9.26.6. — Underlay Beneath Shingles

Content not available for this version.

9.26.6.1. — Materials

(1) Except as required in Sentence (2), when underlay is used beneath shingles, it shall be,

(a) asphalt-saturated sheathing paper weighing not less than 0.195 kg/m², or

(b) No. 15 plain or perforated asphalt-saturated felt.

(2) Underlay used beneath wood shingles shall be breather type.

Text · e-Laws consolidated snapshot

9.26.6.2. — Installation

(1) When used with shingles, underlay shall be installed parallel to the eaves with head and end lap of not less than 50 mm.

(2) The top edge of each strip referred to in Sentence (1) shall be fastened with sufficient roofing nails to hold it in place until the shingles are applied.

(3) The underlay referred to in Sentence (1) shall overlap the eave protection by not less than 100 mm

Editor's note

As filed in O. Reg. 350/06, Sentence (3) of Article 9.26.6.2. ends without a terminal period ('...shall overlap the eave protection by not less than 100 mm'); the current e-Laws consolidation editorially supplies the missing period, with no amending regulation making the change. This map preserves the sentence as filed.