7.4.10.10. — Rain Leaders

(1) No change in the size of a rain leader with a nominally horizontal offset is required if the offset,

(a) is located immediately under the roof,

(b) is not more than 6 m long, and

(c) has a slope not less than 1 in 50.

(2) If the horizontal offset is more than 6 m long, the rain leader shall conform to Table 7.4.10.9.v1

(3) The hydraulic load that is drained to a rain leader shall conform to Table 7.4.10.10.

Editor's note

In Table 7.4.10.10., the maximum hydraulic load for a 4 in. size is filed in O. Reg. 350/06 as '1 0800', with the thousands separator misplaced; the intended value is 10 800. This map reproduces the source as filed. The e-Laws consolidation silently corrects the spacing to '10 800'. This correction was not enacted by an amending regulation.

Text · e-Laws consolidated snapshot

Table 7.4.10.10. Maximum Permitted Hydraulic Load Drained to a Circular Rain Leader Forming Part of Sentence 7.4.10.10.(3)

Column 1

Column 2

Size, in.

Maximum Hydraulic Load, L

2

1 700

2 ½

3 070

3

5 000

4

1 0800

5

19 500

6

31 800

8

68 300