3.1.8.11. — Self-Closing Devices

(1) Except as provided in Sentences (2) to (5) and 3.3.3.2.(5)v1v2, every door in a fire separation shall be equipped with a self-closing device designed to return the door to the closed position after each use.

(2) Self-closing devices need not be provided on doors to freight elevators and dumbwaiters.

(3) In a building that is not more than 3 storeys in building height, a self-closing device is not required on a door that is located between a classroom and a corridor providing access to exit from the classroom, except that a self-closing device is required on a door between a hazardous classroom and the corridor in an elementary or secondary school.

(4) In a building that is not more than 3 storeys in building height, a self-closing device is not required on a door between a public corridor and an adjacent room or suite of business and personal services occupancy if the door is not located in,

(a) a dead-end portion of the corridor, or

(b) a corridor that serves a hotel.

(5) Within a fire compartment in a hospital or nursing home that complies with the requirements of Article 3.3.3.5.v1, a self-closing device is not required on a door that is located between,

(a) a patient’s or resident’s sleeping room and a corridor serving the patient’s or resident’s sleeping room, or

(b) a patient’s or resident’s sleeping room and an adjacent room that serves the patient’s or resident’s sleeping room.