OBC 2006 › Division B
3.1.8.12.
Version 1 — in force 1 January 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.1.8.12.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.1.8.12.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.1.8.12. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 19(3) · ext ← current
In force 2010-01-01
OBC 2012 · continues as 3.1.8.12. — Pro
3.1.8.12. — Hold-Open Devices
(1) A hold-open device is permitted on a door in a required fire separation, other than an exit door in a building more than 3 storeys in building height, and on a door for a vestibule required by Article 3.3.5.7., provided the device is designed to release the door in conformance with Sentences (2) to (7).
(2) Except as required by Sentences (3), (5), (6) and (7), a hold-open device permitted by Sentence (1) shall be designed to release by a signal from,
(a) an automatic sprinkler system,
(b) a heat-actuated device,
(c) fusible link, or
(d) a smoke detector located as described in NFPA 80, “Fire Doors and Other Opening Protectives”.
(3) Except as required by Sentences (4), (5), (6) and (7), a hold-open device permitted by Sentence (1) shall be designed to release upon a signal from a smoke detector located as described in NFPA 80, “Fire Doors and Other Opening Protectives”, if used on,
(a) an exit door,
(b) a door opening into a public corridor,
(c) an egress door referred to in Sentence 3.4.2.4.(2),
(d) a door serving,
(i) an assembly occupancy,
(ii) a care or detention occupancy, or
(iii) a residential occupancy, or
(e) a door required to function as part of a smoke control system.
(4) Except as required by Sentences (5), (6) and (7), a hold-open device permitted by Sentence (1) shall be designed to release upon a signal from the building fire alarm system if a fire alarm system is provided, except that this requirement does not apply to,
(a) a hold-open device on a door located between a corridor used by the public and an adjacent sleeping room in a hospital or nursing home, or
(b) a hold-open device that is designed to release by a heat-actuated device or a fusible link in conformance with Sentence (2).
(5) Sentences (2) and (3) do not apply in a hospital or nursing home to,
(a) a door located between a corridor used by the public and an adjacent sleeping room, or
(b) paired doors described in Sentence 3.3.3.3.(4).
(6) A hold-open device on a door in Clause (5)(a) shall be designed to release the door upon a signal from,
(a) a smoke detector as required by Sentence 3.2.4.11.(1) for sleeping rooms in Group B occupancies, and
(b) the fire alarm system when an alert signal is initiated within the same fire compartment in Sentence 3.3.3.5.(2)v1.
(7) A hold-open device on a door in Clause (5)(b) shall be designed to release the door upon a signal from the fire alarm system when an alert signal is initiated within the same fire compartment in Sentence 3.3.3.5.(2)v1.
(8) A rolling steel fire door installed as a closure in a fire separation shall be equipped with a hold-open device designed to release the shutter as described in Sentence (2).