9.14. — Drainage

Content not available for this version.

9.14.1. — Scope

Content not available for this version.

9.14.1.1. — Application

(1) This Section applies to subsurface drainage and to surface drainage.

Text · e-Laws consolidated snapshot

9.14.1.2. — Crawl Spaces

(1) Drainage for crawl spaces shall conform to Section 9.18.

Text · e-Laws consolidated snapshot

9.14.1.3. — Floors-on-Ground

(1) Drainage requirements beneath floors-on-ground shall conform to Section 9.16.

Text · e-Laws consolidated snapshot

9.14.2. — Foundation Drainage

Content not available for this version.

9.14.2.1. — Foundation Wall Drainage

(1) Unless it can be shown to be unnecessary, drainage shall be provided at the bottom of every foundation wall that contains the building interior.

(2) Except as permitted in Sentences (4) to (6), where the insulation on a foundation wall extends to more than 900 mm below the adjacent exterior ground level,

(a) a drainage layer shall be installed adjacent to the exterior surface of a foundation wall consisting of,

(i) not less than 19 mm mineral fibre insulation with a density of not less than 57 kg/m3, or

(ii) not less than 100 mm of free draining granular material, or

(b) a system shall be installed that can be shown to provide equivalent performance to that provided by the materials described in Clause (a).

(3) Where mineral fibre insulation, crushed rock backfill or other drainage layer medium is provided adjacent to the exterior surface of a foundation wall,

(a) the insulation, backfill or other drainage layer medium shall extend to the footing level to facilitate drainage of ground water to the foundation drainage system, and

(b) any pyritic material in the crushed rock shall be limited to a concentration that will not damage the building to a degree that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

(4) Except when the insulation provides the drainage layer required in Clause (2)(a), when exterior insulation is provided, the drainage layer shall be installed on the exterior face of the insulation.

(5) The drainage layer required in Sentence (2) is not required,

(a) when the foundation wall is not required to be dampproofed, or

(b) when the foundation wall is waterproofed.

(6) The drainage layer in Sentence (2) is only required where the foundation wall is constructed after the day this Regulation comes into force.

(7) Where drainage is required in Sentence (1), the drainage shall conform to Subsection 9.14.3. or 9.14.4.

Text · e-Laws consolidated snapshot

9.14.3. — Drainage Tile and Pipe

Content not available for this version.

9.14.3.1. — Material Standards

(1) Drain tile and drain pipe for foundation drainage shall conform to,

(a) ASTM C4, “Clay Drain Tile and Perforated Clay Drain Tile”,

(b) ASTM C412M, “Concrete Drain Tile (Metric)”,

(c) ASTM C444M, “Perforated Concrete Pipe (Metric)”,

(d) ASTM C700, “Vitrified Clay Pipe, Extra Strength, Standard Strength and Perforated”,

(e) CAN/CGSB-34.22, “Asbestos-Cement Drain Pipe”,

(f) CAN/CSA-B182.1, “Plastic Drain and Sewer Pipe and Pipe Fittings”,

(g) CSA G401, “Corrugated Steel Pipe Products”, or

(h) NQ 3624-115, “Polythylene (PE) Pipe and Fittings – Flexible Corrugated Pipes for Drainage – Characteristics and Test Methods”.

Text · e-Laws consolidated snapshot

9.14.3.2. — Minimum Size

(1) Drain tile or pipe used for foundation drainage shall be not less than 100 mm in diam.

Text · e-Laws consolidated snapshot

9.14.3.3. — Installation

(1) Drain tile or pipe shall be laid on undisturbed or well-compacted soil so that the top of the tile or pipe is below the bottom of the floor slab or crawl space.

(2) Drain tile or pipe with butt joints shall be laid with 6 mm to 10 mm open joints.

(3) The top half of joints referred to in Sentence (2) shall be covered with sheathing paper, 0.10 mm polyethylene or No.15 asphalt or tar-saturated felt.

(4) The top and sides of drain pipe or tile shall be covered with not less than 150 mm of crushed stone or other coarse clean granular material containing not more than 10% of material that will pass a 4 mm sieve.

Text · e-Laws consolidated snapshot

9.14.4. — Granular Drainage Layer

Content not available for this version.

9.14.4.1. — Type of Granular Material

(1) Granular material used to drain the bottom of a foundation shall consist of a continuous layer of crushed stone or other coarse clean granular material containing,

(a) not more than 10% of material that will pass a 4 mm sieve, and

(b) no pyritic material in a concentration that would adversely affect its stability or the performance of assemblies separating dissimilar environments.

Text · e-Laws consolidated snapshot

9.14.4.2. — Installation

(1) Granular material described in Article 9.14.4.1. shall be laid on undisturbed or compacted soil to a minimum depth of not less than 125 mm beneath the building and extend not less than 300 mm beyond the outside edge of the footings.

Text · e-Laws consolidated snapshot

9.14.4.3. — Grading

(1) The bottom of an excavation drained by a granular layer shall be graded so that the entire area described in Article 9.14.4.2. is drained to a sump conforming to Article 9.14.5.2.

Text · e-Laws consolidated snapshot

9.14.4.4. — Wet Site Conditions

(1) Where because of wet site conditions soil becomes mixed with the granular drainage material, sufficient additional granular material shall be provided so that the top 125 mm is kept free of soil.

Text · e-Laws consolidated snapshot

9.14.5. — Drainage Disposal

Content not available for this version.

9.14.5.1. — Drainage Disposal

(1) Foundation drains shall drain to a sewer, drainage ditch or dry well.

Text · e-Laws consolidated snapshot

9.14.5.2. — Sump Pits

(1) Where gravity drainage is not practical, a covered sump with an automatic pump shall be installed to discharge the water into a sewer, drainage ditch or dry well.

(2) Covers for sump pits shall be designed to resist removal by children.

Text · e-Laws consolidated snapshot

9.14.5.3. — Dry Wells

(1) Dry wells are permitted to be used only when located in areas where the natural groundwater level is below the bottom of the dry well.

(2) Dry wells shall be not less than 5 m from the building foundation and located so that drainage is away from the building.

Text · e-Laws consolidated snapshot

9.14.6. — Surface Drainage

Content not available for this version.

9.14.6.1. — Surface Drainage

(1) The building shall be located or the building site graded so that water will not accumulate at or near the building and will not adversely affect adjacent properties.

Text · e-Laws consolidated snapshot

9.14.6.2. — Drainage away from Wells or Septic Disposal Beds

(1) Surface drainage shall be directed away from the location of a water supply well or septic tank disposal bed.

Text · e-Laws consolidated snapshot

9.14.6.3. — Window Wells

(1) Every window well shall be drained to the footing level or other suitable location.

Text · e-Laws consolidated snapshot

9.14.6.4. — Catch Basin

(1) Where runoff water from a driveway is likely to accumulate or enter a garage, a catch basin shall be installed to provide adequate drainage.

Text · e-Laws consolidated snapshot

9.14.6.5. — Downspouts

(1) Downspouts shall conform to Article 9.26.18.2.