8.2.1.6. — Clearances for a Class 4 or 5 Sewage System

(1) Except as provided in Sentences 8.2.1.4.(1) and (2), a treatment unit shall not be located closer than the minimum horizontal distances as set out in Table 8.2.1.6.A.

(2) Except as provided in Sentences 8.2.1.4.(1) and (2), a distribution pipe shall not be located closer than the minimum horizontal distances set out in Table 8.2.1.6.B. and these distances shall be increased when required by Sentence 8.7.4.2.(11).

(3) Except as provided in Sentences 8.2.1.4.(1) and (2), a holding tank shall not be located closer than the minimum horizontal distances set out in Table 8.2.1.6.C.

Text · e-Laws consolidated snapshot

Table 8.2.1.6.A. Minimum Clearances for Treatment Units Forming Part of Sentence 8.2.1.6.(1)

Column 1

Column 2

Object

Minimum Clearance, m

Structure

1.5

Well

15

Lake

15

Pond

15

Reservoir

15

River

15

Spring

15

Stream

15

Property Line

3

Table 8.2.1.6.B. Minimum Clearances for Distribution Piping Forming Part of Sentence 8.2.1.6.(2)

Column 1

Column 2

Object

Minimum Clearance, m

Structure

5

Well with a watertight casing to a depth of 6 m

15

Any other well

30

Lake

15

Pond

15

Reservoir

15

River

15

Spring not used as a source of potable water

15

Stream

15

Property Line

3

Table 8.2.1.6.C. Minimum Clearances for Holding Tanks Forming Part of Sentence 8.2.1.6.(3)

Column 1

Column 2

Object

Minimum Clearance, m

Structure

1.5

Well with a watertight casing to a depth of at least 6 m

15

Any other well

15

Spring

15

Property Line

3