OBC 2006 › Division B
9.10.8.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.8.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.8.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.10.8. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.10.8. — Pro
9.10.8. — Fire-Resistance and Combustibility in Relation to Occupancy, Height and Supported Elements
Content not available for this version.
9.10.8.1. — Fire-Resistance Ratings for Floors and Roofs
(1) Except as otherwise provided in this Subsection, the fire-resistance ratings of floors and roofs shall conform to Table 9.10.8.1.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 |
Major Occupancy | Maximum Building Height, Storeys | Minimum Fire-Resistance Rating by Building Element, min | ||
Floors Except Floors over Crawl Spaces | Mezzanine Floors | Roofs | ||
Residential (Group C) | 3 | 45 | 45 | — |
All other occupancies | 2 | 45 | — | — |
3 | 45 | 45 | 45 | |
9.10.8.2. — Fire-Resistance Ratings in Sprinklered Buildings
(1) Except for roofs that support an occupancy, the requirements in Table 9.10.8.1. for roof assemblies to have a fire-resistance rating are permitted to be waived in sprinklered buildings where,
(a) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.9.(2)v1, and
(b) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4).
Text · e-Laws consolidated snapshot
9.10.8.3. — Fire-Resistance Ratings for Walls, Columns and Arches
(1) Except as otherwise provided in this Subsection, all loadbearing walls, columns and arches in the storey immediately below a floor or roof assembly shall have a fire-resistance rating of not less than that required for the supported floor or roof assembly.
Text · e-Laws consolidated snapshot
9.10.8.4. — Reserved.
Content not available for this version.
Editor's note
As filed in O. Reg. 350/06, the heading of this article reads 'Reserved.' with a closing period. The consolidated e-Laws text renders it without the period ('Reserved'); the as-filed heading is retained here.
9.10.8.5. — Service Rooms
(1) Construction supporting a service room need not conform to Article 9.10.8.3.
Text · e-Laws consolidated snapshot
9.10.8.6. — Mezzanines
(1) Mezzanines required to be counted as storeys in Articles 9.10.4.1. and 9.10.4.2. shall be constructed in conformance with the requirements for “Floors Except Floors over Crawl Spaces” in Table 9.10.8.1.
Text · e-Laws consolidated snapshot
9.10.8.7. — Roofs Supporting an Occupancy
(1) Where a portion of a roof supports an occupancy, that portion shall be constructed as a fire separation having a fire-resistance rating conforming to the rating for “Floors Except Floors over Crawl Spaces” in Table 9.10.8.1.
Text · e-Laws consolidated snapshot
9.10.8.8. — Floors of Exterior Passageways
(1) Except as provided in Sentences (2) and (3), the floor assembly of every exterior passageway used as part of a means of egress shall have a fire-resistance rating of not less than 45 min or be of noncombustible construction.
(2) No fire-resistance rating is required for floors of exterior passageways serving buildings of Group D, E or F major occupancy that are not more than 2 storeys in building height.
(3) No fire-resistance rating is required for floors of exterior passageways serving a single dwelling unit where no suite is located above or below the dwelling unit.
Text · e-Laws consolidated snapshot
9.10.8.9. — Crawl Spaces
(1) Where a crawl space exceeds 1 800 mm in height or is used for any occupancy or as a plenum in combustible construction or for the passage of flue pipes, it shall be considered as a basement in applying the requirements in Article 9.10.8.1.
Text · e-Laws consolidated snapshot
9.10.8.10. — Application to Houses
(1) Table 9.10.8.1. does not apply to a dwelling unit that has no other dwelling unit above or below it or to a dwelling unit that is not above or below another major occupancy.
Text · e-Laws consolidated snapshot
9.10.8.11. — Part 3 as an Alternative
(1) The fire-resistance ratings of floors, roofs, loadbearing walls, columns and arches need not conform to this Subsection if such assemblies conform in all respects to the appropriate requirements in Section 3.2.
Text · e-Laws consolidated snapshot