3.8.3.8. — Water Closet Stalls

(1) Where a washroom is required by Article 3.8.2.3. to barrier-free, at least 1 water closet stall or enclosure shall,

(a) be at least 1 500 mm in width by 1 500 mm in depth,

(b) be equipped with a door that shall,

(i) be capable of being latched from the inside with a mechanism that is operable by one hand,

(ii) provide, when the door is in an open position, a clear opening of at least 810 mm,

(iii) swing outward, unless 760 mm by 1 220 mm clear floor area is provided within the stall or enclosure to permit the door to be closed without interfering with the wheelchair,

(iv) be provided with spring-type or gravity hinges so that the door closes automatically,

(v) be provided with a door pull on the outside, near the latch side of the door, and

(vi) be aligned with the clear manoeuvring space adjacent to the water closet,

(c) have a water closet located so that its centreline is not less than 460 mm and not more than 480 mm from an adjacent side wall on one side,

(d) be equipped with grab bars that shall,

(i) be at least 760 mm in length and mounted at a 30° to 50° angle sloping upwards, away from the water closet with the lower end of the bar mounted 750 mm to 900 mm above the floor and 50 mm in front of the toilet bowl, or alternatively, be L-shaped with 760 mm long horizontal and vertical components mounted with the horizontal component 750 mm to 900 mm above the floor and the vertical component 150 mm in front of the toilet bowl,

(ii) be at least 600 mm in length mounted horizontally on the wall behind the water closet from 840 mm to 920 mm above the floor and, where the water closet has a water tank, be mounted 150 mm above the tank,

(iii) reserved,

(iv) be installed to resist a load of at least 1.3 kN applied vertically or horizontally,

(v) be not less than 30 mm and not more than 40 mm in diameter,

(vi) have a clearance of 30 mm to 40 mm from the wall, and

(vii) have a slip resistant surface,

(e) be equipped with a coat hook mounted not more than 1 200 mm above the floor on a side wall and projecting not more than 50 mm from the wall,

(f) have a clearance of at least 1 700 mm between the outside of the stall face and the face of an in-swinging washroom door and 1 400 mm between the outside of the stall face and any wall-mounted fixture or other obstruction, and

(g) when a toilet paper dispenser is provided, provide a dispenser that is,

(i) wall mounted,

(ii) located below the grab bar,

(iii) in line with or not more than 300 mm in front of the toilet seat, and

(iv) not less than 600 mm above the floor.