3.2.9. — Standpipe Systems

Content not available for this version.

3.2.9.1. — Where Required

(1) Except as provided in Sentences (4) to (7), a standpipe system shall be installed in every building that,

(a) is more than 3 storeys in building height,

(b) is more than 14 m high measured between grade and the ceiling of the top storey, or

(c) is not more than 14 m high measured between grade and the ceiling of the top storey but has a building area exceeding the area shown in Table 3.2.9.1. for the applicable building height if the building is not sprinklered.

(2) A standpipe system shall be installed in every basement of a building that requires a standpipe system above grade.

(3) A standpipe system shall be installed in every basement of a building that is regulated by Sentence 3.2.2.15.(2).

(4) A standpipe system is not required to be installed in the lowest storey in a building if this storey is a service room that has an area not more than 50 m2.

(5) A standpipe system is not required to be installed in a roof-top enclosure if this enclosure has an area not more than 50 m2.

(6) A standpipe system is not required to be installed in a storage garage conforming to Article 3.2.2.83. provided the building is not more than 15 m high.

(7) A standpipe system is not required to be installed in a dwelling unit that,

(a) extends not more than 3 storeys above adjacent ground level,

(b) is completely cut off from the remainder of the building so that there is no access to the remainder of the building, and

(c) has direct access to its interior by means of an exterior doorway located not more than 1 500 mm above or below adjacent finished ground level.

Text · e-Laws consolidated snapshot

Table 3.2.9.1. Building Limits without Standpipe Systems Forming Part of Sentence 3.2.9.1.(1)

Column 1

Column 2

Column 3

Column 4

Occupancy Classification

Building Area, m2

1 Storey

2 Storeys

3 Storeys

A

2 500

2 000

1 500

C

2 000

1 500

1 000

D

4 000

3 000

2 000

F, Division 2

2 000

1 500

1 000

F, Division 3

3 000

2 000

1 000

3.2.9.2. — Standpipe System Design

(1) Except as otherwise provided in this Subsection, if a standpipe system is required, the design, construction, installation and testing of the system shall be in conformance with NFPA 14, “Installation of Standpipe and Hose Systems”.

(2) A dry standpipe that is not connected to a water supply shall not be considered as fulfilling the requirements of this Article.

(3) If more than one standpipe is provided, the total water supply need not be more than 30 L/s.

(4) The residual water pressure at the design flow rate at the hydraulically most remote hose connection of a standpipe system that is required to be installed in a building is permitted to be less than 450 kPa provided that,

(a) the building is sprinklered,

(b) the water supply at the base of the sprinkler riser is capable of meeting the design flow rate and pressure demand of the sprinkler system, including the inside and outside hose allowance, and

(c) fire protection equipment is available to deliver, by means of the fire department connection, the full demand flow rate at a residual water pressure of 450 kPa at the hydraulically most remote hose connection of the standpipe system.

(5) A fire department connection shall be provided for every standpipe system.

(6) Pumps required to have a rated net head pressure greater than 280 kPa and their controllers shall be listed and labelled.

(7) Couplings for hoses or other fittings used in connection with such couplings shall conform to ULC-S513, “Threaded Couplings for 38 mm and 65 mm Fire Hose” or ULC-S543, “Internal Lug Quick Connect Couplings for Fire Hose”.

(8) If freezing of piping may occur, a dry standpipe system may be provided and so arranged through the use of listed devices to,

(a) automatically admit water to the system by opening of a hose valve, and

(b) transmit a signal to an attended location.

(9) A standpipe riser shall be located in,

(a) an exit stair shaft, or

(b) a service space.

Text · e-Laws consolidated snapshot

3.2.9.3. — Hose Connections

(1) If a standpipe system is required in a building, 38 mm diam hose connections shall be provided in each storey in the building.

(2) In addition to the requirements in Sentence (1), if a standpipe system is required, 65 mm diam hose connections shall be installed in each storey in the building if the building,

(a) is more than 25 m high, measured between grade and the ceiling of the top storey, or

(b) has a building area of more than 4 000 m2.

Text · e-Laws consolidated snapshot

3.2.9.4. — Hose Stations

(1) If a standpipe system is required in a building, hose stations shall be provided in each storey in the building.

(2) Each hose station shall be equipped with a hose rack filled with not more than 30 m of 38 mm diam fire hose and the hose rack and fire hose shall be,

(a) listed, or

(b) approved by the Factory Mutual Research Corporation.

(3) Except in a Group F occupancy, at each hose station, hose connections, valves, fire hose, nozzle and hose rack shall be in a hose cabinet.

(4) A hose cabinet referred to in Sentence (3) shall be of sufficient size to,

(a) contain the equipment referred to in Sentence (3),

(b) contain a listed fire extinguisher, and

(c) provide sufficient clearance to permit the use of a standard fire department hose key.

(5) Hose stations shall be located,

(a) so that every portion of the building can be reached by a hose stream and is within 3 m of a nozzle attached to the hose required in Sentence (2),

(b) not more than 5 m from every required exit serving a floor area, except,

(i) for the first storey, or

(ii) if additional hose stations are required to achieve full coverage of the floor area, and

(c) in a conspicuous location where they are not likely to be obstructed.

(6) Except as permitted in Sentence (7), hose stations shall be located so that it is not necessary to penetrate an exit with a hose in order to provide the design coverage required in Clause (5)(a).

(7) A hose is permitted to penetrate an exit in order to provide the required coverage to,

(a) a service room referred to in Sentence 3.2.9.1.(4),

(b) a roof-top enclosure referred to in Sentence 3.2.9.1.(5),

(c) a room not more than 50 m2 in area, or

(d) a room or group of rooms not more than 200 m2 in area in a sprinklered floor area.

(8) A hose station located on one side of a horizontal exit shall be considered to serve only the floor area on that side of the horizontal exit.

(9) A hose cabinet shall be located so that its door, when fully opened, will not obstruct the required width of a means of egress.

(10) A hose station in a Group B, Division 1 major occupancy is permitted to be located in a secure area, or in a lockable cabinet provided that,

(a) identical keys for all cabinets are located at all guard stations, or

(b) electrical remote release devices are provided and are connected to an emergency power supply.

Text · e-Laws consolidated snapshot

3.2.9.5. — Supervisory Signal Annunciation for Valves

(1) If a fire alarm system in a building is required to have an annunciator by Sentence 3.2.4.8.(1), except for hose valves, each valve controlling water supplies in a standpipe system shall be equipped with an electrically supervised switch for transmitting a signal for individual annunciation in the event of movement of the valve handle.

Text · e-Laws consolidated snapshot

3.2.9.6. — Water Supply for 38 mm Hose Connections

(1) If a standpipe and hose system is required, the water supply shall be sufficient to provide a flow, measured at each of the two hydraulically most remote 38 mm diam hose connections,

(a) of not less than 380 L/min,

(b) for not less than 30 min,

(c) at a pressure of not less than 450 kPa, and

(d) of not less than 190 L/min from each of the two outlets simultaneously.

Text · e-Laws consolidated snapshot

3.2.9.7. — Water Supply for 65 mm Hose Connections

(1) If 65 mm diam hose connections are required, the water supply shall be sufficient to provide a flow, measured at each of the two hydraulically most remote 65 mm diam hose connections,

(a) of not less than 1 890 L/min,

(b) for not less than 30 min,

(c) at a pressure of not less than 450 kPa, and

(d) of not less than 945 L/min from each of the two outlets simultaneously.

(2) If the building is less than 84 m high, measured between grade and the ceiling level of the top storey, the water supply required in Sentence (1) is permitted to be supplied through the fire department connection.

(3) If the building is 84 m or more high, measured between grade and the ceiling level of the top storey, the water supply required in Sentence (1) shall be provided by sufficient pumping capacity.

(4) If the building is 84 m or more high, measured between grade and the ceiling level of the top storey, the building shall be served by no fewer than two sources of water supply from a public water system.