OBC 2006 › Division B
3.3.3.2.
Version 1 — in force 2 April 2007
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.3.2.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.3.2.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
Provenance
OBC 1997 · continues from 3.3.3.2. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 137/07, cl. 14 · ext ← current
In force 2007-04-02
O. Reg. 503/09, cl. 38 · ext v2 →
In force 2010-01-01
Next: O. Reg. 503/09, cl. 38 · ext (not in force until 2010-01-01) v2 →
OBC 2012 · continues as 3.3.3.2. — Pro
3.3.3.2. — Fire Separations
(1) The fire separation required by Sentence 3.3.5.5.(1) between a care or detention occupancy and a repair garage shall have no openings.
(2) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls between sleeping rooms and adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than 1 h, except that the fire-resistance rating need not be more than 45 min where the floor assembly is not required to be more than 45 min.
(3) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls separating corridors serving sleeping rooms from adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than 1 h, except that the fire-resistance rating need not be more than 45 min where the floor assembly is not required to be more than 45 min.
(4) The walls separating sleeping rooms from adjacent rooms and corridors in those parts of a floor area classified as a Group B, Division 3 occupancy shall be constructed as fire separations but are not required to have a fire-resistance rating if,
(a) those parts of the floor area contain sleeping accommodation for not more than 10 persons, and
(b) not more than six occupants require assistance in evacuation in case of an emergency.
(5) The door in the fire-separation required in Sentence (4) is permitted to be equipped with a roller latch and need to be provided with a self-closing device.
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · continues from 3.3.3.2. — Pro
Base · O. Reg. 350/06 · ext v0 → compare
O. Reg. 137/07, cl. 14 · ext ← current
In force 2007-04-02
O. Reg. 503/09, cl. 38 · ext v2 →
In force 2010-01-01 compare
Next: O. Reg. 503/09, cl. 38 · ext (not in force until 2010-01-01) v2 →
OBC 2012 · continues as 3.3.3.2. — Pro