3.10.4. — Additional Requirements for 1 Storey Buildings

Content not available for this version.

3.10.4.1. — Application

(1) The requirements in this Subsection apply to 1 storey buildings that do not contain a basement or mezzanine.

Text · e-Laws consolidated snapshot

3.10.4.2. — Building Area

(1) For the purposes of Subsection 3.2.2., building area means,

(a) the building area of each building,

(b) the total of the building areas of all buildings as a group, or

(c) the total of the building areas of any number or group of buildings.

Text · e-Laws consolidated snapshot

3.10.4.3. — Spatial Separations

(1) Except as provided in Sentences (2) to (4), the requirements in Subsection 3.2.3. shall apply.

(2) Where the building area conforms to Clause 3.10.4.2.(1)(b), the limiting distance requirements shall not apply between individual buildings.

(3) Where the building area conforms to Clause 3.10.4.2.(1)(c),

(a) the limiting distance requirements shall apply between each group of buildings, but not between individual buildings within a group, and

(b) the distance between each group of buildings shall be not less than 9 m.

(4) The distance between individual buildings within a group shall be not less than 6 m.

Text · e-Laws consolidated snapshot

3.10.4.4. — Fire Alarm Systems

(1) Except as provided in Sentence (2), the requirements in Subsection 3.2.4. shall not apply.

(2) The requirements for smoke alarms in Article 3.2.4.21. shall apply to a dwelling unit.

Text · e-Laws consolidated snapshot

3.10.4.5. — Provisions for Fire Fighting

(1) Except as provided in Sentences (2) to (7), the requirements in Subsection 3.2.5. shall not apply.

(2) Access routes for fire department vehicles shall be provided and shall be not less than 9 m wide.

(3) Hydrants shall be located in the access routes required in Sentence (2) so that the locations conform to Sentence 3.10.3.4.(3)v1.

(4) The access routes required in Sentence (2) shall conform to the requirements in Sentence 3.2.5.6.(1).

(5) An adequate water supply for fire fighting shall be provided for every building.

(6) Where a sprinkler system is installed, the system shall conform to the requirements in Articles 3.2.5.13., 3.2.5.16. and 3.2.5.18.

(7) Where combustible sprinkler piping is installed, it shall conform to the requirements in Article 3.2.5.14.