9.18.6. — Ground Cover

Content not available for this version.

9.18.6.1. — Ground Cover in Unheated Crawl Spaces

(1) Where a crawl space is unheated, a ground cover shall be provided consisting of not less than,

(a) 50 mm of asphalt paving material,

(b) 100 mm of 15 MPa Portland cement concrete,

(c) Type S roll roofing, or

(d) 0.10 mm polyethylene.

(2) Joints in sheet-type ground cover required in Sentence (1) shall be lapped not less than 100 mm and weighted down.

Text · e-Laws consolidated snapshot

9.18.6.2. — Ground Cover in Heated Crawl Spaces

(1) Where a crawl space is heated, a ground cover consisting of not less than 0.15 mm polyethylene sheet conforming to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet, for Use in Building Construction”, shall be provided.

(2) The ground cover required in Sentence (1) shall,

(a) have its joints lapped not less than 300 mm, and sealed and weighted down, or

(b) be covered with a concrete skim coat not less than 50 mm thick.

(3) The perimeter of the ground cover required in Sentence (1) shall be sealed to the foundation wall.

Text · e-Laws consolidated snapshot