9.6.7. — Thermal Breaks

Content not available for this version.

9.6.7.1. — Application

(1) This Subsection applies to doors and sidelights separating heated space from unheated space or the exterior.

Text · e-Laws consolidated snapshot

9.6.7.2. — Required Thermal Breaks

(1) Except as provided in Sentence (2), metal frames for doors, for glazing in doors, and for sidelights for doors shall incorporate a thermal break.

(2) Thermal breaks need not be installed in accordance with Sentence (1) where the doors are,

(a) garage doors,

(b) storm doors, or

(c) doors that are required to have a fire-resistance rating.