OBC 2006 › Division B
9.28.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.28.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.28.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.28. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.28. — Pro
9.28. — Stucco
Content not available for this version.
9.28.1. — General
Content not available for this version.
9.28.1.1. — Sheathing Beneath Stucco
(1) Sheathing shall be provided beneath stucco applied over wood-frame walls except as permitted in Article 9.28.4.2.
(2) Where applied beneath stucco, sheathing shall conform to Subsection 9.23.16.
Text · e-Laws consolidated snapshot
9.28.1.2. — Lath and Reinforcing
(1) Stucco lath or reinforcing shall be used to attach stucco to any substrate other than masonry.
(2) Stucco lath or reinforcing shall be used to attach stucco to masonry where,
(a) the masonry is soft-burned tile or brick of less strength than the stucco, or
(b) the masonry surface is not sound, clean and sufficiently rough to provide a good key.
(3) Stucco applied over masonry chimneys shall be reinforced.
Text · e-Laws consolidated snapshot
9.28.1.3. — Concrete Masonry Units
(1) Stucco finish shall not be applied over concrete masonry units less than one month old unless the units have been cured by the autoclave process.
Text · e-Laws consolidated snapshot
9.28.1.4. — Clearance over Ground Level
(1) Stucco shall be not less than 200 mm above finished ground level except when it is applied over concrete or masonry.
Text · e-Laws consolidated snapshot
9.28.1.5. — Flashing and Caulking
(1) Flashing and caulking used with stucco shall conform to Subsections 9.27.3. and 9.27.4., except that if aluminum flashing is used, it shall be separated from the stucco by an impervious membrane or coating.
Text · e-Laws consolidated snapshot
9.28.2. — Stucco Materials
Content not available for this version.
9.28.2.1. — Portland Cement
(1) Portland cement shall conform to CAN/CSA-A3001, “Cementitious Materials for Use in Concrete”.
Text · e-Laws consolidated snapshot
9.28.2.2. — Aggregate
(1) Aggregate shall be clean, well-graded natural sand or sand manufactured from crushed stone, gravel or air-cooled blast furnace slag and shall contain no significant amounts of deleterious material.
(2) Aggregate grading shall conform to Table 9.28.2.2.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 |
Sieve Sizes, mm | % Aggregate Passing Sieve | |
Maximum | Minimum | |
4 | — | 100 |
2 | — | 90 |
1 | 90 | 60 |
0.5 | 60 | 45 |
0.25 | 30 | 10 |
0.125 | 5 | — |
9.28.2.3. — Water
(1) Water shall be clean and free of significant amounts of deleterious material.
Text · e-Laws consolidated snapshot
9.28.3. — Fasteners
Content not available for this version.
9.28.3.1. — Materials
(1) Fasteners for stucco lath or reinforcing shall be corrosion-resistant and of a material other than aluminum.
Text · e-Laws consolidated snapshot
9.28.3.2. — Nails and Staples
(1) Nails for stucco lath or reinforcing shall be not less than 3.2 mm diam with a head diameter of not less than 11.1 mm.
(2) Staples for stucco lath reinforcing shall be not less than 1.98 mm diam or thickness.
(3) Staples and nails for attaching stucco lath or reinforcing to vertical surfaces shall be of sufficient length to penetrate 25 mm into framing members or to the full depth of the sheathing where the sheathing is used for attachment.
(4) On horizontal surfaces nails for stucco lath or reinforcing shall be not less than 38 mm long.
Text · e-Laws consolidated snapshot
9.28.4. — Stucco Lath
Content not available for this version.
9.28.4.1. — Materials
(1) Rib lath or expanded metal stucco mesh shall be,
(a) copper-alloy steel coated with rust-inhibitive paint after fabrication, or
(b) galvanized.
(2) Woven or welded wire mesh shall be galvanized.
Text · e-Laws consolidated snapshot
9.28.4.2. — No Sheathing Required
(1) Sheathing need not be provided beneath stucco where not less than 1.19 mm diam galvanized wire is applied horizontally to the framing at vertical intervals not exceeding 150 mm, or where paper-backed welded wire metal lath is used.
Text · e-Laws consolidated snapshot
9.28.4.3. — Stucco Lath Specifications
(1) Stucco lath shall conform to Table 9.28.4.3.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 |
Location | Type of Lath | Minimum Diam. of Wire, mm | Maximum Mesh Opening | Minimum Mass, kg/m2 |
Vertical surfaces | Welded or woven wire | 1.15 | 25 mm | — |
1.30 | 38 mm | — | ||
1.50 | 51 mm | — | ||
Stucco mesh reinforcing (expanded metal) | — | 25.8 cm2 | 0.98 | |
Horizontal surfaces | 9.5 mm rib lath | — | — | 1.84 |
Cedar lath | — | — | — |
9.28.4.4. — Self-Furring Devices
(1) Stucco lath shall be held not less than 6 mm away from the backing by means of suitable self-furring devices.
Text · e-Laws consolidated snapshot
9.28.4.5. — Application of Stucco Lath
(1) Stucco lath shall be applied with the long dimension horizontal.
(2) Horizontal and vertical joints in stucco lath shall be lapped not less than 50 mm.
(3) End joints of stucco lath shall be staggered and shall occur over framing members.
(4) External corners of stucco lath shall be reinforced with a vertical strip of lath or reinforcing extending not less than 150 mm on both sides of the corner, or the lath or reinforcing shall extend around corners not less than 150 mm.
Text · e-Laws consolidated snapshot
9.28.4.6. — Fastening
(1) Stucco lath shall be fastened in conformance with Subsection 9.27.5.
(2) Fasteners on vertical surfaces shall be spaced not more than,
(a) 150 mm o.c. vertically and 400 mm o.c. horizontally, or
(b) 100 mm o.c. vertically and 600 mm o.c. horizontally.
(3) Nailing patterns other than those required in Sentence (2) are permitted to be used provided there are not fewer than 20 fasteners per square metre of wall surface.
(4) Fasteners on horizontal surfaces shall be spaced not more than,
(a) 150 mm o.c. along the framing members when members are spaced not more than 400 mm o.c., and
(b) 100 mm o.c. along members when members are spaced not more than 600 mm o.c.
Text · e-Laws consolidated snapshot
9.28.5. — Stucco Mixes
Content not available for this version.
9.28.5.1. — Mixes
(1) Stucco mixes shall conform to Table 9.28.5.1.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 |
Materials, volume | |||
Portland Cement | Masonry Cement | Lime | Aggregate |
1 | — | 0.25 to 1 | 3.25 to 4 parts per part of cementitious material |
1 | 1 | — | |
9.28.5.2. — Pigments
(1) Pigment if used shall consist of pure mineral oxides inert to the action of sun, lime and cement.
(2) Pigment shall not exceed 6% of the portland cement by weight.
Text · e-Laws consolidated snapshot
9.28.5.3. — Mixing
(1) Materials shall be thoroughly mixed before and after water is added.
(2) Stucco shall be applied not later than 3 h after the initial mixing.
Text · e-Laws consolidated snapshot
9.28.6. — Stucco Application
Content not available for this version.
9.28.6.1. — Low Temperature Conditions
(1) The base for stucco shall be maintained above freezing.
(2) Stucco shall be maintained at a temperature of not less than 10°C during application and for not less than 48 h afterwards.
Text · e-Laws consolidated snapshot
9.28.6.2. — Number of Coats and Total Thickness
(1) Stucco shall be applied with at least 2 base coats and one finish coat, providing a total thickness of not less than 15 mm, measured from the face of the lath or face of the masonry where no lath is used.
Text · e-Laws consolidated snapshot
9.28.6.3. — First Coat
(1) The first coat shall be not less than 6 mm thick, measured from the face of the lath or masonry, fully embedding the lath.
(2) The surface of the first coat shall be scored to provide a key with the second coat.
Text · e-Laws consolidated snapshot
9.28.6.4. — Second Coat
(1) The second coat shall be not less than 6 mm thick.
(2) The surface of the second shall be lightly roughened to provide a key with the finish coat if the finish coat is other than stone dash.
Text · e-Laws consolidated snapshot
9.28.6.5. — Finish Coat
(1) When the finish coat is other than stone dash, the base shall be dampened but not saturated before the finish coat is applied.
(2) The thickness of the finish coat shall be not less than 3 mm.
(3) When a stone dash finish is used, the stone shall be partially embedded in the second coat before the second coat starts to set or stiffen.