3.2.7.4.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.7.4. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 3.2.7.4. — Pro

3.2.7.4. — Emergency Power for Lighting

(1) An emergency power supply shall be,

(a) provided to maintain the emergency lighting required by this Subsection from a power source such as batteries or generators that will continue to supply power in the event that the regular power supply to the building is interrupted, and

(b) so designed and installed that upon failure of the regular power it will assume the electrical load automatically for a period of,

(i) 2 h for a building within the scope of Subsection 3.2.6.v1,

(ii) 1 h for a building of Group B major occupancy classification that is not within the scope of Subsection 3.2.6.v1, and

(iii) 30 min for a building of any other occupancy.

(2) If self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, “Unit Equipment for Emergency Lighting”.