9.32.3.10. — Ducts

(1) Ventilation ducts shall conform to the requirements of Part 6 for supply ducts except that exhaust ducts that serve only a bathroom or water closet room may be of combustible material provided the duct is reasonably airtight and constructed of a material impervious to water.

(2) Exhaust ducts shall not discharge into heated or unheated enclosed spaces.

(3) Where an exhaust duct passes through or is adjacent to unheated space, the duct shall be insulated to not less than RSI 0.5.

(4) Where a supply duct carrying outdoor air that is not tempered or not mixed with indoor air passes through heated space, it shall be insulated to not less than RSI 0.5 except that, where such a duct is exposed in the heated space for more than 3 m of length in the heated space, it shall be insulated to not less than the values listed in Table 9.32.3.10.A.

(5) A kitchen exhaust duct not equipped with a filter at the inlet end shall be designed and installed so that the entire duct can be cleaned.

(6) Ductwork for range hoods and range-top fans shall be of noncombustible, corrosion-resistant material and shall lead directly to the outdoors without connection to other exhaust fans or ducts.

(7) Ductwork for range hoods and range-top fans shall be equipped with a grease filter at the intake.

(8) All ductwork shall be permanently supported or clipped to prevent sagging, excessive movement and vibration.

(9) All ducting connected to supply and exhaust fans shall be constructed so as to inhibit air leakage at joints.

(10) Where rectangular duct is used in place of round duct, it shall be selected according to Table 9.32.3.10.B.

Editor's note

This map follows the as-filed text of O. Reg. 350/06, whose member dimensions in the tables under Article 9.32.3.10. use the letter 'x' (e.g. '82 x 250'). The e-Laws consolidation editorially substitutes the multiplication sign '×'; no amending regulation makes this change.

Text · e-Laws consolidated snapshot

Table 9.32.3.10.A. Insulation of Fresh Air Supply Ducts Forming Part of Sentence 9.32.3.10.(4)

Column 1

Column 2

Outside Winter Design Temperature as per Supplementary Standard SB-1(1), °C

Minimum Thermal Resistance, RSI

–7 to –11

0.5

–12 to –17

0.9

–18 to –24

1.2

–25 to –29

1.4

–30 to –34

1.8

–35 and colder

2.1

Notes to Table 9.32.3.10.A:

(1) The outside winter design temperatures shall be those listed for the January 2.5 percent values.

Table 9.32.3.10.B. Equivalent Duct Sizes Forming Part of Sentence 9.32.3.10.(10)

Column 1

Column 2

Column 3

Column 4

Column 5

Required Round Duct Size, mm

Permitted Equivalent Rectangular Duct Size, mm

Stack Duct

100 mm Depth

125 mm Depth

150 mm Depth

75

82 × 250

57 × 100

100

82 × 250

89 × 100

75 × 125

75 × 150

125

82 × 250

125 × 100

100 × 125

89 × 150

150

82 × 300

200 × 100

150 × 125

125 × 150

175

82 × 350

275 × 100

200 × 125

175 × 150

More than 175

Part 6 design

Part 6 design

Part 6 design

Part 6 design