3.1.8.4.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.1.8.4. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 3.1.8.4. — Pro

3.1.8.4. — Determination of Ratings

(1) Except as permitted by Sentences (2) and 3.1.8.14.(1)v1, the fire-protection rating for a closure shall be determined on the basis of the results of tests conducted in conformance with the appropriate provisions in,

(a) CAN4-S104-M, “Fire Tests of Door Assemblies”,

(b) CAN4-S106-M, “ Fire Tests of Window and Glass Block Assemblies”, or

(c) CAN/ULC-S112-M, “Fire Test of Fire-Damper Assemblies”.

(2) Except as permitted by Sentence 3.1.8.10.(1)v1, the fire-protection rating of a closure shall conform to Table 3.1.8.4. for the required fire-resistance rating of the fire separation.

Text · e-Laws consolidated snapshot

Table 3.1.8.4. Fire-Protection Rating of Closure Forming Part of Sentence 3.1.8.4.(2)

Column 1

Column 2

Fire-Resistance Rating of Fire Separation

Required Fire-Protection Rating of Closure

30 min

20 min

45 min

45 min

1 h

45 min

1.5 h

1 h

2 h

1.5 h

3 h

2 h

4 h

3 h