9.10.13.1. — Closures

(1) Except as provided in Article 9.10.13.2.v1, openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with Chapters 2 to 14 of NFPA 80, “Fire Doors and Windows”, unless otherwise specified in this Part.

Text · e-Laws consolidated snapshot

Table 9.10.13.1. Fire-Protection Ratings for Closures Forming Part of Sentence 9.10.13.1.(1)

Column 1

Column 2

Required Fire-Resistance Rating of Fire Separation

Required Fire-Protection Rating of Closure

30 or 45 min

20 min(1)

1 h

45 min(1)

1.5 h

1 h

2 h

1.5 h

3 h

2 h

4 h

3 h

Notes to Table 9.10.13.1.:

(1) See Article 9.10.13.2.