OBC 2006 › Division B
3.3.1.3.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.1.3.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.3.1.3.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
Provenance
OBC 1997 · continues from 3.3.1.3. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 205/08, cl. 8 · ext v1 →
In force 2010-04-01
Next: O. Reg. 205/08, cl. 8 · ext (not in force until 2010-04-01) v1 →
OBC 2012 · continues as 3.3.1.3. — Pro
3.3.1.3. — Means of Egress
(1) Access to exit within floor areas shall conform to Subsections 3.3.2. to 3.3.5., in addition to the requirements of this Subsection.
(2) If a podium, terrace, platform or contained open space is provided, egress requirements shall conform to the appropriate requirements of Sentence 3.3.1.5.(1) for rooms and suites.
(3) Means of egress shall be provided from every roof that is intended for occupancy, and from every podium, terrace, platform or contained open space.
(4) At least two separate means of egress shall be provided from a roof, used or intended for an occupant load more than 60, to stairs designed in conformance with the exit stair requirements of Section 3.4.
(5) A rooftop enclosure shall be provided with an access to exit that leads to an exit,
(a) at the roof level, or
(b) on the storey immediately below the roof.
(6) A rooftop enclosure that is more than 200 m2 in area shall be provided with at least 2 means of egress.
(7) Two points of egress shall be provided for a service space referred to in Sentence 3.2.1.1.(9) if,
(a) the area is more than 200 m2, or
(b) the travel distance measured from any point in the service space to a point of egress is more than 25 m.
(8) Except as permitted by Sentences 3.3.4.4.(6)v1 and (7), each suite in a floor area that contains more than one suite shall have,
(a) an exterior exit doorway, or
(b) a doorway,
(i) into a public corridor, or
(ii) to an exterior passageway.
(9) Except as permitted by this Section and by Sentence 3.4.2.1.(2)v1, at the point where a doorway referred to in Sentence (8) opens onto a public corridor or exterior passageway, it shall be possible to go in opposite directions to each of 2 separate exits.
(10) Means of egress from a roof for personnel servicing roof top equipment or for a below ground service room that is not normally occupied, is permitted to be provided by stairways or fixed ladders.