9.9.7.4. — Number and Spacing of Egress Doors

(1) Except for dwelling units, at least 2 egress doors shall be provided where,

(a) the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or

(b) the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m.

(2) Doors in Sentence (1) shall be spaced so that in the event one door is made inaccessible by a fire within such a room or suite, the other door will provide safe egress.