OBC 2006 › Division B
9.29.5.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.29.5.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.29.5.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.29.5. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.29.5. — Pro
9.29.5. — Gypsum Board Finish (Taped Joints)
Content not available for this version.
9.29.5.1. — Application
(1) The requirements for application of gypsum board in this Subsection apply to the single layer application of gypsum board to wood furring or framing using nails or screws.
(2) Gypsum board applications not described in this Subsection shall conform to CSA A82.31-M, “Gypsum Board Application”.
Text · e-Laws consolidated snapshot
9.29.5.2. — Materials
(1) Gypsum products shall conform to,
(a) CAN/CSA-A82.27-M, “Gypsum Board”,
(b) ASTM C36 / C36M, “Gypsum Wallboard”,
(c) ASTM C37 / C37M, “Gypsum Lath”,
(d) ASTM C442 / C442M, “Gypsum Backing Board, and Gypsum Coreboard, and Gypsum Shaftliner Board”,
(e) ASTM C558 / C588M, “Gypsum Base for Veneer Plaster”,
(f) ASTM C630 / C630M, “Water-Resistant Gypsum Backing Board”,
(g) ASTM C931 / C931M, “Exterior Gypsum Soffit Board”,
(h) ASTM C960 / C960M, “Predecorated Gypsum Board”,
(i) ASTM C1178 / C1178M, “Glass Mat Water-Resistant Gypsum Backing Panel”,
(j) ASTM C1395 / C1395M, “Gypsum Ceiling Board”, or
(k) ASTM C1396 / C1396M, “Gypsum Board”.
Text · e-Laws consolidated snapshot
9.29.5.3. — Maximum Spacing of Supports
(1) Maximum spacing of supports for gypsum board applied as a single layer shall conform to Table 9.29.5.3.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 |
Thickness, mm | Orientation of Board to Framing | Maximum Spacing of Supports, mm o.c. | ||
Walls | Ceilings | |||
Painted Finish | Water-Based Texture Finish | |||
Gypsum board conforming to Clauses 9.29.5.2.(1)(a)v1v2 to (i) and (k) | ||||
9.5 | parallel | — | — | — |
perpendicular | 400 | 400 | — | |
12.7 | parallel | 600 | 400 | — |
perpendicular | 600 | 600 | 400 | |
15.9 | parallel | 600 | 400 | — |
perpendicular | 600 | 600 | 600 | |
Gypsum board conforming to Clause 9.29.5.2.(1)(j)v1v2 | ||||
12.7 | parallel | 600 | 400 | — |
perpendicular | 600 | 600 | 600 | |
9.29.5.4. — Support of Insulation
(1) Gypsum board supporting insulation shall be at least 12.7 mm thick.
Text · e-Laws consolidated snapshot
9.29.5.5. — Length of Fasteners
(1) The length of fasteners for gypsum board shall conform to Table 9.29.5.5., except that lesser depths of penetration are permitted for assemblies required to have a fire-resistance rating provided it can be shown, on the basis of fire tests, that such depths are adequate for the required rating.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 |
Required Fire-Resistance Rating of Assembly | Minimum Penetration, mm | |||
Walls | Ceilings | |||
Nails | Screws | Nails | Screws | |
Not required | 20 | 15 | 20 | 15 |
45 min | 20 | 20 | 30 | 30 |
1 h | 20 | 20 | 45 | 45 |
1.5 h | 20 | 20 | 60 | 60 |
9.29.5.6. — Nails
(1) Nails for fastening gypsum board to wood supports shall conform to CSA B111, “Wire Nails, Spikes and Staples”.
Text · e-Laws consolidated snapshot
9.29.5.7. — Screws
(1) Screws for fastening gypsum board to wood supports shall conform to ASTM C1002, “Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs”.
Text · e-Laws consolidated snapshot
9.29.5.8. — Spacing of Nails
(1) For single-layer application on ceilings, nails shall be spaced,
(a) not more than 180 mm o.c. on ceiling supports, or
(b) every 300 mm o.c. along ceiling supports, in pairs about 50 mm apart.
(2) Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent to nailing at this location.
(3) Except as required by Sentence (4), for single-layer application on walls, nails shall be spaced,
(a) not more than 200 mm o.c. on vertical wall supports, or
(b) every 300 mm o.c. along vertical wall supports, in pairs about 50 mm apart.
(4) For single-layer application on walls, where gypsum board is required to provide bracing, lateral support or fire protection, nails shall be spaced not more than 200 mm o.c. on,
(a) vertical wall supports, and
(b) top and bottom plates.
(5) The uppermost nails on vertical wall supports shall be not more than 200 mm below the ceiling.
(6) Nails shall be located not less than 10 mm from the side or edge of the board.
(7) Nails shall be driven so that the heads do not puncture the paper.
Text · e-Laws consolidated snapshot
9.29.5.9. — Spacing of Screws
(1) For single-layer application on a ceiling, screws shall be spaced not more than 300 mm o.c. on ceiling supports.
(2) Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent to screwing at this location.
(3) Except as required by Sentence (4), for single-layer application on walls, screws shall be spaced,
(a) not more than 300 mm o.c. on vertical wall supports where the supports are more than 400 mm o.c., or
(b) not more than 400 mm o.c. on vertical wall supports where the supports are not more than 400 mm o.c.
(4) Except as required by Sentence (5), for single-layer application on walls, where gypsum board is required to provide bracing, lateral support or fire protection, screws shall be spaced not more than 300 mm o.c. on,
(a) vertical wall supports, and
(b) top and bottom plates.
(5) Where a fire-resistance rating is determined based on Supplementary Standard SB-3, Sentence (4) need not apply for the purpose of fire protection.
(6) Screws shall be located not less than 10 mm from the side or edge of the board.
(7) Screws shall be driven so that the heads do not puncture the paper.
Text · e-Laws consolidated snapshot
9.29.5.10. — Low Temperature Conditions
(1) In cold weather, heat shall be provided to maintain a temperature of not below 10°C for 48 h prior to taping and finishing and maintained for not less than 48 h after that.
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · continues from 9.29.5. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.29.5. — Pro