7.6.4.2.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 7.6.4.2. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

O. Reg. 503/09, cl. 114 · ext v1 →

In force 2011-01-01

Next: O. Reg. 503/09, cl. 114 · ext (not in force until 2011-01-01) v1 →

OBC 2012 · continues as 7.6.4.2. — Pro

7.6.4.2. — Plumbing Fixtures

(1) Water closets and urinals shall be certified to CAN/CSA-B45.0, “General Requirements for Plumbing Fixtures”.

(2) The flush cycle for each fixture that is a water closet or urinal and that is installed as a replacement for a fixture in a building that existed before the 1st day of January 1996 shall not exceed the maximum flush cycle listed for that fixture in Table 7.6.4.2.A.

(3) Except as provided in Sentence (2) the flush cycle for each fixture that is a water closet or urinal shall not exceed the maximum flush cycle listed for that fixture in Table 7.6.4.2.B.

(4) Sentences (2) and (3) do not apply to a fixture located in a heritage building, care or detention occupancy or passenger station.

Editor's note

In the notes to Table-7.6.4.2.A., Table-7.6.4.2.B., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 7.6.4.2.A. Maximum Flush Cycles for Sanitary Fixtures Forming Part of Sentences 7.6.4.2.(2)

Column 1

Column 2

Fixture

litres

Water Closet (Tank Type)

13.25

Water Closet (Direct Flush)

13.25

Urinal (Tank Type)

5.68(1)

Urinal (Direct Flush)

5.68(1)

Notes to Table 7.6.4.2.A.:

(1)Urinals equipped with automatic flushing devices shall be controlled to prevent unnecessary flush cycles during building down time.

Table 7.6.4.2.B. Maximum Flush Cycles for Sanitary Fixtures Forming Part of Sentence 7.6.4.2.(3)

Column 1

Column 2

Fixture

litres

Water Closet (Tank Type)

6

Water Closet (Direct Flush)

6

Urinal (Tank Type)

3.8(1)

Urinal (Direct Flush)

3.8(1)

Notes to Table 7.6.4.2.B.:

(1)Urinals equipped with automatic flushing devices shall be controlled to prevent unnecessary flush cycles during building down time.