9.18. — Crawl Spaces

Content not available for this version.

9.18.1. — General

Content not available for this version.

9.18.1.1. — Application

(1) In this Section, a crawl space refers to an enclosed space between the underside of a floor assembly and the ground cover directly below, with a clearance less than 1 800 mm in height.

Text · e-Laws consolidated snapshot

9.18.1.2. — Foundations

(1) Foundations enclosing crawl spaces shall conform to Section 9.15.

Text · e-Laws consolidated snapshot

9.18.1.3. — Heated and Unheated Crawl Spaces

(1) Crawl spaces shall be considered to be heated where the space,

(a) is used as a hot air plenum,

(b) contains heating ducts or heating pipes that are not sealed and insulated to minimize heat loss to the space, or

(c) is not separated from heated space in accordance with Section 9.25.

(2) Heating of heated crawl spaces shall conform to Section 9.33.

(3) Insulation, an air barrier system and a vapour barrier shall be installed in the walls of heated crawl spaces in accordance with Section 9.25.

Text · e-Laws consolidated snapshot

9.18.2. — Access

Content not available for this version.

9.18.2.1. — Access Openings

(1) An access opening of not less than 500 mm by 700 mm shall be provided to each crawl space where the crawl space serves a single dwelling unit, and not less than 550 mm by 900 mm for other crawl spaces.

(2) Access openings shall be fitted with a door or hatch, except when the crawl space is heated and the access opening into the crawl space is from the adjacent heated space.

Text · e-Laws consolidated snapshot

9.18.3. — Ventilation

Content not available for this version.

9.18.3.1. — Ventilation of Unheated Crawl Spaces

(1) Unheated crawl spaces shall be ventilated by natural or mechanical means.

(2) Where an unheated crawl space is ventilated by natural means, ventilation shall be provided to the outside air by not less than 0.1 m² of unobstructed vent area for every 50 m² of floor area.

(3) Vents shall be,

(a) uniformly distributed on opposite sides of the building, and

(b) designed to prevent the entry of snow, rain and insects.

Text · e-Laws consolidated snapshot

9.18.3.2. — Ventilation of Heated Crawl Spaces

(1) Heated crawl spaces shall be ventilated in accordance with Section 9.32.

Text · e-Laws consolidated snapshot

9.18.4. — Clearance

Content not available for this version.

9.18.4.1. — Access Way to Services

(1) Where equipment requiring service such as plumbing cleanouts, traps and burners is located in crawl spaces, an access way with a height and width of not less than 600 mm shall be provided from the access door to the equipment and for a distance of 900 mm on the side or sides of the equipment to be serviced.

Text · e-Laws consolidated snapshot

9.18.5. — Drainage

Content not available for this version.

9.18.5.1. — Drainage

(1) Except where it can be shown to be unnecessary, the ingress of water into a crawl space shall be controlled by grading or drainage.

(2) Drainage of foundation walls shall conform to Article 9.14.2.1.v1

(3) Drainage of the ground cover or floor-on-ground in the crawl space shall conform to Subsection 9.16.3.

(4) Drains shall conform to Section 9.14.

Text · e-Laws consolidated snapshot

9.18.6. — Ground Cover

Content not available for this version.

9.18.6.1. — Ground Cover in Unheated Crawl Spaces

(1) Where a crawl space is unheated, a ground cover shall be provided consisting of not less than,

(a) 50 mm of asphalt paving material,

(b) 100 mm of 15 MPa Portland cement concrete,

(c) Type S roll roofing, or

(d) 0.10 mm polyethylene.

(2) Joints in sheet-type ground cover required in Sentence (1) shall be lapped not less than 100 mm and weighted down.

Text · e-Laws consolidated snapshot

9.18.6.2. — Ground Cover in Heated Crawl Spaces

(1) Where a crawl space is heated, a ground cover consisting of not less than 0.15 mm polyethylene sheet conforming to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet, for Use in Building Construction”, shall be provided.

(2) The ground cover required in Sentence (1) shall,

(a) have its joints lapped not less than 300 mm, and sealed and weighted down, or

(b) be covered with a concrete skim coat not less than 50 mm thick.

(3) The perimeter of the ground cover required in Sentence (1) shall be sealed to the foundation wall.

Text · e-Laws consolidated snapshot

9.18.7. — Fire Protection

Content not available for this version.

9.18.7.1. — Crawl Spaces as Warm Air Plenums

(1) Only crawl spaces under 1-storey portions of dwelling units shall be used as warm-air plenums.

(2) Enclosing material in crawl spaces described in Sentence (1) including insulation shall have a surface flame-spread rating not greater than 150.

(3) Combustible ground cover used as enclosing material in Sentence (2) shall be covered with noncombustible material.

Text · e-Laws consolidated snapshot