OBC 2006 › Division B
9.32.3.9.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.32.3.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.32.3.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.32.3.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.32.3.9. — Pro
9.32.3.9. — Fan Ratings
(1) Except as provided in Sentence (4), capacity ratings for required fans shall be determined in accordance with,
(a) CAN/CSA-C260-M, “Rating the Performance of Residential Mechanical Ventilating Equipment”, or
(b) HVI 916, “Airflow Test Procedure”.
(2) Sound ratings for required fans shall be determined in accordance with,
(a) CAN/CSA-C260-M, “Rating the Performance of Residential Mechanical Ventilating Equipment”, or
(b) HVI 915, “Procedure for Loudness Rating of Residential Fan Products”.
(3) Capacity ratings for required fans shall be based on a static pressure differential of 50 Pa, 25 Pa or 7.5 Pa depending on whether the fan is installed with ductwork connected on both sides, one side or neither side, respectively.
(4) Except for heat recovery ventilators, exhaust fans required to make up any part of the total ventilation capacity required by Article 9.32.3.3.v1 shall have a sound rating not greater than that specified in Table 9.32.3.9.
(5) Required fans shall be installed according to the manufacturer's instructions.
(6) Mechanical ventilation devices shall conform to CSA C22.2 No. 113-M, “Fans and Ventilators”.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 |
Fan Application | Maximum Sound Rating, sones | |
Rated according to CAN/CSA-C260-M | Rated according to HVI 915 | |
Principal exhaust fan | 2.0 | 2.5 |
Supplemental exhaust fans installed in bathrooms and water closet rooms and their make-up air fans | 2.5 | 3.5 |
Supplemental exhaust fans installed in kitchens and their make-up air fans | no rating required | no rating required |