CodeChronicle

OBC 2006 Division B

9.33.4.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 9.33.4. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 9.33.4. — Pro

9.33.4. — Carbon Monoxide Detectors

Content not available for this version.

9.33.4.1. — Application

(1) This Subsection applies to every building that,

(a) contains a residential occupancy, and

(b) contains a fuel-burning appliance or a storage garage.

Text · e-Laws consolidated snapshot

9.33.4.2. — Location of Carbon Monoxide Detectors

(1) Where a fuel-burning appliance is installed in a suite of residential occupancy, a carbon monoxide detector shall be installed adjacent to each sleeping area in the suite.

(2) Where a fuel-burning appliance is installed in a service room that is not in a suite of residential occupancy, a carbon monoxide detector shall be installed,

(a) adjacent to each sleeping area in every suite of residential occupancy that is adjacent to the service room, and

(b) in the service room.

(3) Where a storage garage is located in a building containing a residential occupancy, a carbon monoxide detector shall be installed adjacent to each sleeping area in every suite of residential occupancy that is adjacent to the storage garage.

(4) Where a storage garage serves only the dwelling unit to which it is attached or built in, a carbon monoxide detector shall be installed adjacent to each sleeping area in the dwelling unit.

Text · e-Laws consolidated snapshot

9.33.4.3. — Installation and Conformance to Standards

(1) The carbon monoxide detector required by Article 9.33.4.2. shall,

(a) be permanently connected to an electrical circuit and shall have no disconnect switch between the overcurrent device and the carbon monoxide detector,

(b) be wired so that its activation will activate all carbon monoxide detectors within the suite, where located within a suite of residential occupancy,

(c) be equipped with an alarm that is audible within bedrooms when the intervening doors are closed, where located adjacent to a sleeping area, and

(d) conform to,

(i) CAN/CSA-6.19, “Residential Carbon Monoxide Alarming Devices”, or

(ii) UL 2034, “Single and Multiple Station Carbon Monoxide Alarms”.

Text · e-Laws consolidated snapshot