OBC 2006 › Division B
3.2.4.9.
Version 1 — in force 1 April 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.4.9.
- Version
- v1
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.4.9.
- Version
- v1
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.2.4.9. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 205/08, cl. 6 · ext ← current
In force 2010-04-01
OBC 2012 · renumbered to 3.2.4.10. — Pro
3.2.4.9. — Electrical Supervision
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Electrical supervision shall be provided for a fire alarm system.
(2) If a fire alarm system is installed in a building, an automatic sprinkler system shall be electrically supervised to indicate a supervisory signal on the building fire alarm system annunciator for each of the following:
(a) movement of a valve handle that controls the supply of water to sprinklers;
(b) loss of excess water pressure required to prevent false alarms in a wet pipe system;
(c) loss of air pressure in a dry pipe system;
(d) loss of air pressure in a pressure tank;
(e) a significant change in water level in any water storage container used for fire fighting purposes;
(f) loss of power to any automatically starting fire pump, and
(g) a temperature approaching the freezing point in any dry pipe valve enclosure or water storage container used for fire fighting purposes.
v1 O. Reg. 205/08
Later · viewing · 2010-04-01(1) Electrical supervision shall be provided for a fire alarm system.
(2) If a fire alarm system is installed in a building, an automatic sprinkler system shall be electrically supervised to indicate a supervisory signal on the building fire alarm system annunciator for each of the following:
(a) movement of a valve handle that controls the supply of water to sprinklers;
(b) loss of excess water pressure required to prevent false alarms in a wet pipe system;
(c) loss of air pressure in a dry pipe system;
(d) loss of air pressure in a pressure tank;
(e) a significant change in water level in any water storage container used for fire fighting purposes;
(f) loss of power to any automatically starting fire pump, and
(g) a temperature approaching the freezing point in any dry pipe valve enclosure or water storage container used for fire fighting purposes.
(3) In a building regulated by the provisions of Subsection 3.2.6., the indication of a supervisory signal in accordance with Sentence (2) shall be transmitted to a proprietary control centre or to an independent central station.
Provenance
OBC 1997 · continues from 3.2.4.9. — Pro
Base · O. Reg. 350/06 · ext v0 → comparing ×
O. Reg. 205/08, cl. 6 · ext ← current
In force 2010-04-01
OBC 2012 · renumbered to 3.2.4.10. — Pro