OBC 2006 › Division B
9.10.13.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.13.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.13.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.10.13. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.10.13. — Pro
9.10.13. — Doors, Dampers and Other Closures in Fire Separations
Content not available for this version.
9.10.13.1. — Closures
(1) Except as provided in Article 9.10.13.2.v1, openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with Chapters 2 to 14 of NFPA 80, “Fire Doors and Windows”, unless otherwise specified in this Part.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Required Fire-Resistance Rating of Fire Separation | Required Fire-Protection Rating of Closure |
30 or 45 min | 20 min(1) |
1 h | 45 min(1) |
1.5 h | 1 h |
2 h | 1.5 h |
3 h | 2 h |
4 h | 3 h |
Notes to Table 9.10.13.1.:
(1) See Article 9.10.13.2.v1
9.10.13.2. — Solid Core Wood Door as a Closure
(1) A 45 mm thick solid core wood door is permitted to be used where a minimum fire-protection rating of 20 min is permitted or between a public corridor and a suite provided the door conforms to CAN4-S113, “Wood Core Doors Meeting the Performance Required by CAN4-S104-77 for Twenty Minute Fire-Rated Closure Assemblies”.
(2) Doors described in Sentence (1) shall have not more than a 6 mm clearance beneath and not more than 3 mm at the sides and top.
Text · e-Laws consolidated snapshot
9.10.13.3. — Unrated Wood Door Frames
(1) Doors required to provide a 20 min fire-protection rating or permitted to be 45 mm solid core wood shall be mounted in a wood frame of at least 38 mm thickness where the frame has not been tested and rated.
Text · e-Laws consolidated snapshot
9.10.13.4. — Doors as a Means of Egress
(1) Doors forming part of an exit or a public means of egress shall conform to Subsection 9.9.6. in addition to this Subsection.
Text · e-Laws consolidated snapshot
9.10.13.5. — Wired Glass as a Closure
(1) Wired glass conforming to Article 9.7.3.1. that has not been tested in accordance with Article 9.10.3.1.v1 is permitted as a closure in a vertical fire separation required to have a fire-resistance rating of not more than 1 h provided such glass is not less than 6 mm thick and is mounted in conformance with Sentence (2).
(2) Wired glass described in Sentence (1) shall be mounted in fixed steel frames having a minimum metal thickness of not less than 1.35 mm and a glazing stop of not less than 20 mm on each side of the glass.
(3) Individual panes of glass described in Sentence (1) shall not exceed 0.8 m² in area or 1 400 mm in height or width, and the area of glass not structurally supported by mullions shall not exceed 7.5 m².
Text · e-Laws consolidated snapshot
9.10.13.6. — Steel Door Frames
(1) Steel door frames forming part of a closure in a fire separation, including anchorage requirements, shall conform to CAN4-S105-M, “Fire Door Frames Meeting the Performance Required by CAN4-S104”.
Text · e-Laws consolidated snapshot
9.10.13.7. — Glass Block as a Closure
(1) Glass block that has not been tested in accordance with Article 9.10.3.1.v1 is permitted as a closure in a fire separation required to have a fire-resistance rating of not more than 1 h.
Text · e-Laws consolidated snapshot
9.10.13.8. — Maximum Size of Opening
(1) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m², with no dimension greater than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.
(2) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 22 m², with no dimension greater than 6 m, when the fire compartments on both sides of the fire separation are sprinklered.
Text · e-Laws consolidated snapshot
9.10.13.9. — Door Latch
(1) Every swing type door in a fire separation shall be equipped with a latch.
Text · e-Laws consolidated snapshot
9.10.13.10. — Self-Closing Device
(1) Except as described in Sentence (2), every door in a fire separation shall have a self-closing device.
(2) Self-closing devices are not required between public corridors and suites in business and personal services occupancies, except in,
(a) dead-end corridors, or
(b) a corridor that serves a hotel.
Text · e-Laws consolidated snapshot
9.10.13.11. — Hold-Open Devices
(1) Where hold-open devices are used on doors in required fire separations, they shall be installed in accordance with Article 3.1.8.12.v1
Text · e-Laws consolidated snapshot
9.10.13.12. — Service Room Doors
(1) Swing-type doors shall open into service rooms containing fuel-fired equipment where such doors lead to public corridors or rooms used for assembly but shall swing outward from such rooms in all other cases.
Text · e-Laws consolidated snapshot
9.10.13.13. — Fire Dampers
(1) Except as permitted in Sentences (2) to (5) and Sentence 9.10.5.1.(4)v1, a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.9.
(2) A fire damper is not required where a noncombustible branch duct pierces a required fire separation provided the duct,
(a) has a melting point not below 760°C,
(b) has a cross-sectional area less than 0.013 m², and
(c) supplies only air-conditioning units or combined air-conditioning and heating units discharging air at not more than 1 200 mm above the floor.
(3) A fire damper is not required where a noncombustible branch duct pierces a required fire separation around an exhaust duct riser in which the air flow is upward provided,
(a) the melting point of the branch duct is not below 760°C,
(b) the branch duct is carried up inside the riser at least 500 mm, and
(c) the exhaust duct is under negative pressure as described in Article 9.10.9.18.
(4) Noncombustible ducts that penetrate a fire separation separating a vertical service space from the remainder of the building need not be equipped with a fire damper at the fire separation provided,
(a) the ducts have a melting point above 760°C, and
(b) each individual duct exhausts directly to the outside at the top of the vertical service space.
(5) A duct serving commercial cooking equipment and piercing a required fire separation need not be equipped with a fire damper at the fire separation.
Text · e-Laws consolidated snapshot
9.10.13.14. — Fire Stop Flaps
(1) Fire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(4)v1 shall be constructed in conformance with Supplementary Standard SB-2.
Text · e-Laws consolidated snapshot
9.10.13.15. — Doors Between Garages and Dwelling Units
(1) A door between an attached or built-in garage and a dwelling unit shall be tight-fitting and weatherstripped to provide an effective barrier against the passage of gases and exhaust fumes and shall be fitted with a self-closing device.
(2) A doorway between an attached or built-in garage and a dwelling unit shall not be located in a room intended for sleeping.
Text · e-Laws consolidated snapshot
9.10.13.16. — Door Stops
(1) Where a door is installed so that it may damage the integrity of a fire separation if its swing is unrestricted, door stops shall be installed to prevent such damage.