3.1.8.15.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.1.8.15. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 3.1.8.15. — Pro

3.1.8.15. — Temperature Rise Limit for Doors

(1) Except as permitted by Article 3.1.8.17., the maximum temperature rise on the opaque portion of the unexposed side of a door used as a closure in a fire separation in a location shown in Table 3.1.8.15., shall conform to the Table when tested in conformance with Sentence 3.1.8.4.(1).

Text · e-Laws consolidated snapshot

Table 3.1.8.15. Restrictions on Temperature Rise and Glazing for Closures Forming Part Articles of 3.1.8.15. and 3.1.8.16.

Column 1

Column 2

Column 3

Column 4

Column 5

Location

Minimum Required Fire-Protection Rating of Door

Maximum Temperature Rise on Opaque Portion of Unexposed Side of Door, °C

Maximum Area of Wired Glass in Door, m2

Maximum Aggregate Area of Glass Block and Wired Glass Panels not in Door, m2

Between a dead-end corridor and an adjacent occupancy where the corridor provides the only access to exit and is required to have a fire-resistance rating

Less than 45 min

No limit

No limit

No limit

45 min

250 after 30 min

0.0645

0.0645

Between an exit enclosure and the remainder of the floor area in buildings not more than 3 storeys in building height

All ratings

No limit

0.8

0.8

Between an exit enclosure and the remainder of the floor area (except as permitted above)

45 min

250 after 30 min

0.0645

0.0645

1.5 h

250 after 1 h

0.0645

0.0645

2 h

250 after 1 h

0.0645

0.0645

In a firewall

1.5 h

250 after 30 min

0.0645

0

3 h

250 after 1 h

0

0