(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.3.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.3.3. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 3.3.3. — Pro
3.3.3. — Care or Detention Occupancy
Content not available for this version.
3.3.3.1. — Scope
(1) This Subsection applies to care or detention occupancies.
Text · e-Laws consolidated snapshot
3.3.3.2. — Fire Separations
(1) The fire separation required by Sentence 3.3.5.5.(1) between a care or detention occupancy and a repair garage shall have no openings.
(2) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls between sleeping rooms and adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than 1 h, except that the fire-resistance rating need not be more than 45 min where the floor assembly is not required to be more than 45 min.
(3) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls separating corridors serving sleeping rooms from adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than 1 h, except that the fire-resistance rating need not be more than 45 min where the floor assembly is not required to be more than 45 min.
(4) In a Group B, Division 3 occupancy that contains sleeping accommodation for not more than 10 persons and not more than 6 occupants require assistance in evacuation in case of an emergency, the walls separating sleeping rooms from adjacent rooms and corridors shall be constructed as fire separations but are not required to have a fire-resistance rating.
(5) The door in the fire-separation required in Sentence (4) is permitted to be equipped with a roller latch and need to be provided with a self-closing device.
Text · e-Laws consolidated snapshot
3.3.3.3. — Corridors
(1) A corridor used by the public or serving patients or residents shall have no dead-end portion unless the area served by the dead-end portion has a second and separate means of egress.
(2) A corridor serving patients in a hospital shall be not less than 2 400 mm wide.
(3) Except as permitted in Sentence (5), a corridor serving residents who are not ambulatory in a Group B, Division 2 or 3 occupancy shall be not less than 1 650 mm wide.
(4) Paired doors in a corridor serving patients or residents shall,
(a) swing in opposite directions, the right hand door swinging in the direction of travel, and
(b) be not less than 1 100 mm wide.
(5) A corridor in a Group B, Division 3 occupancy that contains sleeping accommodation for not more than 10 persons and not more than 6 occupants require assistance in evacuation in case of an emergency need not comply with Sentence (3).
Text · e-Laws consolidated snapshot
3.3.3.4. — Doorway Width
(1) Except as permitted in Sentence 3.3.1.12.(12), the minimum clear width of doorways serving patients or residents shall be 1 050 mm.
Text · e-Laws consolidated snapshot
3.3.3.5. — Hospitals and Nursing Homes
(1) Floor areas containing patients’ or residents’ sleeping rooms in a hospital or nursing home shall conform to Sentences (2) to (12).
(2) Except as permitted by Sentence (3), a floor area containing patients’ or residents’ sleeping rooms in a hospital or nursing home shall be divided into no fewer than 2 fire compartments, each not more than 1 000 m2 in area.
(3) The floor area on either side of a horizontal exit conforming to Article 3.4.6.9. is permitted to be considered as a fire compartment in applying the requirements of this Article.
(4) Except as permitted by Sentence (5), fire separations separating fire compartments required by Sentence (2) shall have a fire-resistance rating not less than 1 h.
(5) The fire-resistance rating of a fire separation referred to in Sentence (4) is permitted to be less than 1 h but not less than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for,
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(6) A closure in a fire separation between fire compartments referred to in Sentence (2) shall be weatherstripped or otherwise designed and installed to retard the passage of smoke.
(7) The travel distance from any point within each fire compartment referred to in Sentence (2) to a door to an adjoining fire compartment shall be not more than 45 m.
(8) Each fire compartment referred to in Sentence (2) shall be capable of accommodating, in addition to its own occupants, the occupants of the largest adjacent fire compartment based on a clear floor space of 2.5 m2 per patient or resident in the adjacent fire compartment.
(9) Except as permitted by Sentences (10) and (12), walls between patients’ or residents’ sleeping rooms and the remainder of the floor area shall be constructed as fire separations but are not required to have a fire-resistance rating unless a fire-resistance rating is required by other provisions in this Part.
(10) The fire separation requirements of Sentence (9) do not apply to walls within a group of intercommunicating patients’ or residents’ rooms, provided the group of rooms does not
(a) contain more than 5 patients or residents, or
(b) include storage, bathing or toilet facilities serving persons not occupying the group of rooms.
(11) A door in a fire separation required by Sentence (9) is permitted to be equipped with a roller latch.
(12) A fire separation required by Sentence (9) shall not contain any grilles, louvres or other openings.
Text · e-Laws consolidated snapshot
3.3.3.6. — Protection for Special Care and Treatment Facilities
(1) Compartments containing rooms such as operating rooms, recovery rooms, delivery rooms, intensive care units and critical care units, from which it is impracticable to move patients in an emergency, shall be,
(a) separated from adjacent spaces by fire separations having a fire-resistance rating not less than 1 h, and
(b) provided with a mechanical air supply so that during a period of 2 h after the start of a fire in another space, the compartments will not contain more than 1% by volume of contaminated air from the fire area.
Text · e-Laws consolidated snapshot
3.3.3.7. — Contained Use Areas
(1) A contained use area shall conform to Sentences (2) to (5).
(2) A contained use area shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(3) Except as permitted by Sentence (4), a building that includes a contained use area shall be sprinklered.
(4) A contained use area, in a building for which Articles 3.2.2.20. to 3.2.2.83. do not require the installation of an automatic sprinkler system, is not required to be sprinklered as required by Sentence (3) provided,
(a) the building is designed so that during a period of 2 h after the start of a fire in the contained use area, other fire compartments will not contain more than 1% by volume of contaminated air from the contained use area,
(b) the building is designed so that during a period of 2 h after the start of a fire in another part of the building, the contained use area will not contain more than 1% by volume of contaminated air from the other part of the building,
(c) all doors are designed to be remotely released in conformance with Sentence 3.3.1.12.(6), and
(d) the contained use area does not contain any rooms lined with combustible padding.
(5) A corridor serving a contained use area shall have no dead-end portion unless the area served by the dead-end portion has a second and separate means of egress.
Text · e-Laws consolidated snapshot
3.3.3.8. — Handrails
(1) Corridors and ramps used by residents in a nursing home shall be equipped with handrails on each side conforming to Sentences 3.4.6.4.(3)v1, (4), (6), (7) and (8).
Text · e-Laws consolidated snapshot