OBC 2006 › Division B
3.1.8.4.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.1.8.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.1.8.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.1.8.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 3.1.8.4. — Pro
3.1.8.4. — Determination of Ratings
(1) Except as permitted by Sentences (2) and 3.1.8.14.(1)v1, the fire-protection rating for a closure shall be determined on the basis of the results of tests conducted in conformance with the appropriate provisions in,
(a) CAN4-S104-M, “Fire Tests of Door Assemblies”,
(b) CAN4-S106-M, “ Fire Tests of Window and Glass Block Assemblies”, or
(c) CAN/ULC-S112-M, “Fire Test of Fire-Damper Assemblies”.
(2) Except as permitted by Sentence 3.1.8.10.(1)v1, the fire-protection rating of a closure shall conform to Table 3.1.8.4. for the required fire-resistance rating of the fire separation.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Fire-Resistance Rating of Fire Separation | Required Fire-Protection Rating of Closure |
30 min | 20 min |
45 min | 45 min |
1 h | 45 min |
1.5 h | 1 h |
2 h | 1.5 h |
3 h | 2 h |
4 h | 3 h |