240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.7.3.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.2.7.3. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 30 · ext ← current
In force 2010-01-01
OBC 2012 · continues as 3.2.7.3. — Pro
3.2.7.3. — Emergency Lighting
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Emergency lighting shall be provided to an average level of illumination not less than 10 lx at floor or tread level in,
(a) exits,
(b) principal routes providing access to exit in an open floor area and in service rooms,
(c) corridors used by the public,
(d) corridors serving patients’ or residents’ sleeping rooms in a Group B, Division 2 or Division 3 occupancy,
(e) corridors serving classrooms,
(f) underground walkways,
(g) public corridors,
(h) floor areas or parts of them where the public may congregate in,
(i) Group A, Division 1 occupancies, or
(ii) Group A, Division 2 and 3 occupancies having an occupant load of 60 or more,
(i) floor areas or parts of them in day care centres where persons are cared for,
(j) food preparation areas in commercial kitchens,
(k) principal routes providing access to exit in a floor area that is not subdivided into rooms or suites of rooms served by corridors in a business and personal services occupancy, a mercantile occupancy or an industrial occupancy, and
(l) internal corridors or aisles serving as principal routes to exits in a business and personal services occupancy, a mercantile occupancy or an industrial occupancy that is subdivided into rooms or suites of rooms, and is not served by a public corridor.
(2) Emergency lighting to provide an average level of illumination of not less than 10 lx at floor or catwalk level shall be included,
(a) in a service space referred to in Sentence 3.2.1.1.(9), and
(b) on a shelf and rack storage system referred to in Sentence 3.16.1.4.(2).
(3) The minimum value of the illumination required by Sentences (1) and (2) shall be not less than 1 lx.
(4) In addition to the requirements of Sentences (1) to (3), the installation of battery-operated emergency lighting in health care facilities shall conform to the appropriate requirements of CSA Z32, “Electrical Safety and Essential Electrical Systems in Health Care Facilities”.
v1 O. Reg. 503/09
Later · viewing · 2010-01-01(1) Emergency lighting shall be provided to an average level of illumination not less than 10 lx at floor or tread level in,
(a) exits,
(b) principal routes providing access to exit in an open floor area and in service rooms,
(c) corridors used by the public,
(d) corridors serving patients’ or residents’ sleeping rooms in a Group B, Division 2 or Division 3 occupancy,
(e) corridors serving classrooms,
(f) underground walkways,
(g) public corridors,
(h) floor areas or parts of them where the public may congregate in,
(i) Group A, Division 1 occupancies, or
(ii) Group A, Division 2 and 3 occupancies having an occupant load of 60 or more,
(i) floor areas or parts of them in day care centres where persons are cared for,
(j) food preparation areas in commercial kitchens,
(k) principal routes providing access to exit in a floor area that is not subdivided into rooms or suites of rooms served by corridors in a business and personal services occupancy, a mercantile occupancy or an industrial occupancy, and
(l) internal corridors or aisles serving as principal routes to exits in a business and personal services occupancy, a mercantile occupancy or an industrial occupancy that is subdivided into rooms or suites of rooms, and is not served by a public corridor.
(2) Emergency lighting to provide an average level of illumination of not less than 10 lx at floor or catwalk level shall be included,
(a) in a service space referred to in Sentence 3.2.1.1.(9), and
(b) on a shelf and rack storage system, in locations described in Sentence 3.16.1.5.(2).
(3) The minimum value of the illumination required by Sentences (1) and (2) shall be not less than 1 lx.
(4) In addition to the requirements of Sentences (1) to (3), the installation of battery-operated emergency lighting in health care facilities shall conform to the appropriate requirements of CSA Z32, “Electrical Safety and Essential Electrical Systems in Health Care Facilities”.