3.2.4.8. — Annunciator and Zone Indication

(1) Except as permitted in Sentences (3) to (5), an annunciator shall be installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1).

(2) Except as permitted by Sentence (6), the annunciator required by Sentence (1) shall have separate zone indication of the actuation of the alarm initiating devices in each,

(a) floor area so that in a building that is not sprinklered, the area of coverage for each zone is neither more than,

(i) one storey, nor

(ii) 2 000 m2,

(b) floor area so that in a building that is sprinklered, the area of coverage for each zone is neither more than,

(i) one storey, nor

(ii) the system area limits as specified in NFPA 13, “Installation of Sprinkler Systems”,

(c) shaft required to be equipped with smoke detectors,

(d) air handling system required to be equipped with smoke detectors,

(e) contained use area,

(f) impeded egress zone,

(g) fire compartment required in Sentence 3.3.3.5.(2)v1, and

(h) fire compartment required to be separated by vertical fire separations having a fire-resistance rating not less than 2 h, other than dwelling units described in Subsection 3.3.4.

(3) An annunciator need not be provided for a fire alarm system if not more than one zone indicator is required in Sentence (2).

(4) If an annunciator is not installed as part of a fire alarm system in conformance with Sentence (1), a visual and audible trouble signal device shall be provided inside the main entrance of the building.

(5) The requirements in Sentence (1) are waived in a building,

(a) reserved,

(b) that has an aggregate area for all storeys of not more than 2 000 m2, and

(c) that is not more than 3 storeys in building height.

(6) The area limits of Clause (2)(a) are waived for an interior undivided open space used as an arena, a rink or a swimming pool provided that other spaces in the building that are separated from the open space are individually zoned in accordance with the requirements of Sentence (2).

(7) A fire alarm control unit installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1), is deemed to satisfy the requirement for an annunciator provided all indicators required for an annunciator or trouble signal device are included on the control unit.

(8) In a building containing a hotel in which a trouble signal sounding device has a silencing switch, a trouble light shall be installed in,

(a) the main reception area serving the hotel, or

(b) another continually-supervised location.

(9) In a nursing home, a remote audiovisual fire alarm trouble signal shall be located at the main nursing station.

Editor's note

As filed in O. Reg. 350/06, Clause (5)(a) of this article reads 'reserved,' (lower case, ending in a comma that separates it from the following clause). The consolidated e-Laws text renders this clause as 'Reserved' (capitalized, with the comma omitted); this presentation difference was not enacted by any amending regulation, and the as-filed text is retained here.