(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.10.3.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.10.3. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 3.10.3. — Pro
3.10.3. — Additional Requirements for Buildings Containing more than 1 Storey
Content not available for this version.
3.10.3.1. — Application
(1) The requirements in this Subsection apply to all buildings except a 1 storey building that does not contain a basement or mezzanine.
Text · e-Laws consolidated snapshot
3.10.3.2. — Spatial Separations
(1) Except as provided in Sentence (2), the requirements in Subsection 3.2.3. shall apply.
(2) The distance between buildings shall be not less than 9 m.
Text · e-Laws consolidated snapshot
3.10.3.3. — Fire Alarm Systems
(1) Except as provided in Sentences (2) and (3), the requirements in Subsection 3.2.4. shall apply.
(2) A fire alarm system shall be installed.
(3) Within the first storey, manual pull stations are required only in corridors.
Text · e-Laws consolidated snapshot
3.10.3.4. — Provisions for Fire Fighting
(1) Except as provided in Sentences (2) to (4), the requirements in Subsection 3.2.5. shall apply.
(2) Access routes for fire department vehicles shall be provided and shall be not less than 9 m wide.
(3) Hydrants shall be located in the access routes required in Sentence (2) so that,
(a) for a building provided with a fire department connection for a standpipe system or a sprinkler system,
(i) a fire department pumper vehicle can be located adjacent to a hydrant, and
(ii) the unobstructed path of travel for the firefighter from the vehicle to the fire department connection is not more than 45 m, and
(b) for a building that is not sprinklered, a fire department pumper vehicle can be located in the access route so that the unobstructed path of travel for the firefighter is not more than,
(i) 45 m from the hydrant to the vehicle, and
(ii) 45 m from the vehicle to every opening in the building.
Editor's note
As filed in O. Reg. 350/06, Subclause (3)(a)(ii) and Clause (3)(b) of this article use the single word 'firefighter'. The consolidated e-Laws text renders it as two words ('fire fighter'); this spelling difference was not enacted by any amending regulation, and the as-filed text is retained here.
3.10.3.5. — Standpipe Systems
(1) Except as provided in Sentence (2), the requirements in Subsection 3.2.9. shall apply.
(2) Hose stations are not required in the first storey.
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · continues from 3.10.3. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 3.10.3. — Pro