CodeChronicle

OBC 2006 Division B

9.10.13.1.

Version 1 — in force 1 January 2010

In force · amended
Verified · covered Verified against the 2010-01-01–2010-03-31 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 9.10.13.1. — Pro

Base · O. Reg. 350/06 · ext v0 →

O. Reg. 503/09, cl. 145 · ext ← current

In force 2010-01-01

OBC 2012 · continues as 9.10.13.1. — Pro

9.10.13.1. — Closures

(1) Except as provided in Article 9.10.13.2.v1, openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives”, unless otherwise specified in this Part.

Text · e-Laws consolidated snapshot

Table 9.10.13.1. Fire-Protection Ratings for Closures Forming Part of Sentence 9.10.13.1.(1)

Column 1

Column 2

Required Fire-Resistance Rating of Fire Separation

Required Fire-Protection Rating of Closure

30 or 45 min

20 min(1)

1 h

45 min(1)

1.5 h

1 h

2 h

1.5 h

3 h

2 h

4 h

3 h

Notes to Table 9.10.13.1.:

(1)See Article 9.10.13.2.