9.32.3.3. — Total Ventilation Capacity

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · viewing · 2006-12-31

(1) The minimum total ventilation capacity of the ventilation system required in Clauses 9.32.3.2.(1)(b) shall be the sum of the individual room capacities given in Table 9.32.3.3.

v1 O. Reg. 503/09

Later · 2010-01-01

(1) The minimum total ventilation capacity of the ventilation system required in Clause 9.32.3.2.(1)(b) shall be the greater of,

(a) the sum of the individual room capacities given in Table 9.32.3.3., or

(b) 0.3 air changes per hour based on the conditioned volume of the dwelling unit.