9.26. — Roofing

Content not available for this version.

9.26.1. — General

Content not available for this version.

9.26.1.1. — Purpose of Roofing

(1) Roofs shall be protected with roofing, including flashing, installed to shed rain effectively and prevent water due to ice damming from entering the roof.

(2) For the purpose of Sentence (1), roofs shall include platforms that effectively serve as roofs with respect to accumulation or drainage of precipitation.

Text · e-Laws consolidated snapshot

9.26.1.2. — Alternate Installation Methods

(1) Methods described in CAN3-A123.51-M, “Asphalt Shingle Application on Roof Slopes 1:3 and Steeper”, or CAN3-A123.52-M, “Asphalt Shingle Application on Roof Slopes 1:6 to Less than 1:3”, are permitted to be used for asphalt shingle applications not described in this Section.

Text · e-Laws consolidated snapshot

9.26.1.3. — Solar Collector Systems

(1) A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1)v1.

Text · e-Laws consolidated snapshot

9.26.2. — Roofing Materials

Content not available for this version.

9.26.2.1. — Material Standards

(1) Roofing materials shall conform to,

(a) CAN/CGSB-37.4-M, “Fibrated, Cutback Asphalt, Lap Cement for Asphalt Roofing”,

(b) CAN/CGSB-37.5-M, “Cutback Asphalt Plastic, Cement”,

(c) CAN/CGSB-37.8-M, “Asphalt, Cutback, Filled, for Roof Coating”,

(d) CGSB 37-GP-9Ma, “Primer, Asphalt, Unfilled, for Asphalt Roofing, Dampproofing and Waterproofing”,

(e) CGSB 37-GP-21M, “Tar, Cutback, Fibrated, for Roof Coating”,

(f) CAN/CGSB-37.50-M, “Hot Applied, Rubberized Asphalt for Roofing and Waterproofing”,

(g) CGSB 37-GP-52M, “Roofing and Waterproofing Membrane, Sheet Applied, Elastomeric”,

(h) CAN/CGSB-37-GP-54, “Polyvinyl Chloride Roofing and Waterproofing Membrane”,

(i) CGSB 37-GP-56M, “Membrane, Modified, Bituminous, Prefabricated, and Reinforced for Roofing”,

(j) CGSB 41-GP-6M, “Sheets, Thermosetting Polyester Plastics, Glass Fiber Reinforced”,

(k) CAN/CGSB-51.32-M, “Sheathing, Membrane, Breather Type”,

(l) CAN/CSA-A123.1, “Asphalt Shingles Made from Organic Felt and Surfaced with Mineral Granules”,

(m) CSA A123.2, “Asphalt Coated Roofing Sheets”,

(n) CAN/CSA-A123.3, “Asphalt or Tar Saturated Roofing Felt”,

(o) CAN/CSA-A123.4, “Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems”,

(p) CAN/CSA-A123.5, “Asphalt Shingles Made from Glass Felt and Saturated with Mineral Granules”,

(q) CSA A123.17, “Asphalt-Saturated Felted Glass-Fibre Mat for Use in Construction of Built-Up Roofs”,

(r) CAN/CSA-A220.0-M, “Performance of Concrete Roof Tiles”,

(s) CSA O118.1, “Western Cedars Shakes and Shingles”, or

(t) CSA O118.2-M, “Eastern White Cedar Shingles”.

Text · e-Laws consolidated snapshot

9.26.2.2. — Nails

(1) Nails used for roofing shall be corrosion-resistant roofing or shingle nails conforming to CSA B111, “Wire Nails, Spikes and Staples”.

(2) Nails shall have sufficient length to penetrate through or 12 mm into roof sheathing.

(3) Nails used with asphalt roofing shall have a head diameter of not less than 9.5 mm and a shank thickness of not less than 2.95 mm.

(4) Nails used with wood shingles or shakes shall have a head diameter of not less than 4.8 mm and a shank thickness of not less than 2.0 mm and shall be stainless steel, aluminum or hot-dipped galvanized.

Text · e-Laws consolidated snapshot

9.26.2.3. — Staples

(1) Staples used to apply asphalt or wood shingles shall be corrosion-resistant and shall be driven with the crown parallel to the eaves.

(2) Staples used with asphalt shingles shall be not less than 19 mm long, 1.6 mm diam or thickness, with not less than a 25 mm crown, except that an 11 mm crown may be used as provided in Sentence 9.26.7.4.(2).

(3) Staples used with wood shingles shall be not less than 29 mm long, 1.6 mm diam or thickness, with not less than a 9.5 mm crown and shall be stainless steel or aluminum.

Text · e-Laws consolidated snapshot

9.26.3. — Slope of Roof Surfaces

Content not available for this version.

9.26.3.1. — Slope

(1) Except as provided in Sentences (2) and (3), the slopes on which roof coverings may be applied shall conform to Table 9.26.3.1.

(2) Asphalt and gravel or coal tar and gravel roofs may be constructed with lower slopes than required in Sentence (1) when effective drainage is provided by roof drains located at the lowest points on the roofs.

(3) Profiled metal roof cladding systems specifically designed for low-slope applications are permitted to be installed with lower slopes than required in Sentence (1), provided they are installed in conformance with the manufacturer’s written recommendations.

(4) Except where back-slope will not adversely affect adjacent supported or supporting elements due to water ingress, roofs and elements that effectively serve as roofs shall be constructed with sufficient slope away from,

(a) exterior walls, and

(b) guards that are connected to the roof, or to an element that effectively serves as a roof, by other than pickets or posts.

(5) The slope required in Sentence (4) shall be sufficient to maintain a positive slope,

(a) after expected shrinkage of the building frame, where these surfaces are supported by exterior walls and on exterior columns, and

(b) once design loading is taken into consideration, where these surfaces are cantilevered from exterior walls.

Editor's note

In the notes to Table-9.26.3.1., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 9.26.3.1. Roofing Types and Slope Limits Forming Part of Sentence 9.26.3.1.(1)

Column 1

Column 2

Column 3

Type of Roofing

Minimum Slope

Maximum Slope

Asbestos-Cement Corrugated Sheets

1 in 4

no limit

Asphalt Shingles

Low slope application

1 in 6

no limit

Normal application

1 in 3

no limit

Built-up Roofing

Asphalt base (without gravel)

1 in 25

1 in 2

Asphalt base (gravelled)

1 in 50(1)

1 in 4

Coal-tar base (gravelled)

1 in 50(1)

1 in 25

Cold process

1 in 25

1 in 1.33

Cedar Shakes

1 in 3

no limit

Clay Tile

1 in 2

no limit

Glass Fibre Reinforced Polyester Roofing Panels

1 in 4

no limit

Modified Bituminous Membranes

1 in 50

1 in 4

Profiled Metal Roofing

1 in 4(2)

no limit

Roll Roofing

480 mm wide selvage asphalt roofing

1 in 6

no limit

Cold application felt

1 in 50

1 in 1.33

Smooth and mineral surfaced

1 in 4

no limit

Sheet Metal Shingles

1 in 4(2)

no limit

Slate Shingles

1 in 2

no limit

Wood Shingles

1 in 4

no limit

Notes to Table 9.26.3.1.:

(1)See Sentence 9.26.3.1.(2).

(2)See Sentence 9.26.3.1.(3).

9.26.4. — Flashing at Intersections

Content not available for this version.

9.26.4.1. — Required Flashing at Intersections

(1) Except where the omission will not adversely affect adjacent supported or supporting elements, flashing shall be installed at junctions between roofs and,

(a) walls that rise above the roof, and

(b) guards that are connected to the roof by other than pickets or posts.

(2) For the purpose of Sentence (1), roofs shall include platforms that effectively serve as roofs with respect to accumulation or drainage of precipitation.

Text · e-Laws consolidated snapshot

9.26.4.2. — Materials

(1) Sheet metal flashing shall consist of not less than,

(a) 1.73 mm thick sheet lead,

(b) 0.33 mm thick galvanized steel,

(c) 0.33 mm thick copper,

(d) 0.35 mm thick zinc, or

(e) 0.48 mm thick aluminum.

Text · e-Laws consolidated snapshot

9.26.4.3. — Valley Flashing

(1) Where sloping surfaces of shingled roofs intersect to form a valley, the valley shall be flashed.

(2) Valley flashing shall be installed over continuous sheathing.

(3) Closed valleys shall not be used with rigid shingles on slopes of less than 1 in 1.2.

(4) Closed valley flashing shall consist of sheet metal, self sealing composite membranes consisting of polyethylene and bituminous material or one layer of either Type S smooth surface roll roofing or Type M mineral surface roll roofing (mineral surface down) not less than 600 mm wide, and nails shall not penetrate the flashing within 75 mm of its edge or 124 mm of the bottom of the valley centreline.

(5) Open valleys shall be flashed with,

(a) at least one layer of sheet metal not less than 600 mm wide, or

(b) no fewer than 2 layers of roll roofing.

(6) The bottom layer of roofing required in Sentence (4) shall consist of not less than Type S smooth roll roofing or Type M mineral surface roll roofing (mineral surface down) not less than 457 mm wide, centred in the valley and fastened with nails spaced not more than 450 mm o.c. located 25 mm away from the edges.

(7) The top layer of roofing required in Sentence (4) shall consist of not less than Type M mineral surface roll roofing (mineral surface up), 914 mm wide, centred in the valley, applied over a 100 mm wide strip of cement along each edge of the bottom layer, and fastened with a sufficient number of nails to hold it in place until the shingles are applied.

Text · e-Laws consolidated snapshot

9.26.4.4. — Intersection of Shingle Roofs and Masonry

(1) The intersection of shingle roofs and masonry walls or chimneys shall be protected with flashing.

(2) Counter flashing required in Sentence (1) shall be embedded not less than 25 mm in the masonry and shall extend not less than 150 mm down the masonry and lap the lower flashing not less than 100 mm.

(3) Flashing along the slopes of a roof described in Sentence (1) shall be stepped so that there is not less than a 75 mm head lap in both the lower flashing and counter flashing.

(4) Where the roof described in Sentence (1) slopes upwards from the masonry, the flashing shall extend up the roof slope to a point equal in height to the flashing on the masonry, but not less than 1.5 times the shingle exposure.

Text · e-Laws consolidated snapshot

9.26.4.5. — Intersection of Shingle Roofs and Walls Other Than Masonry

(1) The intersection of shingle roofs and walls clad with other than masonry shall be protected with flashing.

(2) Flashing required in Sentence (1) shall be installed so that it extends up the wall not less than 75 mm behind the sheathing paper, and extends not less than 75 mm horizontally.

(3) Along the slope of the roof, the flashing required in Sentence (1) shall be stepped with not less than a 75 mm head lap.

Text · e-Laws consolidated snapshot

9.26.4.6. — Intersection of Built-Up Roofs and Masonry

(1) The intersection of built-up roofs with masonry walls or chimneys shall have a cant strip at the intersection and a roofing membrane shall be mopped over the cant strip and not less than 150 mm up the wall.

(2) Counter flashing installed over the intersection referred to in Sentence (1) shall be embedded not less than 25 mm in the masonry, and shall be of sufficient length to extend down not less than 150 mm, lapping the membrane on the masonry not less than 100 mm.

Text · e-Laws consolidated snapshot

9.26.4.7. — Intersection of Built-Up Roofs and Walls other than Masonry

(1) The intersection of built-up roofs with walls clad with other than masonry shall have a cant strip at the intersection.

(2) The roofing membrane shall be mopped over the cant strip referred to in Sentence (1).

(3) Flashing plies shall extend not less than 150 mm up the wall referred to in Sentence (1) behind the sheathing paper.

Text · e-Laws consolidated snapshot

9.26.4.8. — Chimney Saddles

(1) Except as otherwise permitted in Sentence (5), chimney saddles shall be installed where the upper side of a chimney on a sloping roof is more than 750 mm wide.

(2) Chimney saddles shall be covered with sheet metal or roofing material of equivalent weight and quality equivalent to the roofing.

(3) Saddles shall be flashed where they intersect the roof.

(4) The intersection of the saddle and the chimney shall be flashed and counterflashed as in Article 9.26.4.4.

(5) A chimney saddle need not be installed if the intersection between the chimney and roof is protected by sheet metal flashing that extends up the chimney to a height equal to at least one sixth the width of the chimney, but not less than 150 mm, and up the roof slope to a point equal in height to the flashing on the chimney, but not less than 1.5 times the shingle exposure.

(6) Flashing described in Sentence (5) at the chimney shall be counterflashed as required by Article 9.26.4.4.

Text · e-Laws consolidated snapshot

9.26.5. — Eave Protection for Shingles and Shakes

Content not available for this version.

9.26.5.1. — Required Eave Protection

(1) Except as provided in Sentence (2), eave protection shall be provided on shingle, shake or tile roofs, extending from the edge of the roof a minimum of 900 mm up the roof slope to a line not less than 300 mm inside the inner face of the exterior wall.

(2) Eave protection is not required,

(a) over unheated garages, carports and porches,

(b) where the roof overhang exceeds 900 mm measured along the roof slope from the edge of the roof to the inner face of the exterior wall,

(c) on roofs of asphalt shingles installed in accordance with Subsection 9.26.8.,

(d) on roofs with slopes of 1 in 1.5 or greater, or

(e) in regions with 3 500 or fewer degree-days.

Text · e-Laws consolidated snapshot

9.26.5.2. — Materials

(1) Eave protection shall be laid beneath the starter strip and shall consist of,

(a) No. 15 asphalt-saturated felt laid in two plies lapped 480 mm and cemented together with lap cement,

(b) Type M or S roll roofing laid with not less than 100 mm head and end laps cemented together with lap cement,

(c) glass fibre or polyester fibre coated base sheets, or

(d) self-sealing composite membranes consisting of modified bituminous coated material.

Text · e-Laws consolidated snapshot

9.26.6. — Underlay Beneath Shingles

Content not available for this version.

9.26.6.1. — Materials

(1) Except as required in Sentence (2), when underlay is used beneath shingles, it shall be,

(a) asphalt-saturated sheathing paper weighing not less than 0.195 kg/m², or

(b) No. 15 plain or perforated asphalt-saturated felt.

(2) Underlay used beneath wood shingles shall be breather type.

Text · e-Laws consolidated snapshot

9.26.6.2. — Installation

(1) When used with shingles, underlay shall be installed parallel to the eaves with head and end lap of not less than 50 mm.

(2) The top edge of each strip referred to in Sentence (1) shall be fastened with sufficient roofing nails to hold it in place until the shingles are applied.

(3) The underlay referred to in Sentence (1) shall overlap the eave protection by not less than 100 mm

Editor's note

As filed in O. Reg. 350/06, Sentence (3) of Article 9.26.6.2. ends without a terminal period ('...shall overlap the eave protection by not less than 100 mm'); the current e-Laws consolidation editorially supplies the missing period, with no amending regulation making the change. This map preserves the sentence as filed.

9.26.7. — Asphalt Shingles on Slopes of 1 in 3 or Greater

Content not available for this version.

9.26.7.1. — Coverage

(1) Coverage shall be not less than 2 thicknesses of shingle over the entire roof, disregarding cutouts.

Text · e-Laws consolidated snapshot

9.26.7.2. — Starter Strip

(1) A starter strip shall be installed along the lower edge of the roof so that it extends approximately 12 mm beyond the eaves and rake of the roof and fastened along the bottom edge with nails spaced not more than 300 mm o.c.

(2) Starter strips shall be at least Type M mineral-surfaced roll roofing not less than 300 mm wide, or shingles of the same weight and quality as those used as a roof covering with tabs facing up the roof slope.

(3) Starter strips need not be provided where eave protection of not less than Type M mineral-surfaced roll roofing is provided or self-sealing composite membranes consisting of polyethylene and bituminous material is provided.

Text · e-Laws consolidated snapshot

9.26.7.3. — Head Lap

(1) Shingles shall have a head lap of not less than 50 mm.

Text · e-Laws consolidated snapshot

9.26.7.4. — Fasteners

(1) Except as provided in Sentence (2), shingles shall be fastened with at least 4 nails or staples for 1 000 mm wide shingles so that no nails or staples are exposed.

(2) Where staples with an 11 mm crown are used, shingles shall be fastened with at least 6 staples.

(3) Fasteners may be reduced for narrower shingles in proportion to the width of the shingle or when shingles incorporating interlocking devices are used.

(4) Fasteners referred to in Sentences (1) and (2) shall be located 25 mm to 40 mm from each end of each strip shingle with other fasteners equally spaced between them.

(5) Fasteners referred to in Sentences (1) and (2) shall be located not less than 12 mm above the tops of the cutouts.

Text · e-Laws consolidated snapshot

9.26.7.5. — Securing of Tabs

(1) Shingle tabs shall be secured by a spot of plastic cement not exceeding 25 mm diam under the centre of each tab or by interlocking devices or self-sealing strips.

Text · e-Laws consolidated snapshot

9.26.7.6. — Hips and Ridges

(1) Shingles on hips and ridges shall be applied so they extend not less than 100 mm on either side of the hip or ridge, and shall be lapped not less than 150 mm.

(2) Shingles referred to in Sentence (1) shall be fastened with nails or staples on each side located not more than 25 mm from the edge and 25 mm above the butt of the overlying shingle.

Text · e-Laws consolidated snapshot

9.26.7.7. — Eave Protection

(1) Eave protection shall conform to Subsection 9.26.5.

Text · e-Laws consolidated snapshot

9.26.7.8. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.8. — Asphalt Shingles on Slopes of Less Than 1 in 3

Content not available for this version.

9.26.8.1. — Coverage

(1) Except for the first 2 courses, coverage shall be not less than 3 thicknesses of shingle over the entire roof, disregarding cutouts.

Text · e-Laws consolidated snapshot

9.26.8.2. — Starter Strip

(1) A starter strip shall be installed as in Article 9.26.7.2.

(2) Starter strips required in Sentence (1) shall be laid in a continuous band of cement not less than 200 mm wide.

Text · e-Laws consolidated snapshot

9.26.8.3. — Securing of Tabs

(1) Shingle tabs shall be secured with cold application cement applied at the rate of not less than 0.5 L/m² of cemented area, or hot application asphalt applied at the rate of 1 kg/m² of cemented area.

Text · e-Laws consolidated snapshot

9.26.8.4. — Securing of Shingle Courses

(1) The first course of shingles shall be secured by a continuous band of cement along the eaves applied so that the width of the band equals the shingle exposure plus 100 mm.

(2) The succeeding courses of shingles shall be secured by a continuous band of cement applied so that the width of the band equals the shingle exposure plus 50 mm.

(3) The band required in Sentence (2) shall be located not more than 50 mm above the butt of the overlying course of shingles.

Text · e-Laws consolidated snapshot

9.26.8.5. — Hips and Ridges

(1) Shingles on hips and ridges shall be not less than 300 mm wide applied to provide triple coverage.

(2) Shingles referred to in Sentence (1) shall be cemented to the roof shingles and to each other with a coat of cement and fastened with nails or staples located 40 mm above the butt of the overlying shingle and 50 mm from each edge.

Text · e-Laws consolidated snapshot

9.26.8.6. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.8.7. — Fastening

(1) Shingles shall be fastened in accordance with Article 9.26.7.4.

Text · e-Laws consolidated snapshot

9.26.9. — Wood Roof Shingles

Content not available for this version.

9.26.9.1. — Decking

(1) Decking for wood shingled roofs may be continuous or spaced.

Text · e-Laws consolidated snapshot

9.26.9.2. — Grade

(1) Western cedar shingles shall be not less than No. 2 grade.

(2) Eastern white cedar shingles shall be not less than B (clear) grade.

Text · e-Laws consolidated snapshot

9.26.9.3. — Size

(1) Wood shingles shall be not less than 400 mm long and not less than 75 mm nor more than 350 mm wide.

Text · e-Laws consolidated snapshot

9.26.9.4. — Spacing and Joints

(1) Shingles shall be spaced approximately 6 mm apart and offset at the joints in adjacent courses not less than 40 mm so that joints in alternate courses are staggered.

Text · e-Laws consolidated snapshot

9.26.9.5. — Fastening

(1) Shingles shall be fastened with 2 nails or staples located approximately 20 mm from the sides of the shingle and 40 mm above the exposure line.

Text · e-Laws consolidated snapshot

9.26.9.6. — Exposure

(1) The exposure of wood roof shingles shall conform to Table 9.26.9.6.

Text · e-Laws consolidated snapshot

Table 9.26.9.6. Exposure of Wood Shingles Forming Part of Sentence 9.26.9.6.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Roof Slope

Maximum Exposure, mm

No. 1 or A Grade Length of Shingle, mm

No. 2 or B Grade Length of Shingle, mm

400

450

600

400

450

600

<1 in 3

100

115

165

90

100

140

≥1 in 3

125

140

190

100

115

165

9.26.9.7. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.9.8. — Eave Protection

(1) Eave protection shall conform to Subsection 9.26.5.

Text · e-Laws consolidated snapshot

9.26.10. — Cedar Roof Shakes

Content not available for this version.

9.26.10.1. — Size and Thickness

(1) Shakes shall be not less than 450 mm long and not less than 100 mm nor more than 350 mm wide with a butt thickness of not more than 32 mm and not less than 9 mm.

Text · e-Laws consolidated snapshot

9.26.10.2. — Underlay

(1) Where eave protection is not provided, an underlay conforming to the requirements in Article 9.26.6.1. for wood shingles shall be laid as a strip not less than 900 mm wide along the eaves.

(2) A strip of material similar to that described in Sentence (1) not less than 450 mm wide shall be interlayed between each course of shakes with the bottom edge of the strip positioned above the butt line at a distance equal to double the exposure of the shakes.

(3) Interlayed strips in Sentence (2) shall be lapped at least 150 mm at hips and ridges in a manner that will prevent water from reaching the roof sheathing.

Text · e-Laws consolidated snapshot

9.26.10.3. — Spacing and Joints

(1) Shakes shall be spaced 6 mm to 9 mm apart and the joints in one course shall be separated not less than 40 mm from joints in adjacent courses.

Text · e-Laws consolidated snapshot

9.26.10.4. — Fastening

(1) Shakes shall be fastened with nails located approximately 20 mm from the sides of the shakes and 40 mm above the exposure line.

Text · e-Laws consolidated snapshot

9.26.10.5. — Exposure

(1) The exposure of wood shakes shall not exceed,

(a) 190 mm for shakes not less than 450 mm long, and

(b) 240 mm for shakes not less than 600 mm long.

Text · e-Laws consolidated snapshot

9.26.10.6. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.10.7. — Eave Protection

(1) Eave protection shall conform to Subsection 9.26.5.

Text · e-Laws consolidated snapshot

9.26.10.8. — Grade

(1) Shakes shall be not less than No. 1 or Handsplit grade.

Text · e-Laws consolidated snapshot

9.26.11. — Built-Up Roofs

Content not available for this version.

9.26.11.1. — Quantity of Materials

(1) The quantities of bituminous materials used on built-up roofs shall conform to Table 9.26.11.1.

Text · e-Laws consolidated snapshot

Table 9.26.11.1. Quantities of Bitumen for Built-Up Roofs Forming Part of Sentence 9.26.11.1.(1)

Column 1

Column 2

Column 3

Type of Roof

Amount of Bitumen per Square Metre of Roof Surface

Mopping Coats Between Layers

Flood Coat

Asphalt and aggregate

1 kg

3 kg

Coal-tar and aggregate

1.2 kg

3.6 kg

Cold process roofing

0.75 L cold process cement

2 L cold process top coating

9.26.11.2. — Coal-Tar and Asphalt Products

(1) Coal-tar products and asphalt products shall not be used together in built-up roof construction.

Text · e-Laws consolidated snapshot

9.26.11.3. — Roof Felts

(1) Bitumen roofing felts shall be not less than No.15 felt.

Text · e-Laws consolidated snapshot

9.26.11.4. — Aggregate Surfacing

(1) Aggregate used for surfacing built-up roofs shall be clean, dry and durable and shall consist of particles of gravel, crushed stone or air-cooled blast furnace slag having a size of from 6 mm to 15 mm.

(2) The minimum amount of aggregate surfacing per square metre of roof surface shall be 15 kg gravel or crushed stone or 10 kg crushed slag.

Text · e-Laws consolidated snapshot

9.26.11.5. — Flashing

(1) Flashing shall conform to Subsection 9.26.4.

Text · e-Laws consolidated snapshot

9.26.11.6. — Number of Layers

(1) Built-up roofing shall consist of at least 3 mopped-down layers of roofing felt flood coated with bitumen.

Text · e-Laws consolidated snapshot

9.26.11.7. — Installation of Layers

(1) In hot process applications each layer of bitumen-saturated felt shall be laid while the bitumen is hot, with each layer overlapping the previous one.

(2) The full width under each lap referred to in Sentence (1) shall be coated with bitumen so that in no place does felt touch felt.

(3) Felt shall be laid free of wrinkles and shall be rolled directly into the hot bitumen and broomed forward and outward from the centre to ensure complete adhesion.

Text · e-Laws consolidated snapshot

9.26.11.8. — Roofing over Wood-Based Sheathing

(1) Except as permitted in Sentence (2), built-up roofing applied over wood, plywood, OSB or waferboard roof sheathing shall be laid over an additional base layer of felt laid dry over the entire roof deck with at least a 50 mm headlap and a 50 mm sidelap between each sheet.

(2) Where plywood, OSB or waferboard roof sheathing is used, the dry layer of felt required in Sentence (1) may be omitted when the joints are taped and the sheathing is primed with asphalt.

Text · e-Laws consolidated snapshot

9.26.11.9. — Attachment to Decking

(1) Roofing shall be securely attached to the decking or where insulation is applied above the deck, the insulation shall be securely attached to the deck before the first layer of felt is fastened to the insulation.

Text · e-Laws consolidated snapshot

9.26.11.10. — Cant Strips

(1) Except as permitted in Sentence (4), a cant strip shall be provided at the edges of roofs.

(2) No fewer than 2 plies of the roofing membrane shall be carried over the top of the cant strip.

(3) Flashing shall extend over the top of the cant strip and be shaped to form a drip.

(4) The cant strip required in Sentence (1) may be omitted where a gravel stop is provided at the edge of roofs.

(5) The roofing membranes shall be carried over the edge of the roof before the gravel stop is fastened and 2 plies of roofing membrane mopped to the top surface of the gravel stop referred to in Sentence (4) before the flood coat is applied.

(6) The gravel stop referred to in Sentence (4) shall extend over the edge of the roof to form a drip or shall be flashed so that the flashing extends over the edge to form a drip.

Text · e-Laws consolidated snapshot

9.26.12. — Selvage Roofing

Content not available for this version.

9.26.12.1. — Double Coverage

(1) Wide selvage asphalt roofing shall provide double coverage over the entire roof surface.

Text · e-Laws consolidated snapshot

9.26.12.2. — Joints

(1) Plies of selvage roofing shall be cemented together to ensure a water-tight joint.

Text · e-Laws consolidated snapshot

9.26.13. — Sheet Metal Roofing

Content not available for this version.

9.26.13.1. — Thickness

(1) Sheet metal roofing shall be not less than,

(a) 0.33 mm thick galvanized steel,

(b) 0.46 mm thick copper,

(c) 0.46 mm thick zinc, or

(d) 0.48 mm thick aluminum.

Text · e-Laws consolidated snapshot

9.26.13.2. — Support

(1) Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be designed to support the specified live loads for roofs.

Text · e-Laws consolidated snapshot

9.26.14. — Glass Reinforced Polyester Roofing

Content not available for this version.

9.26.14.1. — Support

(1) Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced supports, the panels shall be designed to support the specified roof loads.

Text · e-Laws consolidated snapshot

9.26.15. — Hot Applied Rubberized Asphalt Roofing

Content not available for this version.

9.26.15.1. — Installation

(1) Hot applied rubberized asphalt roofing shall be installed in accordance with CAN/CGSB-37.51-M, “Application for Hot Applied Rubberized Asphalt for Roofing and Waterproofing”.

Text · e-Laws consolidated snapshot

9.26.16. — Polyvinyl Chloride Sheet Roofing

Content not available for this version.

9.26.16.1. — Installation

(1) Polyvinyl chloride sheet applied roofing membrane shall be installed in accordance with CGSB 37-GP-55M, “Application of Sheet Applied Flexible Polyvinyl Chloride Roofing Membrane”.

Text · e-Laws consolidated snapshot

9.26.17. — Concrete Roof Tiles

Content not available for this version.

9.26.17.1. — Installation

(1) Concrete roof tiles shall be installed according to CAN/CSA-A220.1-M, “Installation of Concrete Roof Tiles”.

Text · e-Laws consolidated snapshot

9.26.18. — Roof Drains and Downspouts

Content not available for this version.

9.26.18.1. — Roof Drains

(1) When roof drains are provided they shall conform to Part 7.

Text · e-Laws consolidated snapshot

9.26.18.2. — Downspouts

(1) Where downspouts are provided and are not connected to a sewer, extensions shall be provided to carry rainwater away from the building in a manner that will prevent soil erosion.

Text · e-Laws consolidated snapshot