(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.15.4.5.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 159(3) · ext v1 →
In force 2010-01-01
Next: O. Reg. 503/09, cl. 159(3) · ext (not in force until 2010-01-01) v1 →
OBC 2012 · continues as 9.15.4.5. — Pro
9.15.4.5. — Reinforcement for Flat Insulating Concrete Form Foundation Walls
(1) Horizontal reinforcement in flat insulating concrete form foundation walls shall,
(a) consist of,
(i) one 10M bar placed not more than 300 mm from the top of the wall, and
(ii) 10M bars spaced not more than 600 mm o.c., and
(b) be located,
(i) in the inside half of the wall section, and
(ii) with a minimum cover of 30 mm from the inside face of the concrete.
(2) Vertical wall reinforcement in flat insulating concrete form foundation walls shall,
(a) conform to,
(i) Table 9.15.4.5.A. for 140 mm walls,
(ii) Table 9.15.4.5.B. for 190 mm walls, and
(iii) Table 9.15.4.5.C. for 240 mm walls,
(b) be located in the inside half of the wall section with a minimum cover of 30 mm from the inside face of the concrete wall, and
(c) where interrupted by wall openings, be placed not more than 600 mm from each side of the openings.
(3) Cold joints in flat insulating concrete form foundation walls shall be reinforced with at least one 15M bar spaced not more than 600 mm o.c. and embedded not less than 300 mm on both sides of the joint.
(4) Reinforcing around openings in flat insulating concrete form foundation walls shall comply with Articles 9.20.17.3.v1v2 or 9.20.17.4.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 |
Maximum Height of Finished Ground Above Finished Basement Floor, m | Maximum Vertical Reinforcement | ||
Maximum Unsupported Basement Wall Height | |||
2.44 m | 2.75 m | 3.00 m | |
1.35 | 10M at 400 mm o.c. | 10M at 400 mm o.c. | 10M at 400 mm o.c. |
1.60 | 10M at 400 mm o.c. | 10M at 380 mm o.c. | 10M at 380 mm o.c. |
2.00 | 10M at 380 mm o.c. | 10M at 380 mm o.c. | 10M at 380 mm o.c. |
2.20 | 10M at 250 mm o.c. | 10M at 250 mm o.c. | 10M at 250 mm o.c. |
2.35 | n/a | 10M at 250 mm o.c. | 10M at 250 mm o.c. |
2.60 | n/a | 10M at 250 mm o.c. | 10M at 250 mm o.c. |
3.00 | n/a | n/a | 15M at 250 mm o.c. |
Column 1 | Column 2 | Column 3 | Column 4 |
Maximum Height of Finished Ground Above Finished Basement Floor, m | Maximum Vertical Reinforcement | ||
Maximum Unsupported Basement Wall Height | |||
2.44 m | 2.75 m | 3.00 m | |
2.20 | none required | 10M at 400 mm o.c. | 10M at 400 mm o.c. |
2.35 | n/a | 10M at 300 mm o.c. | 10M at 300 mm o.c. |
2.60 | n/a | 10M at 300 mm o.c. | 15M at 400 mm o.c. |
3.00 | n/a | n/a | 15M at 400 mm o.c. |
Column 1 | Column 2 | Column 3 | Column 4 |
Maximum Height of Finished Ground Above Finished Basement Floor, m | Maximum Vertical Reinforcement | ||
Maximum Unsupported Basement Wall Height | |||
2.44 m | 2.75 m | 3.00 m | |
2.20 | none required | none required | none required |
2.60 | n/a | 15M at 400 mm o.c. | 15M at 400 mm o.c. |
3.00 | n/a | n/a | 15M at 400 mm o.c. |
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 159(3) · ext v1 →
In force 2010-01-01 compare
Next: O. Reg. 503/09, cl. 159(3) · ext (not in force until 2010-01-01) v1 →
OBC 2012 · continues as 9.15.4.5. — Pro