9.9.6.2. — Clear Opening Height at Doorways

(1) Except as provided in Sentences (2) and (3), the clear opening height of doorways shall be not less than 2 030 mm high at,

(a) exit doors,

(b) doors that open into or are located within a public corridor, and

(c) doors that open into or are located within another facility that provides access to exit from a suite.

(2) The clear opening height under door closers and other devices in doorways described in Sentence (1) shall be not less than 1 980 mm.

(3) Doorways serving a single dwelling unit need not comply with Sentences (1) and (2).