3.3.4.4.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.4.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
(5) Sections 23, 26 and 31, subsection 32 (2), sections 36, 40, 45, 46 and 48 and subsection 214 (2) come into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(5)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.4.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
(5) Sections 23, 26 and 31, subsection 32 (2), sections 36, 40, 45, 46 and 48 and subsection 214 (2) come into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(5)
Provenance
OBC 1997 · continues from 3.3.4.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 40 · ext v1 →
In force 2010-04-01
Next: O. Reg. 503/09, cl. 40 · ext (not in force until 2010-04-01) v1 →
OBC 2012 · continues as 3.3.4.4. — Pro
3.3.4.4. — Egress from Dwelling Units
(1) Single storey dwelling units in an apartment building need not lead to a public corridor or exterior passageway on the same storey provided the dwelling units are served by private stairways leading directly to a public access to exit on the storey,
(a) immediately above, and
(b) immediately below.
(2) Except as permitted by Sentences (3) to (5), a dwelling unit containing more than one storey shall have an exit door or an egress door opening directly into a public access to exit from the uppermost storey and from the lowest storey of the dwelling unit so that each storey is served by an exit or egress door located not more than 1 500 mm above or below its floor level.
(3) A single exit is permitted from a dwelling unit provided the exit is an exterior doorway not more than 1 500 mm above adjacent ground level and,
(a) it is not necessary to travel up or down more than one storey to reach the exit door, or
(b) the uppermost floor level opens to a balcony not more than 6 m above adjacent ground level.
(4) An egress door from either the uppermost storey or the lowest storey in a dwelling unit, as required in Sentence (2), need not be provided,
(a) if that storey is served by a stairway that,
(i) leads to a public access to exit,
(ii) has no direct access to any other storey in the dwelling unit, and
(iii) is separated from the other storeys in the dwelling unit by a fire separation having a fire-resistance rating of not less than 45 min,
(b) if the dwelling unit has not more than 2 storeys above the first storey of the building, or
(c) if it is not necessary to travel either more than 18 m, or more than 1 storey up or down to reach the egress door.
(5) An egress door from either the uppermost storey or the lowest storey in a dwelling unit, as required in Sentence (2), need not be provided,
(a) on the uppermost storey of a dwelling unit having not more than 2 storeys above the first storey of the building,
(b) on each storey from which it is not necessary to travel either more than 18 m or more than 1 storey up or down within the dwelling unit to reach an egress door, or
(c) where that storey is,
(i) provided with a balcony conforming to Sentence (8),
(ii) not more than 2 storeys above or below the dwelling unit egress door, and
(iii) in a building that is not more than 6 storeys in building height.
(6) In a building of residential occupancy not more than 3 storeys in building height, a doorway from a dwelling unit is permitted to open directly into an exit stairway provided the dwelling unit has a second and separate means of egress.
(7) If a dwelling unit has a second and separate means of egress, one means of egress from a dwelling unit is permitted to pass through,
(a) an interior corridor served by a single exit,
(b) an exterior balcony served by a single exit stairway, or
(c) an exterior passageway served by a single exit stairway.
(8) Where a balcony is provided to meet the requirements of Sentence (3) or (5), the balcony shall have,
(a) a solid floor having a fire-resistance rating not less than that required for a floor assembly between suites, and
(b) an area providing not less than 1.5 m2 per suite occupant, based on occupant load, and a minimum dimension of 1 200 mm.
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · continues from 3.3.4.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 40 · ext v1 →
In force 2010-04-01 compare
Next: O. Reg. 503/09, cl. 40 · ext (not in force until 2010-04-01) v1 →
OBC 2012 · continues as 3.3.4.4. — Pro