3.2.4.10. — Fire Detectors

(1) Fire detectors required by this Article shall be connected to the fire alarm system.

(2) Except as provided in Article 3.2.4.15., if a fire alarm system is required, fire detectors shall be installed in,

(a) storage rooms not within dwelling units,

(b) service rooms not within dwelling units,

(c) janitors’ rooms,

(d) rooms in which hazardous substances are to be used or stored,

(e) elevator and dumbwaiter shafts,

(f) a laundry room in a building of residential occupancy, but not one within a dwelling unit, and

(g) hazardous classrooms and change rooms in elementary and secondary schools.