7.4.10. — Hydraulic Loads

Content not available for this version.

7.4.10.1. — Total Load on a Pipe

(1) The hydraulic load on a pipe is the total load from,

(a) every fixture that is connected to the system upstream of the pipe,

(b) every fixture for which provision is made for future connection upstream of the pipe, and

(c) all roofs and paved surfaces that drain into the system upstream of the pipe.

Text · e-Laws consolidated snapshot

7.4.10.2. — Hydraulic Loads for Fixtures

(1) The hydraulic load from a fixture that is listed in Table 7.4.9.3. is the number of fixture units set forth in the Table.

(2) Except as provided in Sentence (1), the hydraulic load from a fixture that is not listed in Table 7.4.9.3. is the number of fixture units set forth in Table 7.4.10.2. for the trap of the size that serves the fixture.

Text · e-Laws consolidated snapshot

Table 7.4.10.2. Permitted Hydraulic Load from a Fixture Based on Size of Trap Forming Part of Sentence 7.4.10.2.(2)

Column 1

Column 2

Size of Trap, in.

Hydraulic Load, fixture units

1 ¼

1

1 ½

2

2

3

2 ½

4

3

5

4

6

7.4.10.3. — Hydraulic Loads from Fixtures with Continuous or Semi-continuous Flow

(1) Except as provided in Sentence (2), the hydraulic load from a fixture that produces a continuous flow, such as a pump or an air-conditioning fixture, is 31.7 fixture units for each litre per second of flow.

(2) Where a fixture or equipment that produces a continuous or semi-continuous flow drains to a storm drainage system, the hydraulic load from the fixture is 900 litres for each litre per second of flow.

(3) The hydraulic load from a fixture or equipment that produces a semi-continuous flow shall conform to Table 7.4.10.3.

Text · e-Laws consolidated snapshot

Table 7.4.10.3. Maximum Permitted Hydraulic Load from Fixtures with Semi-continuous Flows Forming Part of Sentence 7.4.10.3.(3)

Column 1

Column 2

Column 3

Maximum Permitted Flows by Trap Size

Trap Size, in.

Flow, L/s

Hydraulic Load, fixture units

1 ½

0.00 - 0.090

3

2

0.091 - 0.190

6

3

0.191 - 0.850

27

4

0.851 - 5.700

180

7.4.10.4. — Hydraulic Loads from Roofs or Paved Surfaces

(1) Except as provided in Sentence (2), the hydraulic load in litres from a roof or paved surface is the maximum 15 min rainfall determined in conformance with Supplementary Standard SB-1, multiplied by the sum of,

(a) the area in square metres of the horizontal projection of the surface drained, and

(b) one-half the area in square metres of the largest adjoining vertical surface.

(2) Flow control roof drains may be installed provided,

(a) the maximum drain down time does not exceed 24 h,

(b) the roof structure has been designed to carry the load of the accumulated water,

(c) one or more scuppers are installed so that the maximum depth of water on the roof cannot exceed 150 mm,

(d) they are located not more than 15 m from the edge of the roof and not more than 30 m from adjacent drains, and

(e) there is at least one drain for each 900 m2.

Text · e-Laws consolidated snapshot

7.4.10.5. — Conversion of Fixture Units to Litres and Gal/min

(1) Except as provided in Sentence 7.4.10.3.(2), where the hydraulic load is to be expressed in litres, fixture units shall be converted as follows:

(a) when the number of fixture units is 260 or fewer, the load is 2 360 L, and

(b) when the number of fixture units exceeds 260, the load is 9.1 L for each fixture unit.

(2) Where the hydraulic load is to be expressed in gal/min, fixture units shall be converted in accordance with Table 7.4.10.5.

Text · e-Laws consolidated snapshot

Table 7.4.10.5. Maximum Probable Drainage Rate, gal/min Forming Part of Sentences 7.4.10.3.(1), 7.4.10.5.(2)

Column 1

Column 2

Column 3

Column 4

Fixture Units in Service

Fixture Units

Fixture Units

Fixture Units

Col. 1

Col. 1 × 10

Col. 1 × 100

100

53

174

900

90

51

164

835

80

49

153

750

70

47

140

680

60

44

128

600

50

41

115

520

40

38

102

435

30

33

88

350

20

27

72

262

10

21

53

174

7.4.10.6. — Hydraulic Loads to Soil or Waste Pipes

(1) Except as provided in Sentences (2) and (4), the hydraulic load that is drained to every soil or waste stack shall conform to Table 7.4.10.6.A.

(2) Where the norminally horizontal offset in a soil or waste stack is 1 500 mm or more, the hydraulic load that is served by it shall conform to Table 7.4.10.8.

(3) Vertical sanitary drainage pipe shall be designed to carry no more than 29% of its full capacity.

(4) No vertical waste pipe, branch or stack of less than 3 in. diameter shall have a hydraulic load in excess of that permitted by Table 7.4.10.6.B.

Text · e-Laws consolidated snapshot

Table 7.4.10.6.A. Maximum Permitted Hydraulic Load Drained to Soil-or-Waste Stack Forming Part of Sentence 7.4.10.6.(1)

Column 1

Column 2

Column 3

Pipe Size, in.

Maximum Hydraulic Load, fixture units

Maximum Fixture Units Drained from any one Storey

1 ¼

2

2

1 ½

8

5

2

24

10

3

102

18

4

540

100

5

1 400

250

6

2 900

500

8

7 600

830

10

15 000

2 700

12

26 000

4 680

15

50 000

9 000

Table 7.4.10.6.B. Maximum Load on Vertical Drainage Pipe, Fixture Units Forming Part of Sentence 7.4.10.6.(4)

Column 1

Column 2

Column 3

Column 4

Pipe Size, in.

Stack Height

Stack Height

For Each Storey in Stack of

3 Storeys or less

More than 3 Storeys

more than 3 Storeys

1 ¼

2

2

2

1 ½

8

8

5

2

16

24

10

7.4.10.7. — Hydraulic Loads on Branches

(1) No horizontal sanitary drainage pipe of less than 3 in. size shall have a fixture loading in excess of that permitted by Table 7.4.10.7.

Text · e-Laws consolidated snapshot

Table 7.4.10.7. Maximum Permitted Hydraulic Load Drained to a Branch Forming Part of Sentence 7.4.10.7.(1)

Column 1

Column 2

Size of Branch, in.

Maximum Load, fixture units

1 ¼

2

1 ½

4

2

6

7.4.10.8. — Hydraulic Loads on Sanitary Horizontal Drain

(1) Except as permitted by Article 7.4.10.7., the hydraulic load that is drained to a horizontal sanitary drainage pipe shall conform to Table 7.4.10.8., based on the size and slope.

(2) Horizontal sanitary drainage pipe shall be designed to carry no more than 65% of its full capacity.

Editor's note

In the notes to Table-7.4.10.8., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.

Text · e-Laws consolidated snapshot

Table 7.4.10.8. Maximum Permitted Hydraulic Load Drained to a Horizontal Sanitary Drainage Pipe Forming Part of Sentences 7.4.10.3.(1), 7.4.10.6.(2) and 7.4.10.8.(1)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Drain Size, Nominal in.

Maximum Hydraulic Load, fixture units

Slope(1)

1:400

1:200

1:133

1:100

1:50

1:25

3

---

---

---

---

27

36

4

---

---

---

180

240

300

5

---

---

380

390

480

670

6

---

---

600

700

840

1300

8

---

1400

1500

1600

2250

3370

10

---

2500

2700

3000

4500

6500

12

2240

3900

4500

5400

8300

13000

15

4800

7000

9300

10400

16300

22500

Notes to Table 7.4.10.8.:

(1)Slope is the ratio of rise to run, in whatever measurement units are chosen.

7.4.10.9. — Hydraulic Loads on Horizontal Storm Drains

(1) The hydraulic load that is drained to a horizontal storm drainage pipe shall conform to Table 7.4.10.9., based on the size and slope.

Text · e-Laws consolidated snapshot

Table 7.4.10.9. Minimum Permitted Hydraulic Load Drained to a Horizontal Storm Drainage Pipe Forming Part of Sentences 7.4.10.9.(1) and 7.4.10.10.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8

Size of Drain or Sewer, in.

Maximum Hydraulic Load, L

Slope(1)

1 in 400

1 in 200

1 in 133

1 in 100

1 in 68

1 in 50

1 in 25

3

------

------

------

------

2 390

2 770

3 910

4

------

------

------

4 220

5 160

5 970

8 430

5

------

------

6 760

7 650

9 350

10 800

15 300

6

------

------

10 700

12 400

15 200

17 600

24 900

8

------

18 900

23 200

26 700

32 800

37 800

53 600

10

------

34 300

41 900

48 500

59 400

68 600

97 000

12

37 400

55 900

68 300

78 700

96 500

112 000

158 000

15

71 400

101 000

124 000

143 000

175 000

202 000

287 000

Notes to Table 7.4.10.9.:

(1)Slope is the ratio of rise to run, in whatever measurement units are chosen.

7.4.10.10. — Rain Leaders

(1) No change in the size of a rain leader with a nominally horizontal offset is required if the offset,

(a) is located immediately under the roof,

(b) is not more than 6 m long, and

(c) has a slope not less than 1 in 50.

(2) If the horizontal offset is more than 6 m long, the rain leader shall conform to Table 7.4.10.9.v1

(3) The hydraulic load that is drained to a rain leader shall conform to Table 7.4.10.10.

Editor's note

In Table 7.4.10.10., the maximum hydraulic load for a 4 in. size is filed in O. Reg. 350/06 as '1 0800', with the thousands separator misplaced; the intended value is 10 800. This map reproduces the source as filed. The e-Laws consolidation silently corrects the spacing to '10 800'. This correction was not enacted by an amending regulation.

Text · e-Laws consolidated snapshot

Table 7.4.10.10. Maximum Permitted Hydraulic Load Drained to a Circular Rain Leader Forming Part of Sentence 7.4.10.10.(3)

Column 1

Column 2

Size, in.

Maximum Hydraulic Load, L

2

1 700

2 ½

3 070

3

5 000

4

1 0800

5

19 500

6

31 800

8

68 300