9.9.8. — Exits From Floor Areas

Content not available for this version.

9.9.8.1. — Measurement of Travel Distance

(1) Except as provided in Sentences (2) and (3), for the purposes of this Subsection, travel distance means the distance from any point in the floor area to an exit measured along the path of exit travel.

(2) Where a room or suite is separated from the remainder of the floor area by a fire separation having a fire-resistance rating of at least 45 min, or in a sprinklered building, by a fire separation that is not required to have a fire-resistance rating, the travel distance is permitted to be measured from an egress door of the room or suite to the nearest exit.

(3) Where a public corridor is not less than 9 m wide and conforms to Clause 3.4.2.5.(1)(d), the travel distance is permitted to be determined in accordance with that Clause.

Text · e-Laws consolidated snapshot

9.9.8.2. — Number of Required Exits

(1) Except as provided in Sentences (2) and (3) and Subsection 9.9.9., no fewer than 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than,

(a) 40 m in the case of business and personal services occupancies,

(b) 45 m for all occupancies where the floor area is sprinklered, and

(c) 30 m for all other occupancies.

(2) Except as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.

(3) In boarding, lodging or rooming houses,

(a) where sleeping accommodation is provided for not more than 8 persons, a single exit is permitted from each floor area, or

(b) where sleeping accommodation is not provided in the basement, a single exit is permitted from the basement floor area.

Text · e-Laws consolidated snapshot

9.9.8.3. — Contribution of Each Exit

(1) Where more than 1 exit is required from a floor area, each exit shall be considered as contributing not more than half the required exit width.

Text · e-Laws consolidated snapshot

9.9.8.4. — Location of Exits

(1) Where more than 1 exit is required from a floor area, no fewer than 2 exits shall be independent of each other and be placed remote from each other along the path of travel between them.

Text · e-Laws consolidated snapshot

9.9.8.5. — Exiting through a Lobby

(1) Not more than one exit from a floor area is permitted to lead through a lobby.

(2) The floor of the lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the lobby to the outdoors shall not exceed 15 m.

(3) The lobby referred to in Sentence (1) shall conform in all respects with the requirements for exits, except that rooms other than service rooms, storage rooms and rooms of residential or industrial occupancy are permitted to open directly onto such lobby.

(4) Except as required in Sentence (6), an exit is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space other than as described in Sentence 3.2.8.2.(6)v1v2.

(5) Passenger elevator entrances are permitted to open onto the lobby referred to in Sentence (1) provided the elevator doors are designed to remain closed except while loading and unloading.

(6) An exit that serves a hotel is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space.

(7) Where the lobby referred to in Sentence (1) and adjacent occupancies that are permitted to open into the lobby are sprinklered, the fire separation between such occupancies and the lobby need not have a fire-resistance rating.

Text · e-Laws consolidated snapshot

9.9.8.6. — Mezzanine Means of Egress

(1) Except as permitted by Sentences (2) and (3), the space above a mezzanine shall be served by no fewer than 2 means of egress leading to exits accessible at the mezzanine level on the same basis as floor areas.

(2) One means of egress from a mezzanine is permitted where,

(a) the mezzanine is not required to terminate at a vertical fire separation, as permitted by Sentence 9.10.12.1.(2),

(b) the occupant load of the mezzanine is not more than 60,

(c) the area of the mezzanine does not exceed the area limits of Clause 9.9.7.4.(1)(a), and

(d) the distance limits of Clause 9.9.7.4.(1)(b) measured along the path of travel, are not exceeded from any point on the mezzanine to,

(i) an egress door serving the space that the mezzanine overlooks if the space is served by a single egress door, or

(ii) an egress stairway leading to an access to exit in the space below if that space is required to be served by two or more egress doorways in conformance with Sentence 9.9.7.4.(1).

(3) One of the means of egress from a mezzanine that is not required to terminate at a fire separation as permitted by Sentence 9.10.12.1.(2) and that exceeds the limits of Sentence (2), is permitted to lead through the room in which the mezzanine is located provided all other means of egress from that mezzanine lead to exits accessible at the mezzanine level.

(4) Except as provided in Sentence (2), the maximum travel distance from any point on a mezzanine to the nearest exit shall be not more than,

(a) 40 m in a business and personal services occupancy,

(b) 45 m in a floor area that is sprinklered provided it does not contain a high hazard industrial occupancy, or

(c) 30 m in any floor area not referred to in Clauses (a) or (b).