3.2.8.7. — Sprinklers

(1) In a building containing an interconnected floor space, storeys that are wholly or partially within an interconnected floor space and all storeys below an interconnected floor space shall be sprinklered.

(2) In a building containing an interconnected floor space,

(a) waterflow alarm signals from sprinkler systems shall be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4), and

(b) sprinkler systems shall be electrically supervised as required in Sentence 3.2.4.9.(2)v1.