OBC 2006 › Division B
3.2.4.9.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.4.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.4.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
Provenance
OBC 1997 · continues from 3.2.4.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 205/08, cl. 6 · ext v1 →
In force 2010-04-01
Next: O. Reg. 205/08, cl. 6 · ext (not in force until 2010-04-01) v1 →
OBC 2012 · renumbered to 3.2.4.10. — Pro
3.2.4.9. — Electrical Supervision
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · viewing · 2006-12-31(1) Electrical supervision shall be provided for a fire alarm system.
(2) If a fire alarm system is installed in a building, an automatic sprinkler system shall be electrically supervised to indicate a supervisory signal on the building fire alarm system annunciator for each of the following:
(a) movement of a valve handle that controls the supply of water to sprinklers;
(b) loss of excess water pressure required to prevent false alarms in a wet pipe system;
(c) loss of air pressure in a dry pipe system;
(d) loss of air pressure in a pressure tank;
(e) a significant change in water level in any water storage container used for fire fighting purposes;
(f) loss of power to any automatically starting fire pump, and
(g) a temperature approaching the freezing point in any dry pipe valve enclosure or water storage container used for fire fighting purposes.
v1 O. Reg. 205/08
Later · 2010-04-01(1) Electrical supervision shall be provided for a fire alarm system.
(2) If a fire alarm system is installed in a building, an automatic sprinkler system shall be electrically supervised to indicate a supervisory signal on the building fire alarm system annunciator for each of the following:
(a) movement of a valve handle that controls the supply of water to sprinklers;
(b) loss of excess water pressure required to prevent false alarms in a wet pipe system;
(c) loss of air pressure in a dry pipe system;
(d) loss of air pressure in a pressure tank;
(e) a significant change in water level in any water storage container used for fire fighting purposes;
(f) loss of power to any automatically starting fire pump, and
(g) a temperature approaching the freezing point in any dry pipe valve enclosure or water storage container used for fire fighting purposes.
(3) In a building regulated by the provisions of Subsection 3.2.6., the indication of a supervisory signal in accordance with Sentence (2) shall be transmitted to a proprietary control centre or to an independent central station.