9.24.2. — Size of Framing

Content not available for this version.

9.24.2.1. — Size and Spacing of Studs in Interior Walls

(1) Except as required in Articles 9.24.2.3. and 9.24.2.4., the size and spacing of steel studs for non-loadbearing interior walls shall conform to Table 9.24.2.1.

Text · e-Laws consolidated snapshot

Table 9.24.2.1. Steel Studs for Non-Loadbearing Interior Walls Forming Part of Sentence 9.24.2.1.(1)

Column 1

Column 2

Column 3

Minimum Stud Size, mm

Maximum Stud Spacing, mm

Maximum Wall Height, m

30 × 40

400

3.0

600

2.7

30 × 63

400

4.0

600

3.6

30 × 91

400

5.2

600

4.9

9.24.2.2. — Thickness of Studs

(1) Except as required in Article 9.24.2.4., steel studs in non-loadbearing interior walls shall have a metal thickness of not less than 0.46 mm.

Text · e-Laws consolidated snapshot

9.24.2.3. — Runners

(1) Runners for interior and exterior non-loadbearing walls shall have a thickness of not less than the thickness of the corresponding studs and shall have not less than 30 mm flanges.

Text · e-Laws consolidated snapshot

9.24.2.4. — Openings in Fire Separations

(1) Where openings for doors in non-loadbearing fire separations required to have a fire-resistance rating do not exceed 1 200 mm in width,

(a) the width of steel studs shall be not less than 63 mm, and

(b) the steel thickness shall be not less than 0.46 mm.

(2) Where openings described in Sentence (1) exceed 1 200 mm in width,

(a) the width of steel studs shall be not less than 91 mm, and

(b) the metal thickness shall be not less than 0.85 mm.

(3) The distance to the first stud beyond the jamb of any door opening in a fire separation required to have a fire-resistance rating shall not exceed 400 mm.

(4) Where the distance between the framing over the opening referred to in Sentence (3) and the top runner exceeds 400 mm in such walls, intermediate support shall be installed at intervals of not more than 400 mm above the opening.

Text · e-Laws consolidated snapshot

9.24.2.5. — Size and Spacing of Studs in Exterior Walls

(1) The size and spacing of non-loadbearing steel studs for exterior walls shall conform to Table 9.24.2.5.

Editor's note

As filed in O. Reg. 350/06, the column-heading row of Table 9.24.2.5. carries a typographical error: the second heading reads 'Column 1' (duplicating the first) where it should read 'Column 2'. The current e-Laws consolidation silently corrects this to 'Column 2', with no amending regulation making the change. This map preserves the heading as filed.

Text · e-Laws consolidated snapshot

Table 9.24.2.5. Size and Spacing of Steel Studs for Non-Loadbearing Exterior Walls Forming Part of Sentence 9.24.2.5.(1)

Column 1

Column 1

Column 3

Column 4

Column 5

Minimum Stud Size, mm

Minimum Metal

Thickness, mm

Maximum Stud Length, m

Spacing of Studs

300 mm (o.c.)

400 mm (o.c.)

600 mm (o.c.)

30 × 91

0.53

3.0

2.4

30 × 91

0.69

3.3

2.7

2.4

30 × 91

0.85

3.6

3.0

2.7

30 × 91

1.0

4.0

3.3

3.0