3.3.1.5. — Egress Doorways

(1) Except for dwelling units, a minimum of 2 egress doorways located so that one doorway could provide egress from the room or suite as required by Article 3.3.1.3.v1 if the other doorway becomes inaccessible to the occupants due to a fire that originates in the room or suite, shall be provided for every room and every suite,

(a) whose area is more than 15 m2 and is used for,

(i) a high hazard industrial occupancy, or

(ii) a hazardous room,

(b) intended for an occupant load more than 60,

(c) in a floor area that is not sprinklered if,

(i) the area of a room or suite is more than the value in Table 3.3.1.5.A., or

(ii) the travel distance within the room or suite to the nearest egress doorway, is more than the value in Table 3.3.1.5.A.,

(d) in a floor area that is sprinklered and does not contain a high hazard industrial occupancy if,

(i) the travel distance to an egress doorway is more than 25 m, or

(ii) the area of the room or suite is more than the value in Table 3.3.1.5.B., or

(e) where the area of the room is more than 100 m2 and it is a hazardous classroom in elementary or secondary school.

(2) Except for a mezzanine within a dwelling unit, every mezzanine that is not required to terminate at a vertical fire separation in Article 3.2.8.2.v1v2 shall have 2 egress facilities placed in such a manner that one facility could provide egress from the mezzanine if the other facility becomes inaccessible to the occupants of the mezzanine due to a fire that might originate in the room or suite in which the mezzanine is located,

(a) where the occupancy of the mezzanine, room or suite is classified as Group F, Division 1,

(b) where the mezzanine is intended for an occupant load of more than 60 persons,

(c) in a floor area that is not sprinklered if,

(i) the area of a mezzanine is more than the value in Table 3.3.1.5.A., or

(ii) the travel distance to an egress doorway or an egress facility is more than the value in Table 3.3.1.5.A., or

(d) in a floor area that is sprinklered if,

(i) the travel distance to an egress doorway or an egress facility is more than 25 m, or

(ii) the area of the mezzanine is more than the value in Table 3.3.1.5.B.

(3) For the purpose of Clause (2)(c) and Clause 2(d),

(a) if the room or suite in which the mezzanine is located is permitted to have one egress doorway, the travel distance is measured from any point on the mezzanine to that doorway, or

(b) if the room or suite in which the mezzanine is located is required to have more than one egress doorway, the travel distance is measured from any point on the mezzanine to the nearest egress facility leading from the mezzanine.

(4) Except for a mezzanine which is not considered as a storey in calculating building height in Sentence 3.2.1.1.(4), where the space below a mezzanine is enclosed, an egress facility from the mezzanine shall not lead into the enclosed space.

Editor's note

As filed in O. Reg. 350/06, Sentence (3) of this article reads 'For the purpose of Clause (2)(c) and Clause 2(d),' - the second reference appearing in the malformed form 'Clause 2(d)' as enacted. The consolidated e-Laws text rewrites it as 'Clause (2)(c) and (d)'. The headnotes of Tables 3.3.1.5.A. and 3.3.1.5.B. are also filed in bold with a space following the footnote marker '(1)'; the e-Laws text removes the bold weight and that space. None of these differences was enacted by any amending regulation, and the as-filed text is retained here.

Text · e-Laws consolidated snapshot

Table 3.3.1.5.A. Egress in Floor Area, not Sprinklered Forming Part of Sentence 3.3.1.5.(1)

Column 1

Column 2

Column 3

Occupancy of Room or Suite

Maximum Area of Room or Suite, m2

Maximum Distance to Egress Doorway, m

Group A

150

15

Group C

150(1)

25(1)

Group D

200

25

Group E

200

25

Group F, Division 2

200

25

Group F, Division 3

200

25

Note to Table 3.3.1.5.A.:

(1)See Article 3.3.4.4. for dwelling units.

Table 3.3.1.5.B. Egress in Sprinklered Floor Area Forming Part of Sentence 3.3.1.5.(1)

Column 1

Column 2

Occupancy of Room or Suite

Maximum Area of Room or Suite, m2

Group A

200

Group B, Division 1

100

Group B, Division 2 or 3

sleeping rooms

100

other than sleeping rooms

200

Group C

150(1)

Group D

300

Group E

200

Group F, Division 2

200

Group F, Division 3

300

Note to Table 3.3.1.5.B.:

(1)See Article 3.3.4.4. for dwelling units.