9.33.3. — Design Temperatures

Content not available for this version.

9.33.3.1. — Indoor Design Temperatures

(1) At the outside design temperature, required heating facilities shall be capable of maintaining an indoor air temperature of not less than,

(a) 22°C in all living spaces,

(b) 22°C in unfinished basements, and

(c) 15°C in heated crawl spaces.

Text · e-Laws consolidated snapshot

9.33.3.2. — Outdoor Design Temperatures

(1) The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be the appropriate values for the Municipality as set out in Supplementary Standard SB-1, using 2.5 per cent design temperature criteria.

Text · e-Laws consolidated snapshot