OBC 2006 Division B

9.5.2.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 9.5.2. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 9.5.2. — Pro

9.5.2. — Barrier-Free Design

Content not available for this version.

9.5.2.1. — General

(1) Except as provided in Sentence (2) and Article 3.8.1.1., every building shall be designed in conformance with Section 3.8.

(2) The requirements of Section 3.8. need not be provided for houses including semi-detached houses, duplexes, triplexes, town houses, row houses and boarding, or rooming houses with fewer than 8 boarders or roomers.

Text · e-Laws consolidated snapshot

9.5.2.2. — Protection on Floor Areas with a Barrier-Free Path of Travel

(1) Where a barrier-free path of travel required in Article 9.5.2.1. is provided to any storey above the first storey, the requirements in Article 3.3.1.7.v1 shall apply.

Text · e-Laws consolidated snapshot

9.5.2.3. — Stud Wall Reinforcement

(1) If wood wall studs or sheet steel wall studs enclose the main bathroom in a dwelling unit, reinforcement shall be installed to permit the future installation of a grab bar on a wall adjacent to,

(a) a water closet in the location required by Clause 3.8.3.8.(1)(d)v1, and

(b) a shower or bathtub in the location required by Clause 3.8.3.13.(1)(f).

Text · e-Laws consolidated snapshot