extend not less than 150 mm above ground level.

(2) Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size.

Text · e-Laws consolidated snapshot

9.35.4. — Walls and Columns

Content not available for this version.

9.35.4.1. — Interior Finish

(1) Interior finish need not be applied to garage and carport walls.

Text · e-Laws consolidated snapshot

9.35.4.2. — Columns

(1) Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used.

Text · e-Laws consolidated snapshot

9.35.4.3. — Anchorage

(1) Garage or carport walls and columns shall be anchored to the foundation to resist wind uplift in conformance with Subsection 9.23.6., except that where a garage is supported on the surface of the ground, ground anchors shall be provided to resist wind uplift.

Text · e-Laws consolidated snapshot

9.36. — Cottages

Content not available for this version.

9.36.1. — Scope

Content not available for this version.

9.36.1.1. — Application

(1) This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings.

(2) The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.

Text · e-Laws consolidated snapshot

9.36.2. — General

Content not available for this version.

9.36.2.1. — Exclusions

(1) Except as provided in Articles 9.36.3.1. and 9.36.2.4. and Subsection 9.10.15., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11.

(2) Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to support the live and dead loads.

(3) Except as provided in Sentences (4) and (5), thermal insulation, vapour barrier, air-barrier construction, interior finishes, plumbing, heating, mechanical ventilation, air-conditioning and electrical facilities, need not be provided, but where any of these are provided, they shall comply with the requirements of this Part.

(4) Where heating and air-conditioning are provided, Article 9.33.3.1. need not be complied with.

(5) Where thermal insulation is provided, the minimum thermal resistance of insulation in Table 9.25.2.1. need not be provided.

Text · e-Laws consolidated snapshot

9.36.2.2. — Foundations

(1) Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part.

(2) Where unit masonry columns are used, the height of such columns shall not exceed,

(a) in the case of hollow masonry units, 4 times the least dimension of the units,

(b) in the case of solid masonry units or hollow units with voids filled with concrete, 10 times the least dimension of the column, or

(c) where the column is reinforced with at least four 13 mm diameter bars and filled with concrete, 18 times the least dimension of the column.

(3) Columns in excess of the height limitations of Clauses (2)(a) to 2(c) shall be designed in accordance with Part 4.

Editor's note

As filed in O. Reg. 350/06, Sentence (3) cites 'Clauses (2)(a) to 2(c)', with a stray '2' before the closing '(c)'; the consolidated e-Laws text renders the range end in the standard form 'to (c)'. No amending regulation makes this change; the as-filed wording is retained here.

9.36.2.3. — Waterproofing and Dampproofing

(1) Where foundations below ground level and concrete floors on ground are used, they shall comply with Section 9.13.

Text · e-Laws consolidated snapshot

9.36.2.4. — Smoke Alarms

(1) Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.

Text · e-Laws consolidated snapshot

9.36.3. — Tourist Accommodation

Content not available for this version.

9.36.3.1. — Buildings for Seasonal Tourist Accommodation or for Rent

(1) Where buildings are used or intended to be used for seasonal tourist accommodation or for rent, they shall comply with Sections 9.5. to 9.8. in addition to the requirements of this Section.

Text · e-Laws consolidated snapshot

9.37. — Log Construction

Content not available for this version.

9.37.1. — General

Content not available for this version.

9.37.1.1. — Material Requirements

(1) Logs that are sound and free of fractures may be used for foundations, beams, posts and similar members providing it can be shown by a structural analysis or tests or previous experience that the strength of the member is adequate for its intended purposes.

Text · e-Laws consolidated snapshot

9.37.1.2. — Requirement for Wood Preservative

(1) The portion of any log coming in contact with masonry or concrete at or below grade shall be treated with a wood preservative to prevent decay.

Text · e-Laws consolidated snapshot

9.37.1.3. — Exterior Joints

(1) All exterior joints between logs shall be rendered water-tight by methods such as machined joints, oakum packing, cement parging, chinking, caulking or a combination of these.

Text · e-Laws consolidated snapshot

9.37.2. — Walls

Content not available for this version.

9.37.2.1. — Logs

(1) Walls may be built of natural or manufactured logs.

Text · e-Laws consolidated snapshot

9.37.2.2. — Attachment of Logs

(1) Walls made of logs in a horizontal position shall have interlocking intersections that will prevent the collection of water in the joints, or the horizontal logs shall butt to a vertical corner post to which the horizontal logs shall be firmly attached.

Text · e-Laws consolidated snapshot

9.37.2.3. — Joining Logs

(1) Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the distance between fastenings exceed 1 800 mm.

Text · e-Laws consolidated snapshot

9.37.2.4. — Vertical Logs

(1) Each log in a wall built of vertical logs shall be scribed to fit as closely as possible to the adjacent logs.

Text · e-Laws consolidated snapshot

9.37.2.5. — Plates

(1) Logs used in a vertical position shall have a plate at the top and a plate at the bottom and the plates shall be at least as wide as the largest end diameter of any of the logs.

Text · e-Laws consolidated snapshot

9.37.3. — Lintels

Content not available for this version.

9.37.3.1. — Support Over Openings

(1) Logs placed in vertical position shall be supported over window and door openings by lintels meeting the requirements of Tables A-12 to A-16.

Text · e-Laws consolidated snapshot

9.37.3.2. — Clearance

(1) At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement.

Text · e-Laws consolidated snapshot

9.38. — Reserved

Content not available for this version.

9.39. — Park Model Trailers

Content not available for this version.

9.39.1. — Scope

Content not available for this version.

9.39.1.1. — Application

(1) This Section applies to manufactured buildings designed and constructed in conformance with CAN/CSA-Z241 Series, “Park Model Trailers”, and used or intended to be used as a seasonal recreational building of residential occupancy.

Text · e-Laws consolidated snapshot

9.39.2. — General

Content not available for this version.

9.39.2.1. — General

(1) Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, “Park Model Trailers”.

Text · e-Laws consolidated snapshot

9.39.3. — Requirements

Content not available for this version.

9.39.3.1. — Other Building Components

(1) The requirements of this Code shall apply to building components designed and constructed outside the place of manufacture of a building described in Article 9.39.1.1.

Text · e-Laws consolidated snapshot

9.39.3.2. — Spatial Separation

(1) Buildings described in Article 9.39.1.1. shall comply with Section 9.10. where the building is,

(a) used or intended to be used for seasonal tourist accommodation, or

(b) leased or intended to be leased.

Text · e-Laws consolidated snapshot

9.39.3.3. — Foundations and Anchorage

(1) Buildings described in Article 9.39.1.1. shall be supported and anchored in conformance with the manufacturer's installation instructions.

Text · e-Laws consolidated snapshot

9.39.3.4. — Proximity to Above Ground Electrical Conductors

(1) Buildings described in Article 9.39.1.1. shall comply with Article 9.1.1.5.

Text · e-Laws consolidated snapshot

9.40. — Reinforced Concrete Slabs

Content not available for this version.

9.40.1. — Scope

Content not available for this version.

9.40.1.1. — Application

(1) This Section applies to,

(a) reinforced concrete slabs that are suspended over cold rooms in basements, and are supported by foundation walls along the perimeter of the slab with no additional interior supports and

(b) slabs in which the clear span between supporting walls is not more than 2 500 mm along the shortest dimension of the slab.

(2) Slabs for conditions other than described in Sentence (1) shall be designed in accordance with Part 4.

(3) This Section does not apply to reinforced concrete slabs intended to support motor vehicles.

Text · e-Laws consolidated snapshot

9.40.1.2. — Concrete

(1) Concrete shall conform to Section 9.3.

Text · e-Laws consolidated snapshot

9.40.1.3. — Reinforcing Steel

(1) Reinforcing steel shall conform to Grade 400 in CAN/CSA-G30.18-M, “Billet Steel Bars for Concrete Reinforcement”.

Text · e-Laws consolidated snapshot

9.40.1.4. — Slab Construction

(1) Concrete shall be cast against form work in accordance with CAN/CSA-A23.1-M, “Concrete Materials and Methods of Concrete Construction”.

(2) The slab shall be not less than 125 mm thick.

(3) The slab shall be reinforced with 10M bars spaced not more than 200 mm on centre in each direction, with 30 mm clear cover from the bottom of the slab to the first layer of bars, and the second layer of bars laid directly on top of the lower layer in the opposite direction.

(4) The slab shall bear not less than 75 mm on the supporting foundation walls and be anchored to the walls with 600 × 600 mm 10M bent dowels spaced at not more than 600 mm on centre.

(5) Exposed slabs shall be sloped to effectively shed water away from the exterior wall.

Text · e-Laws consolidated snapshot

9.41. — Additional Requirements for Change of Use

Content not available for this version.

9.41.1. — Scope

Content not available for this version.

9.41.1.1. — Application

(1) This Section applies where proposed construction in respect of an existing building will result in any of the following changes of use of all or part of the building:

(a) a change of the major occupancy of all or part of a building that is designated with a “Y” in Table 1.3.1.4.v1 of Division C,

(b) a suite of a Group C major occupancy is converted into more than one suite of a Group C major occupancy,

(c) a farm building or part of a farm building is changed to a major occupancy,

(d) a building or part of a building is changed to a post-disaster building, or

(e) the use of a building or part of a building is changed and the previous major occupancy of the building or part of the building cannot be determined.

(2) For the purposes of this Section and Sentences 11.4.2.1.(1) and 11.4.2.5.(4), the changes of use set out in Clauses (1)(b) to (e) shall also be deemed to constitute a change in major occupancy.

(3) The requirements of this Section are in addition to the requirements of other Parts of the Code as they apply to the proposed construction.

Text · e-Laws consolidated snapshot

9.41.2. — Additional Construction

Content not available for this version.

9.41.2.1. — Change of Use and Compensating Construction

(1) Where proposed construction will result in a change of use described in Clauses 9.41.1.1.(1)(a) to (d), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Sections 9.5. and 9.7., Subsection 9.10.17., Sections 9.31. and 9.32., and Subsections 9.34.1. to 9.34.3. as they apply to the new major occupancy that the building or part of a building is to support.

(2) For the purposes of this Article, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1)v1.

Text · e-Laws consolidated snapshot

9.41.2.2. — Performance Level Evaluation and Compensating Construction

(1) The performance level of a building after construction shall not be less than the performance level of the building prior to construction.

(2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3.v1v2 and 11.4.2.5.

(3) Where the proposed construction would reduce the performance level of an existing building, compensating construction shall be required in conformance with Articles 11.4.3.1., 11.4.3.2., 11.4.3.4.v1v2 and 11.4.3.6.

(4) Section 11.5. applies in respect of the requirements of Sentences 11.4.3.4.(1)v1v2, (3) and (4).

Text · e-Laws consolidated snapshot

Part 9 — Housing and Small Buildings

Content not available for this version.