OBC 2006 › Division B
7.4.10.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 7.4.10.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 7.4.10.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 7.4.10. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 7.4.10. — Pro
7.4.10. — Hydraulic Loads
Content not available for this version.
7.4.10.1. — Total Load on a Pipe
(1) The hydraulic load on a pipe is the total load from,
(a) every fixture that is connected to the system upstream of the pipe,
(b) every fixture for which provision is made for future connection upstream of the pipe, and
(c) all roofs and paved surfaces that drain into the system upstream of the pipe.
Text · e-Laws consolidated snapshot
7.4.10.2. — Hydraulic Loads for Fixtures
(1) The hydraulic load from a fixture that is listed in Table 7.4.9.3. is the number of fixture units set forth in the Table.
(2) Except as provided in Sentence (1), the hydraulic load from a fixture that is not listed in Table 7.4.9.3. is the number of fixture units set forth in Table 7.4.10.2. for the trap of the size that serves the fixture.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Size of Trap, in. | Hydraulic Load, fixture units |
1 ¼ | 1 |
1 ½ | 2 |
2 | 3 |
2 ½ | 4 |
3 | 5 |
4 | 6 |
7.4.10.3. — Hydraulic Loads from Fixtures with Continuous or Semi-continuous Flow
(1) Except as provided in Sentence (2), the hydraulic load from a fixture that produces a continuous flow, such as a pump or an air-conditioning fixture, is 31.7 fixture units for each litre per second of flow.
(2) Where a fixture or equipment that produces a continuous or semi-continuous flow drains to a storm drainage system, the hydraulic load from the fixture is 900 litres for each litre per second of flow.
(3) The hydraulic load from a fixture or equipment that produces a semi-continuous flow shall conform to Table 7.4.10.3.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 |
Maximum Permitted Flows by Trap Size | ||
Trap Size, in. | Flow, L/s | Hydraulic Load, fixture units |
1 ½ | 0.00 - 0.090 | 3 |
2 | 0.091 - 0.190 | 6 |
3 | 0.191 - 0.850 | 27 |
4 | 0.851 - 5.700 | 180 |
7.4.10.4. — Hydraulic Loads from Roofs or Paved Surfaces
(1) Except as provided in Sentence (2), the hydraulic load in litres from a roof or paved surface is the maximum 15 min rainfall determined in conformance with Supplementary Standard SB-1, multiplied by the sum of,
(a) the area in square metres of the horizontal projection of the surface drained, and
(b) one-half the area in square metres of the largest adjoining vertical surface.
(2) Flow control roof drains may be installed provided,
(a) the maximum drain down time does not exceed 24 h,
(b) the roof structure has been designed to carry the load of the accumulated water,
(c) one or more scuppers are installed so that the maximum depth of water on the roof cannot exceed 150 mm,
(d) they are located not more than 15 m from the edge of the roof and not more than 30 m from adjacent drains, and
(e) there is at least one drain for each 900 m2.
Text · e-Laws consolidated snapshot
7.4.10.5. — Conversion of Fixture Units to Litres and Gal/min
(1) Except as provided in Sentence 7.4.10.3.(2), where the hydraulic load is to be expressed in litres, fixture units shall be converted as follows:
(a) when the number of fixture units is 260 or fewer, the load is 2 360 L, and
(b) when the number of fixture units exceeds 260, the load is 9.1 L for each fixture unit.
(2) Where the hydraulic load is to be expressed in gal/min, fixture units shall be converted in accordance with Table 7.4.10.5.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 |
Fixture Units in Service | Fixture Units | Fixture Units | Fixture Units |
Col. 1 | Col. 1 × 10 | Col. 1 × 100 | |
100 | 53 | 174 | 900 |
90 | 51 | 164 | 835 |
80 | 49 | 153 | 750 |
70 | 47 | 140 | 680 |
60 | 44 | 128 | 600 |
50 | 41 | 115 | 520 |
40 | 38 | 102 | 435 |
30 | 33 | 88 | 350 |
20 | 27 | 72 | 262 |
10 | 21 | 53 | 174 |
7.4.10.6. — Hydraulic Loads to Soil or Waste Pipes
(1) Except as provided in Sentences (2) and (4), the hydraulic load that is drained to every soil or waste stack shall conform to Table 7.4.10.6.A.
(2) Where the norminally horizontal offset in a soil or waste stack is 1 500 mm or more, the hydraulic load that is served by it shall conform to Table 7.4.10.8.
(3) Vertical sanitary drainage pipe shall be designed to carry no more than 29% of its full capacity.
(4) No vertical waste pipe, branch or stack of less than 3 in. diameter shall have a hydraulic load in excess of that permitted by Table 7.4.10.6.B.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 |
Pipe Size, in. | Maximum Hydraulic Load, fixture units | Maximum Fixture Units Drained from any one Storey |
1 ¼ | 2 | 2 |
1 ½ | 8 | 5 |
2 | 24 | 10 |
3 | 102 | 18 |
4 | 540 | 100 |
5 | 1 400 | 250 |
6 | 2 900 | 500 |
8 | 7 600 | 830 |
10 | 15 000 | 2 700 |
12 | 26 000 | 4 680 |
15 | 50 000 | 9 000 |
Column 1 | Column 2 | Column 3 | Column 4 |
Pipe Size, in. | Stack Height | Stack Height | For Each Storey in Stack of |
3 Storeys or less | More than 3 Storeys | more than 3 Storeys | |
1 ¼ | 2 | 2 | 2 |
1 ½ | 8 | 8 | 5 |
2 | 16 | 24 | 10 |
7.4.10.7. — Hydraulic Loads on Branches
(1) No horizontal sanitary drainage pipe of less than 3 in. size shall have a fixture loading in excess of that permitted by Table 7.4.10.7.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Size of Branch, in. | Maximum Load, fixture units |
1 ¼ | 2 |
1 ½ | 4 |
2 | 6 |
7.4.10.8. — Hydraulic Loads on Sanitary Horizontal Drain
(1) Except as permitted by Article 7.4.10.7., the hydraulic load that is drained to a horizontal sanitary drainage pipe shall conform to Table 7.4.10.8., based on the size and slope.
(2) Horizontal sanitary drainage pipe shall be designed to carry no more than 65% of its full capacity.
Editor's note
In the notes to Table-7.4.10.8., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 | Column 6 | Column 7 |
Drain Size, Nominal in. | Maximum Hydraulic Load, fixture units | |||||
Slope(1) | ||||||
1:400 | 1:200 | 1:133 | 1:100 | 1:50 | 1:25 | |
3 | --- | --- | --- | --- | 27 | 36 |
4 | --- | --- | --- | 180 | 240 | 300 |
5 | --- | --- | 380 | 390 | 480 | 670 |
6 | --- | --- | 600 | 700 | 840 | 1300 |
8 | --- | 1400 | 1500 | 1600 | 2250 | 3370 |
10 | --- | 2500 | 2700 | 3000 | 4500 | 6500 |
12 | 2240 | 3900 | 4500 | 5400 | 8300 | 13000 |
15 | 4800 | 7000 | 9300 | 10400 | 16300 | 22500 |
Notes to Table 7.4.10.8.:
(1)Slope is the ratio of rise to run, in whatever measurement units are chosen.
7.4.10.9. — Hydraulic Loads on Horizontal Storm Drains
(1) The hydraulic load that is drained to a horizontal storm drainage pipe shall conform to Table 7.4.10.9., based on the size and slope.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 | Column 6 | Column 7 | Column 8 |
Size of Drain or Sewer, in. | Maximum Hydraulic Load, L | ||||||
Slope(1) | |||||||
1 in 400 | 1 in 200 | 1 in 133 | 1 in 100 | 1 in 68 | 1 in 50 | 1 in 25 | |
3 | ------ | ------ | ------ | ------ | 2 390 | 2 770 | 3 910 |
4 | ------ | ------ | ------ | 4 220 | 5 160 | 5 970 | 8 430 |
5 | ------ | ------ | 6 760 | 7 650 | 9 350 | 10 800 | 15 300 |
6 | ------ | ------ | 10 700 | 12 400 | 15 200 | 17 600 | 24 900 |
8 | ------ | 18 900 | 23 200 | 26 700 | 32 800 | 37 800 | 53 600 |
10 | ------ | 34 300 | 41 900 | 48 500 | 59 400 | 68 600 | 97 000 |
12 | 37 400 | 55 900 | 68 300 | 78 700 | 96 500 | 112 000 | 158 000 |
15 | 71 400 | 101 000 | 124 000 | 143 000 | 175 000 | 202 000 | 287 000 |
Notes to Table 7.4.10.9.:
(1)Slope is the ratio of rise to run, in whatever measurement units are chosen.
7.4.10.10. — Rain Leaders
(1) No change in the size of a rain leader with a nominally horizontal offset is required if the offset,
(a) is located immediately under the roof,
(b) is not more than 6 m long, and
(c) has a slope not less than 1 in 50.
(2) If the horizontal offset is more than 6 m long, the rain leader shall conform to Table 7.4.10.9.v1
(3) The hydraulic load that is drained to a rain leader shall conform to Table 7.4.10.10.
Editor's note
In Table 7.4.10.10., the maximum hydraulic load for a 4 in. size is filed in O. Reg. 350/06 as '1 0800', with the thousands separator misplaced; the intended value is 10 800. This map reproduces the source as filed. The e-Laws consolidation silently corrects the spacing to '10 800'. This correction was not enacted by an amending regulation.
Text · e-Laws consolidated snapshot
| Column 1 | Column 2 |
| Size, in. | Maximum Hydraulic Load, L |
| 2 | 1 700 |
| 2 ½ | 3 070 |
| 3 | 5 000 |
| 4 | 1 0800 |
| 5 | 19 500 |
| 6 | 31 800 |
| 8 | 68 300 |