OBC 2006 › Division B
9.32.3.3.
Version 1 — in force 1 January 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.32.3.3.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.32.3.3.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.32.3.3. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 188 · ext ← current
In force 2010-01-01
OBC 2012 · continues as 9.32.3.3. — Pro
9.32.3.3. — Total Ventilation Capacity
(1) The minimum total ventilation capacity of the ventilation system required in Clause 9.32.3.2.(1)(b) shall be the greater of,
(a) the sum of the individual room capacities given in Table 9.32.3.3., or
(b) 0.3 air changes per hour based on the conditioned volume of the dwelling unit.
Editor's note
In the notes to Table-9.32.3.3., the footnote reference numbers are presented inline with a separating space; the e-Laws consolidation renders them as superscript abutting the text. The footnote text is identical.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Room | Capacity, L/s |
Master bedroom(1) | 10 |
Other bedrooms | 5 |
Living room(2) | 5 |
Dining room(2) | 5 |
Kitchen | 5 |
Family room(2) | 5 |
Recreation room | 5 |
Basement(3) | 10 |
Other habitable rooms(4) | 5 |
Bathroom or water closet room | 5 |
Laundry room | 5 |
Utility room | 5 |
Notes to Table 9.32.3.3.:
(1)At least one bedroom in each dwelling unit shall be designated as the master bedroom.
(2)Ventilation capacities assigned to any combined living/dining or family/dining space shall be determined as if the spaces were individual rooms.
(3)Where a basement incorporates rooms of the types designated in this Table, the assigned ventilation capacities for each room shall be as specified for those types of rooms. Basement areas used for other purposes that exceed ⅔ of the total basement floor area shall be assigned a fan capacity of 10 L/s. Those that are less than ⅔ of the total floor area shall be assigned 5 L/s.
(4)Other habitable rooms shall be assigned a ventilation capacity of 5 L/s. This does not include spaces intended solely for access, egress, storage or service equipment.