OBC 2006 Division B

8.2.1.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 8.2.1. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 8.2.1. — Pro

8.2.1. — General Requirements

Content not available for this version.

8.2.1.1. — Scope

(1) This Subsection applies to the design of sewage systems.

Text · e-Laws consolidated snapshot

8.2.1.2. — Site Evaluation

(1) A site evaluation shall be conducted on every site where a new or replacement sewage system is to be installed.

(2) The percolation time shall be determined by either percolation tests or by classifying the soil according to the Unified Soil Classification System as described in Supplementary Standard SB-5.

(3) Where the percolation time is determined by a percolation test, there shall be a minimum of 3 locations selected, suitably spaced to accurately evaluate the leaching bed area, with the highest percolation time of the tests being used

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 8.2.1.2. of Division B, in which Sentence (3) ('... with the highest percolation time of the tests being used') ends without a sentence-ending period. The e-Laws consolidation editorially adds a terminal period, with no amending regulation making the change. This map preserves the as-filed wording.

8.2.1.3. — Sewage System Design Flows

(1) For residential occupancies, the total daily design sanitary sewage flow shall be at least the value in Column 2 as determined from Table 8.2.1.3.A.

(2) For all other occupancies, the total daily design sanitary sewage flow shall be at least the value in Column 2 as determined from Table 8.2.1.3.B.

(3) Where a building contains more than one establishment, the total daily design sanitary sewage flow shall be the sum of the total daily design sanitary sewage flow for each establishment.

(4) Where an occupancy is not listed in Table 8.2.1.3.B., the highest of metered flow data from at least 3 similar establishments shall be acceptable for determining total daily design sanitary sewage flow.

Editor's note

In the notes to Table-8.2.1.3.A., Table-8.2.1.3.B., a separating space follows the footnote reference numbers; the e-Laws consolidation omits it. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 8.2.1.3.A. Residential Occupancy Forming Part of Sentence 8.2.1.3.(1)

Column 1

Column 2

Residential Occupancy

Volume, litres

Apartments, Condominiums, Other Multi-family Dwellings - per person(1)

275

Boarding Houses

    a) Per person,

      i) with meals and laundry facilities, or,

200

      ii) without meal or laundry facilities, and

150

    b) Per non-resident staff per 8 hour shift

40

Boarding School - per person

300

Dwellings

    a) 1 bedroom dwelling

750

    b) 2 bedroom dwelling

1100

    c) 3 bedroom dwelling

1600

    d) 4 bedroom dwelling

2000

    e) 5 bedroom dwelling

2500

    f) Additional flow for(2)

      i) each bedroom over 5,

500

      ii) A) each 10 m2 (or part of it) over 200 m2 up to 400 m2 (3) ,

100

        B) each 10 m2 (or part of it) over 400 m2 up to 600 m2 (3) , and

75

        C) each 10 m2 (or part of it) over 600 m2 (3) , or

50

      iii) each fixture unit over 20 fixture units

50

Hotels and Motels (excluding bars and restaurants)

    a) Regular, per room

250

    b) Resort hotel, cottage, per person

500

    c) Self service laundry, add per machine

2500

Work Camp/Construction Camp, semi-permanent per worker

250

Notes to Table 8.2.1.3.A.:

(1) The occupant load shall be calculated using Subsection 3.1.17.

(2)Where multiple calculations of sewage volume is permitted the calculation resulting the highest flow shall be used in determining the design daily sanitary sewage flow.

(3)Total finished area, excluding the area of the finished basement.

Table 8.2.1.3.B. Other Occupancies Forming Part of Sentence 8.2.1.3.(2)

Column 1

Column 2

Establishments(1)

Volume, litres

Airports, Bus Terminals, Train Stations, Dock/Port Facilities (Food Services excluded)

    a) Per passenger, and

20

    b) Per employee per 8 hour shift

40

Assembly Hall - per seat

    a) No food service, or

8

    b) Food service provided

36

Barber Shop/Beauty Salon - per service chair

650

Bowling Alleys (Food Service not included) - per lane

400

Churches and Similar Places of Worship - per seat

    a) No kitchen facilities, or

8

    b) Kitchen facilities provided

36

Country Club (excluding Food Service)

    a) Per resident,

375

    b) Per employee per 8 hour shift, and

50

    c) Per member or patron

40

Day Care Facility per person (staff and children)

75

Dentist Office

    a) Per wet service chair, and

275

    b) Per dry service chair

190

Doctors Office

    a) Per practitioner, and

275

    b) Per employee per 8 hour shift

75

Factory (excluding process or cleaning waters) - per employee per 8 hour shift

    a) No showers, or

75

    b) Including showers

125

Flea Markets(2) (open not more than 3 days per week)

    a) Per non-food service vendor space,

60

    b) Per food service establishment / 9.25 m2 of floor space, and

190

    c) Per limited food service outlet

95

Food Service Operations

    a) Restaurant (not 24 hour), per seat

125

    b) Restaurant (24 hour), per seat

200

    c) Restaurant on controlled access highway, per seat

400

    d) Paper service restaurant, per seat

60

    e) Donut shop, per seat

400

    f) Bar and cocktail lounge, per seat

125

    g) Drive-in restaurant per parking space

60

    h) Take-out restaurant (no seating area)

      i) per 9.25 m2 of floor area, and

190

      ii) per employee per 8 hour shift

75

    i) Cafeteria - per meal

12

    j) Food outlet

      i) excluding delicatessen, bakery and meat department, per 9.25 m2 of floor space,

40

      ii) per 9.25 m2 of delicatessen floor space,

190

      iii) per 9.25 m2 of bakery floor space,

190

      iv) per 9.25 m2 of meat department floor space, and

380

      v) per water closet

950

Hospitals - per bed

    a) Including laundry facilities, or

750

    b) Excluding laundry facilities

550

Nursing Homes, Rest Homes, etc. - per bed

450

Office Building(3)

    a) Per employee per 8 hour shift, or

75

    b) Per each 9.3 m2 of floor space

75

Public Parks

    a) With toilets only per person, or

20

    b) With bathhouse, showers, and toilets per person

50

Recreational Vehicle or Campground Park

    a) Per site without water or sewer hook-up, or

275

    b) Per site with water and sewer hook-up

425

Schools - per student

    a) Day school,

30

    b) With showers,

30

    c) With cafeteria, and

30

    d) Per non-teaching employee per 8 hour shift

50

Service Stations (no vehicle washing)(3)

    a) Per water closet, and

950

      i) per fuel outlet(4), or

560

      ii) per vehicle served

20

Shopping Centre (excluding food and laundry) - per 1.0 m2 of floor space

5

Stadiums, Race Tracks, Ball Parks - per seat

20

Stores(3)

    a) Per 1.0 m2 of floor area, or

5

    b) Per water closet

1230

Swimming and Bathing Facilities (Public) - per person

40

Theatres

    a) Indoor, auditoriums per seat,

20

    b) Outdoor, drive-ins per space, or

40

    c) Movie theatres per seat

15

Veterinary Clinics

    a) Per practitioner,

275

    b) Per employee per 8 hour shift, and

75

    c) Per stall, kennel, or cage if floor drain connected

75

Warehouse

    a) Per water closet, and

950

    b) Per loading bay

150

Notes to Table 8.2.1.3.B.:

(1)The occupant load shall be calculated using Subsection 3.1.17.

(2)Flea markets open more than 3 days per week shall be assessed using the volumes stated under the heading “Stores”.

(3)Where multiple calculations of sanitary sewage volume is permitted the calculation resulting in the highest flow shall be used in determining the design daily sanitary sewage flow.

(4)The number of fuel outlets is considered the maximum number of gas nozzles that could be in use at the same time.

8.2.1.4. — Clearances

(1) Unless it can be shown to be unnecessary, where the percolation time is 10 minutes or greater, the location of all components within a sewage system shall be in conformance with the clearances listed in Articles 8.2.1.5. or 8.2.1.6.v1

(2) Unless it can be shown to be unnecessary, where the percolation time is less than 10 minutes, the clearances listed in Articles 8.2.1.5. and 8.2.1.6.v1 for wells, lakes, ponds, reservoirs, rivers, springs or streams shall be increased to compensate for the lower percolation time.

(3) No building shall be constructed closer to any part of a sewage system than the clearances listed in Articles 8.2.1.5. or 8.2.1.6.v1

(4) If more than one sewage system is located on a lot or parcel of land, there shall be no overlap of any part of the systems.

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 8.2.1.4. of Division B, in which Sentences (1) and (3) refer to the clearances listed in 'Articles 8.2.1.5. or 8.2.1.6.' using the plural 'Articles', because the reference is to two articles. The e-Laws consolidation editorially renders both references in the singular as 'Article 8.2.1.5. or 8.2.1.6.', with no amending regulation making the change. This map preserves the as-filed wording.

8.2.1.5. — Clearance Distances for Class 1, 2 and 3 Sewage Systems

(1) Except as provided in Sentences 8.2.1.4.(1) and (2), no Class 1, 2, or 3 sewage system shall have a horizontal distance of less than that permitted by Table 8.2.1.5.

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 8.2.1.5. of Division B, in which Sentence (1) reads 'no Class 1, 2, or 3 sewage system' with a serial comma before 'or'. The e-Laws consolidation editorially drops the serial comma, rendering 'Class 1, 2 or 3', with no amending regulation making the change. This map preserves the as-filed wording.

Text · e-Laws consolidated snapshot

Table 8.2.1.5. Clearance Distances for Class 1, 2 and 3 Sewage Systems Forming Part of Sentence 8.2.1.5.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Sewage System

Minimum horizontal distance in metres from a well with watertight casing to a depth of at least 6 m

Minimum horizontal distance in metres from a spring used as a source of potable water or well other than a well with a water tight casing to a depth of at least 6 m

Minimum horizontal distance in metres from a lake, river, pond, stream, reservoir, or a spring not used as a source of potable water

Minimum horizontal distance in metres from a property line

Earth Pit Privy

15

30

15

3

Privy Vault

Pail Privy

10

15

10

3

Greywater System

10

15

15

3

Cesspool

30

60

15

3

8.2.1.6. — Clearances for a Class 4 or 5 Sewage System

(1) Except as provided in Sentences 8.2.1.4.(1) and (2), a treatment unit shall not be located closer than the minimum horizontal distances as set out in Table 8.2.1.6.A.

(2) Except as provided in Sentences 8.2.1.4.(1) and (2), a distribution pipe shall not be located closer than the minimum horizontal distances set out in Table 8.2.1.6.B. and these distances shall be increased when required by Sentence 8.7.4.2.(9).

(3) Except as provided in Sentences 8.2.1.4.(1) and (2), a holding tank shall not be located closer than the minimum horizontal distances set out in Table 8.2.1.6.C.

Text · e-Laws consolidated snapshot

Table 8.2.1.6.A. Minimum Clearances for Treatment Units Forming Part of Sentence 8.2.1.6.(1)

Column 1

Column 2

Object

Minimum Clearance, m

Structure

1.5

Well

15

Lake

15

Pond

15

Reservoir

15

River

15

Spring

15

Stream

15

Property Line

3

Table 8.2.1.6.B. Minimum Clearances for Distribution Piping Forming Part of Sentence 8.2.1.6.(2)

Column 1

Column 2

Object

Minimum Clearance, m

Structure

5

Well with a watertight casing to a depth of 6 m

15

Any other well

30

Lake

15

Pond

15

Reservoir

15

River

15

Spring not used as a source of potable water

15

Stream

15

Property Line

3

Table 8.2.1.6.C. Minimum Clearances for Holding Tanks Forming Part of Sentence 8.2.1.6.(3)

Column 1

Column 2

Object

Minimum Clearance, m

Structure

1.5

Well with a watertight casing to a depth of at least 6 m

15

Any other well

15

Spring

15

Property Line

3